ClimateMaster Tranquility 22 (TY) Series Скачать руководство пользователя страница 7

7

c l i m a t e m a s t e r. c o m

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

Tr a n q u i l i t y

®

  2 2   ( T Y )   S e r i e s

R e v. :   1 2 / 1 7 / 1 4

Horizontal Installation

Mounting Horizontal Units

Horizontal units have hanger kits pre-installed from the 
factory as shown in Figure 1. Figure 3 shows a typical 
horizontal unit installation.

Horizontal heat pumps are typically suspended above 
a ceiling or within a soffi t using fi eld supplied, threaded 
rods sized to support the weight of the unit.

Use four (4) fi eld supplied threaded rods and factory 
provided vibration isolators to suspend the unit. Hang 
the unit clear of the fl oor slab above and support the 
unit by the mounting bracket assemblies only. DO NOT 
attach the unit fl ush with the fl oor slab above.

Pitch the unit toward the drain as shown in Figure 2 to 
improve the condensate drainage. On small units (less 
than 2.5 tons/8.8kW) ensure that unit pitch does not 
cause condensate leaks inside the cabinet.

Figure 1: Hanger Bracket

Figure 2: Horizontal Unit Pitch

>PP@7KUHDGHG

5RGE\RWKHUV

9LEUDWLRQ,VRODWRU

IDFWRU\VXSSOLHG

:DVKHU

E\RWKHUV

'RXEOH+H[1XWV

E\RWKHUV

1/4” (6.4mm) pitch
toward drain for drainage

Drain Connection

Horizontal Unit Location

Units are not designed for outdoor installation. Locate 
the unit in an INDOOR area that allows enough space 
for service personnel to perform typical maintenance or 
repairs without removing unit from the ceiling. Horizontal 
units are typically installed above a false ceiling or in a 
ceiling plenum. Never install units in areas subject to 
freezing or where humidity levels could cause cabinet 
condensation (such as unconditioned spaces subject 
to 100% outside air). Consideration should be given to 
access for easy removal of the fi lter and access panels. 
Provide suffi cient room to make water, electrical, and 
duct connection(s). 

If the unit is located in a confi ned space, such as a closet, 
provisions must be made for return air to freely enter the 
space by means of a louvered door, etc. Any access panel 
screws that would be diffi cult to remove after the unit 
is installed should be removed prior to setting the unit. 
Refer to Figure 3 for an illustration of a typical installation. 
Refer to unit submittal data or engineering design guide 
for dimensional data.

Conform to the following guidelines when selecting 
unit location:
1.  Provide a hinged access door in concealed-spline 

or plaster ceilings. Provide removable ceiling 
tiles in T-bar or lay-in ceilings. Refer to horizontal 
unit dimensions for specifi c series and model in 
unit submittal data. Size the access opening to 
accommodate the service technician during the 
removal or replacement of the compressor and the 
removal or installation of the unit itself.

2.  Provide access to hanger brackets, water valves and 

fi ttings. Provide screwdriver clearance to access 
panels, discharge collars and all electrical connections.

3.  DO NOT obstruct the space beneath the unit with 

piping, electrical cables and other items that prohibit 
future removal of components or the unit itself.

4.  Use a manual portable jack/lift to lift and support the 

weight of the unit during installation and servicing.

The installation of water source heat pump units and all 
associated components, parts and accessories which 
make up the installation shall be in accordance with 
the regulations of ALL authorities having jurisdiction 
and MUST conform to all applicable codes. It is the 
responsibility of the installing contractor to determine 
and comply with ALL applicable codes and regulations.

Содержание Tranquility 22 (TY) Series

Страница 1: ...ge Wiring 22 Electrical Low Voltage Wiring 23 Electrical Low Voltage Wiring for Units Using External Motorized Water Valve 24 Electrical Thermostat Wiring 25 Blower Performance Data 26 ECM Blower Cont...

Страница 2: ...2 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 This Page Intentionally Left Blank...

Страница 3: ...al Up CONFIGURATION Standard Copper Cupro Nickel A J 0 None WATER CIRCUIT OPTIONS S 15 S Standard STANDARD H Horizontal 036 042 Supply Configuration Motor T TYV B TYH S TYH Top Back Straight ECM ECM E...

Страница 4: ...ion of installation operation or maintenance information which is important but which is not hazard related Inspection Upon receipt of the equipment carefully check the shipment against the bill of la...

Страница 5: ...before installing any of the system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each uni...

