26
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
2 2 ( T Y ) S e r i e s
R e v. : 1 2 / 1 7 / 1 4
Blower Performance Data
TY Standard Unit - No Reheat
Model
Max ESP
(in wg)
Fan
Motor
(hp)
Range
Cooling Mode
Dehumid Mode
Heating Mode
Fan Only
Mode
Aux Emerg
Mode
Stg 2
Stg 1
Stg 2
Stg 1
Stg 2
Stg 1
024
0.75
1/2
Default
750
575
650
500
750
575
350
750
Maximum
850
650
800
600
850
850
850
850
Minimum
600
450
600
450
600
450
300
650
030
0.5
1/2
Default
950
650
800
575
950
650
450
950
Maximum
1100
750
1000
700
1100
1100
1100
1100
Minimum
750
525
750
525
750
525
375
750
036
0.6
1/2
Default
1125
750
975
650
1125
750
525
1125
Maximum
1250
950
1200
800
1250
1250
1250
1250
Minimum
900
600
900
600
900
600
450
900
042
0.6
3/4
Default
1300
925
1125
825
1300
925
600
1300
Maximum
1475
1100
1400
1000
1475
1475
1475
1475
Minimum
1050
750
1050
750
1050
750
525
1050
048
0.75
3/4
Default
1500
1125
1300
975
1500
1125
700
1500
Maximum
1700
1300
1600
1200
1700
1700
1700
1700
Minimum
1200
900
1200
900
1200
900
600
1350
060
0.75
1
Default
1875
1500
1625
1300
1875
1500
875
1875
Maximum
2100
1700
2000
1600
2100
2100
2100
2100
Minimum
1500
1200
1500
1200
1500
1200
750
1500
Airfl ow is controlled within 5% up to the Max ESP shown with wet coil.
Performance shown is with wet coil and factory air fi lters.