C l i m a t e M a s t e r W a t e r- S o u r c e H e a t P u m p s
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tr a n q u i l i t y
®
2 2 ( T Y ) S e r i e s
R e v. : 1 2 / 1 7 / 1 4
DXM2 Controls
On = normal. O
ff
= Boilerless operation.
1.8
– Boilerless changeover temperature: DIP 1.8
provides selection of boilerless changeover temperature
setpoint. Note that the LT1 thermistor is sensing
refrigerant temperature between the coaxial heat
exchanger and the expansion device (TXV). Therefore,
the 50°F [10°C] setting is not 50°F [10°C] water, but
approximately 60°F [16°C] EWT.
On = 50°F [10°C]. O
ff
= 40°F [16°C].
DIP Package #2 (S2)
– A combination of dip switches
2.1, 2.2, 2.3, and 2.4, 2.5, 2.6 deliver confi guration of
ACC1 and ACC2 relay options respectively. See Table 7a
for description and functionality
.
2.7
– Auto dehumidifi cation fan mode or high fan mode:
DIP 2.7 provides selection of auto dehumidifi cation fan
mode or high fan mode. In auto dehumidifi cation mode,
the fan speed relay will remain off during cooling stage 2
IF the H input is active. In high fan mode, the fan enable
and fan speed relays will turn on when the H input is
active.
On = Auto dehumidifi cation mode (default). Off = High
fan mode.
2.8
– Special factory selection: DIP 2.8 provides special
factory selection. Normal position is “On”. Do not
change selection unless instructed to do so by the
factory.
Table 7a: Accessory DIP Switch Settings
DIP Package #3 (S3)
– DIP Package #3 has 4 switches and provides the
following setup and operating selections:
3.1
– Communications confi guration: DIP 3.1 provides
selection of the DXM2 operation in a communicating
system. The DXM2 may operate as the Master of certain
network confi gurations. In most confi gurations the
DXM2 will operate as a master device.
On = Communicating Master device (default). Off =
communicating Slave device.
3.2
– HWG Test Mode: DIP 3.2 provides forced operation
of the HWG pump output, activating the HWG pump
output for up to fi ve minutes.
On = HWG test mode. Off = Normal HWG mode
(default).
3.3
– HWG Temperature: DIP 3.3 provides the selection
of the HWG operating setpoint.
On = 150°F [66°C]. Off = 125°F [52°C] (default).
3.4
– HWG Status: DIP 3.4 provides HWG operation
control.
On = HWG mode enabled. Off = HWG mode disabled
(default).
CAUTION!
CAUTION!
Do not restart units without inspection and
remedy of faulting condition. Equipment damage may occur.
DIP 2.1
DIP 2.2
DIP 2.3
ACC1 Relay Option
On
On
On
Cycle with fan
Off
On
On
Digital NSB
On
Off
On
Water Valve - slow opening
On
On
Off
OAD
Off
Off
Off
Reheat Option - Humidistat
Off
On
Off
Reheat Option - Dehumidistat
DIP 2.4
DIP 2.5
DIP 2.6
ACC2 Relay Option
On
On
On
Cycle with compressor
Off
On
On
Digital NSB
On
Off
On
Water Valve - slow opening
On
On
Off
OAD
(SSV[OLY+07JVTIPUH[PVUZHYLPU]HSPK