Страница 6: ...w in mm 20 X 17 25 20 X 17 25 24 X 21 75 24 X 21 75 24x28 25 24x28 25 Standard Filter 1 25 4mm Throwaway qty in mm 20x20 20x20 24x24 24x24 1 14x24 1 18x24 1 14x24 1 18x24 Weight Operating lbs kg 189...

Страница 7: ...n should be given to access for easy removal of the filter and access panels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a...

Страница 8: ...g Vertical WSHPs are commonly installed in a mechanical room with free return e g louvered door Therefore filter rails are the industry standard and are included on ClimateMaster commercial heat pumps...

Страница 9: ...ft out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or...

Страница 10: ...re than other units connected to the same condensate main since this may cause poor drainage for all units on the line WHEN A VENT IS INSTALLED IN THE DRAIN LINE IT MUST BE LOCATED AFTER THE TRAP IN T...

Страница 11: ...etc Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figures 7 and 8 for typical installation illustrations Re...

Страница 12: ...low for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trapping loop therefore an external trap is not nec...

Страница 13: ...h unheated areas outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops b...

Страница 14: ...chips and other foreign material prior to operation see Piping System Cleaning and Flushing Procedures in this manual The flow rate is usually set between 2 25 and 3 5 gpm per ton 2 9 and 4 5 l m per...

Страница 15: ...t to freezing antifreeze is required Alcohols and glycols are commonly used as antifreeze however your local sales office should be consulted to determine the antifreeze best suited to your area Freez...

Страница 16: ...ockouts Vibration Isolation Pad To Thermostat Water Out Shut Off Ball Valves for Isolation Water In Ground Water Heat Pump Applications Typical Open Loop Well High and Low Voltage Knockouts Vibration...

Страница 17: ...ilding and zoning department to assure compliance in your area Water Control Valve Always maintain water pressure in the heat exchanger by placing the water control valve s on the discharge line to pr...

Страница 18: ...method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typically a brass fitting with an orifice of rubber or plastic material that is des...

Страница 19: ...loride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particul...

Страница 20: ...Voltage Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR RLA LRA Qty 024 G 208 230 60 1 197 252 11 7 58 3 1 3 9 15 6 18 5 30 E 265 60 1 239 292 9 1 54 0 1 3 2 12 3 14 6 20 H 208 230...

Страница 21: ...of flexible conduit to minimize vibration and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate L...

Страница 22: ...tor is located on the refrigerant line between the coaxial heat exchanger and expansion device TXV Therefore LT1 is sensing refrigerant temperature not water temperature which is a better indication o...

Страница 23: ...d water installations to shut off flow to the unit when the compressor is not operating A slow closing valve may be required to help reduce water hammer Figure 18 shows typical wiring for a 24VAC exte...

Страница 24: ...Units Using External Motorized Water Valve Figure 19 AVM Valve Wiring Figure 20 Taco SBV Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown S...

Страница 25: ...lly any heat pump thermostat will work with ClimateMaster units provided it has the correct number of heating and cooling stages Electrical Thermostat Wiring Field Wiring Factory Wiring Figure 22a Con...

Страница 26: ...mum 750 525 750 525 750 525 375 750 036 0 6 1 2 Default 1125 750 975 650 1125 750 525 1125 Maximum 1250 950 1200 800 1250 1250 1250 1250 Minimum 900 600 900 600 900 600 450 900 042 0 6 3 4 Default 130...

Страница 27: ...Cooling in Dehumidification Mode Y1 Y2 O Dehumid First Stage Heating Y1 Second Stage Heating Y1 Y2 Third Stage Auxiliary Heating Y1 Y2 W Emergency Heating W with no Y1 or Y2 Fan G with no Y1 Y2 or W I...

Страница 28: ...28 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 Typical Wiring Diagram Single Phase Units...

Страница 29: ...29 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility 22 T Y Ser ies R ev 1 2 1 7 1 4 Typical Wiring Diagram Single Phase Unit with MPC Controller...

Страница 30: ...30 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 Typical Wiring Diagram Three Phase Units...

Страница 31: ...election of compressor relay staging operation The compressor relay can be selected to turn on with a stage 1 or stage 2 call from the thermostat This is used with dual stage units 2 compressors where...

Страница 32: ...e selection unless instructed to do so by the factory Table 7a Accessory DIP Switch Settings DIP Package 3 S3 DIP Package 3 has 4 switches and provides the following setup and operating selections 3 1...

Страница 33: ...Status Operation with Test Mode Active Fault LED Red Status LED Green Alarm Relay No Fault Since Power Up In Memory Flashing Code 1 Cycling Code 1 High Pressure Fault In Memory Flashing Code 2 Cycling...

Страница 34: ...4 5 6 7 8 1 2 3 4 5 6 7 8 Service tool connection Communicating stat connection Conventional stat connection Cabinet temperature sensor with variable speed pump 24V to compressor second stage solenoi...

Страница 35: ...e compressor 2nd stage fan operation reversing valve DXM2 Controls Figure 26b Test Mode Button Table 7c Unit Operation DXM2 Control Start up Operation The control will not operate until all inputs and...

Страница 36: ...65 70 158 0 1 75 1 33 8 31 03 71 159 8 1 69 2 35 6 29 50 72 161 6 1 64 3 37 4 28 05 73 163 4 1 58 4 39 2 26 69 74 165 2 1 53 5 41 0 25 39 75 167 0 1 48 6 42 8 24 17 76 168 8 1 43 7 44 6 23 02 77 170...

Страница 37: ...C 50 110 F 10 43 3 C 120 F 48 9 C 20 F 6 7 C 30 80 F 1 1 26 7 C 90 F 32 2 C Normal Water Flow 1 5 to 3 0 gpm ton 1 6 to 3 2 l m per kW Unit Starting and Operating Conditions Operating Limits Environm...

Страница 38: ...0 gallons 8 kg per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the...

Страница 39: ...fittings see table 3 System flushing Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger water valves and other components Water used in...

Страница 40: ...ure drop across the heat exchanger to table 10 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperatur...

Страница 41: ...F 27 19 C in cooling Subcooling is based upon head pressure at compressor service port Cooling air and water values can vary greatly with changes in humidity level Model GPM Pressure Drop psi 30 F 50...

Страница 42: ...7 22 88 98 96 106 105 115 353 373 361 381 370 390 6 11 8 13 9 14 12 17 12 17 12 17 13 2 15 2 9 0 11 0 4 8 6 8 24 29 25 30 26 31 70 1 5 2 25 3 128 138 124 134 119 129 328 348 300 320 273 293 8 13 9 14...

Страница 43: ...7 7 12 7 12 8 13 10 15 10 15 10 15 8 4 10 4 6 0 8 0 3 6 5 6 19 24 20 25 20 25 50 1 5 2 25 3 120 130 120 130 118 128 225 245 222 242 220 240 9 14 9 14 9 14 13 18 10 15 9 14 21 8 23 8 14 7 16 7 8 7 10 7...

Страница 44: ...motor and reduce air flow resulting in poor performance It is especially important to provide consistent washing of these filters in the opposite direction of the normal air flow once per month using...

Страница 45: ...s are paired wires connecting each component to the board Therefore continuity on pressure switches for example can be checked at the board connector The thermistor resistance should be measured with...

Страница 46: ...aller menu For more detailed information on the advanced diagnostics of the DXM2 see the DXM2 Application Operation and Maintenance AOM manual part 97B0003N15 DXM2 Troubleshooting Process Flowchart Fu...

Страница 47: ...Start Did Unit Lockout at Start up Unit Short Cycles Only Fan Runs Only Compressor Runs Did unit lockout after a period of operation Does unit operate in cooling Unit is OK See Performance Troubleshoo...

Страница 48: ...rature limit setting 30 F vs 10 F 1 C vs 12 C Normal airside applications will require 30 F 1 C only X X Bad thermistor Check temp and impedance correlation per chart Condensate Fault Code 6 X X Block...

Страница 49: ...ard Reset power and check operation Unit Short Cycles X X Dirty air filter Check and clean air filter Unit in Test Mode Reset power or wait 20 minutes for auto exit Unit selection Unit may be oversize...

Страница 50: ...airflow restrictions Too high of external static check static vs blower table X Reduced or no water flow Check pump operation or valve operation setting in cooling Check water flow adjust to proper fl...

Страница 51: ...pressor and electric heat Unit Doesn t Operate in Cooling X Reversing Valve Set for cooling demand and check 24VAC on RV coil If RV is stuck run high pressure up by reducing water flow and while opera...

Страница 52: ...or CFM Settings ECM Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Tempera...

Страница 53: ...1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 27 5 6 2 75...

Страница 54: ...t of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to...

Страница 55: ...or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or un...

Страница 56: ...T E R T O AIR BRI N E T O A I R 97B0075N15 97B0075N15 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com ClimateMaster Inc 2009 ClimateMaster works conti...

Отзывы: