ClimateMaster Tranquility 22 (TY) Series Скачать руководство пользователя страница 39

39

c l i m a t e m a s t e r. c o m

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

Tr a n q u i l i t y

®

  2 2   ( T Y )   S e r i e s

R e v. :   1 2 / 1 7 / 1 4

Unit and System Checkout

Unit and System Checkout

BEFORE POWERING SYSTEM, please check the following:

UNIT CHECKOUT

 

Balancing/shutoff valves: Ensure that all isolation 
valves are open and water control valves are wired.

 

Line voltage and wiring: Verify that voltage is within 
an acceptable range for the unit and wiring and 
fuses/breakers are properly sized. Verify that low 
voltage wiring is complete

.

 

Unit control transformer: Ensure that transformer has 
the properly selected voltage tap. 

 

Entering water and air: Ensure that entering water 
and air temperatures are within operating limits of 
Table 9a-b.

 

Low water temperature cutout: Verify that low water 
temperature cut-out on the DXM2 control is properly 
set

.

 

Unit fan: Manually rotate fan to verify free rotation 
and ensure that blower wheel is secured to the 
motor shaft. Be sure to remove any shipping 
supports if needed. DO NOT oil motors upon start-
up. Fan motors are pre-oiled at the factory. Check 
unit fan speed selection and compare to design 
requirements.

 

Condensate line: Verify that condensate line is open 
and properly pitched toward drain

.

 

Water fl ow balancing: Record inlet and outlet water 
temperatures for each heat pump upon startup. 
This check can eliminate nuisance trip outs and 
high velocity water fl ow that could erode heat 
exchangers.

 

Unit air coil and fi lters: Ensure that fi lter is clean and 
accessible. Clean air coil of all manufacturing oils

.

 

Unit controls: Verify that DXM2 fi eld selection 
options are properly set.

SYSTEM CHECKOUT

  System water temperature: Check water temperature 

for proper range and also verify heating and cooling 
set points for proper operation.

 

System pH: Check and adjust water pH if necessary 
to maintain a level between 6 and 8.5. Proper pH 
promotes longevity of hoses and fi ttings (see table 3).

 System 

fl ushing: Verify that all hoses are connected 

end to end when fl ushing to ensure that debris 
bypasses the unit heat exchanger, water valves and 
other components. Water used in the system must be 
potable quality initially and clean of dirt, piping slag, 
and strong chemical cleaning agents. Verify that all 
air is purged from the system. Air in the system can 
cause poor operation or system corrosion.

  Cooling tower/boiler: Check equipment for proper 

setpoints and operation.

  Standby pumps: Verify that the standby pump is 

properly installed and in operating condition

.

 

System controls: Verify that system controls function 
and operate in the proper sequence

.

 

Low water temperature cutout: Verify that low water 
temperature cut-out controls are provided for the 
outdoor portion of the loop. Otherwise, operating 
problems may occur.

 

System control center: Verify that the control center 
and alarm panel have appropriate setpoints and are 
operating as designed.

 

Miscellaneous: Note any questionable aspects of the 
installation.

CAUTION! 

Verify that ALL water control valves are open and 

allow water fl ow prior to engaging the compressor. Freezing 
of the coax or water lines can permanently damage the heat 
pump.

NOTICE! Failure to remove shipping brackets from 
spring-mounted compressors will cause excessive 
noise, and could cause component failure due to 
added vibration.

CAUTION! 

To avoid equipment damage, DO NOT 

leave system fi lled in a building without heat during the 
winter unless antifreeze is added to the water loop. Heat 
exchangers never fully drain by themselves and will freeze 
unless winterized with antifreeze.

 

CAUTION!

 

 

CAUTION!

 

WARNING! 

Polyolester Oil, commonly known as POE oil, is 

a synthetic oil used in many refrigeration systems including 
those with HFC-410A refrigerant. POE oil, if it ever comes 
in contact with PVC or CPVC piping, may cause failure of 
the PVC/CPVC. PVC/CPVC piping should never be used 
as supply or return water piping with water source heat 
pump products containing HFC-410A as system failures and 
property damage may result.

 

WARNING!

 

Содержание Tranquility 22 (TY) Series

Страница 1: ...ge Wiring 22 Electrical Low Voltage Wiring 23 Electrical Low Voltage Wiring for Units Using External Motorized Water Valve 24 Electrical Thermostat Wiring 25 Blower Performance Data 26 ECM Blower Cont...

Страница 2: ...2 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 This Page Intentionally Left Blank...

Страница 3: ...al Up CONFIGURATION Standard Copper Cupro Nickel A J 0 None WATER CIRCUIT OPTIONS S 15 S Standard STANDARD H Horizontal 036 042 Supply Configuration Motor T TYV B TYH S TYH Top Back Straight ECM ECM E...

Страница 4: ...ion of installation operation or maintenance information which is important but which is not hazard related Inspection Upon receipt of the equipment carefully check the shipment against the bill of la...

Страница 5: ...before installing any of the system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each uni...

Страница 6: ...w in mm 20 X 17 25 20 X 17 25 24 X 21 75 24 X 21 75 24x28 25 24x28 25 Standard Filter 1 25 4mm Throwaway qty in mm 20x20 20x20 24x24 24x24 1 14x24 1 18x24 1 14x24 1 18x24 Weight Operating lbs kg 189...

Страница 7: ...n should be given to access for easy removal of the filter and access panels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a...

Страница 8: ...g Vertical WSHPs are commonly installed in a mechanical room with free return e g louvered door Therefore filter rails are the industry standard and are included on ClimateMaster commercial heat pumps...

Страница 9: ...ft out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension or...

Страница 10: ...re than other units connected to the same condensate main since this may cause poor drainage for all units on the line WHEN A VENT IS INSTALLED IN THE DRAIN LINE IT MUST BE LOCATED AFTER THE TRAP IN T...

Страница 11: ...etc Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figures 7 and 8 for typical installation illustrations Re...

Страница 12: ...low for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trapping loop therefore an external trap is not nec...

Страница 13: ...h unheated areas outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops b...

Страница 14: ...chips and other foreign material prior to operation see Piping System Cleaning and Flushing Procedures in this manual The flow rate is usually set between 2 25 and 3 5 gpm per ton 2 9 and 4 5 l m per...

Страница 15: ...t to freezing antifreeze is required Alcohols and glycols are commonly used as antifreeze however your local sales office should be consulted to determine the antifreeze best suited to your area Freez...

Страница 16: ...ockouts Vibration Isolation Pad To Thermostat Water Out Shut Off Ball Valves for Isolation Water In Ground Water Heat Pump Applications Typical Open Loop Well High and Low Voltage Knockouts Vibration...

Страница 17: ...ilding and zoning department to assure compliance in your area Water Control Valve Always maintain water pressure in the heat exchanger by placing the water control valve s on the discharge line to pr...

Страница 18: ...method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typically a brass fitting with an orifice of rubber or plastic material that is des...

Страница 19: ...loride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particul...

Страница 20: ...Voltage Compressor Fan Motor FLA Total Unit FLA Min Circ Amp Max Fuse HACR RLA LRA Qty 024 G 208 230 60 1 197 252 11 7 58 3 1 3 9 15 6 18 5 30 E 265 60 1 239 292 9 1 54 0 1 3 2 12 3 14 6 20 H 208 230...

Страница 21: ...of flexible conduit to minimize vibration and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate L...

Страница 22: ...tor is located on the refrigerant line between the coaxial heat exchanger and expansion device TXV Therefore LT1 is sensing refrigerant temperature not water temperature which is a better indication o...

Страница 23: ...d water installations to shut off flow to the unit when the compressor is not operating A slow closing valve may be required to help reduce water hammer Figure 18 shows typical wiring for a 24VAC exte...

Страница 24: ...Units Using External Motorized Water Valve Figure 19 AVM Valve Wiring Figure 20 Taco SBV Valve Wiring From Water Source IN OUT NOTE Shut off valves strainers and other required components not shown S...

Страница 25: ...lly any heat pump thermostat will work with ClimateMaster units provided it has the correct number of heating and cooling stages Electrical Thermostat Wiring Field Wiring Factory Wiring Figure 22a Con...

Страница 26: ...mum 750 525 750 525 750 525 375 750 036 0 6 1 2 Default 1125 750 975 650 1125 750 525 1125 Maximum 1250 950 1200 800 1250 1250 1250 1250 Minimum 900 600 900 600 900 600 450 900 042 0 6 3 4 Default 130...

Страница 27: ...Cooling in Dehumidification Mode Y1 Y2 O Dehumid First Stage Heating Y1 Second Stage Heating Y1 Y2 Third Stage Auxiliary Heating Y1 Y2 W Emergency Heating W with no Y1 or Y2 Fan G with no Y1 Y2 or W I...

Страница 28: ...28 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 Typical Wiring Diagram Single Phase Units...

Страница 29: ...29 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility 22 T Y Ser ies R ev 1 2 1 7 1 4 Typical Wiring Diagram Single Phase Unit with MPC Controller...

Страница 30: ...30 ClimateMaster Water Source Heat Pumps CL I MATEM ASTER WATER SOURCE HEAT PUMPS Tran q u i l i t y 22 TY Series Rev 12 17 14 Typical Wiring Diagram Three Phase Units...

Страница 31: ...election of compressor relay staging operation The compressor relay can be selected to turn on with a stage 1 or stage 2 call from the thermostat This is used with dual stage units 2 compressors where...

Страница 32: ...e selection unless instructed to do so by the factory Table 7a Accessory DIP Switch Settings DIP Package 3 S3 DIP Package 3 has 4 switches and provides the following setup and operating selections 3 1...

Страница 33: ...Status Operation with Test Mode Active Fault LED Red Status LED Green Alarm Relay No Fault Since Power Up In Memory Flashing Code 1 Cycling Code 1 High Pressure Fault In Memory Flashing Code 2 Cycling...

Страница 34: ...4 5 6 7 8 1 2 3 4 5 6 7 8 Service tool connection Communicating stat connection Conventional stat connection Cabinet temperature sensor with variable speed pump 24V to compressor second stage solenoi...

Страница 35: ...e compressor 2nd stage fan operation reversing valve DXM2 Controls Figure 26b Test Mode Button Table 7c Unit Operation DXM2 Control Start up Operation The control will not operate until all inputs and...

Страница 36: ...65 70 158 0 1 75 1 33 8 31 03 71 159 8 1 69 2 35 6 29 50 72 161 6 1 64 3 37 4 28 05 73 163 4 1 58 4 39 2 26 69 74 165 2 1 53 5 41 0 25 39 75 167 0 1 48 6 42 8 24 17 76 168 8 1 43 7 44 6 23 02 77 170...

Страница 37: ...C 50 110 F 10 43 3 C 120 F 48 9 C 20 F 6 7 C 30 80 F 1 1 26 7 C 90 F 32 2 C Normal Water Flow 1 5 to 3 0 gpm ton 1 6 to 3 2 l m per kW Unit Starting and Operating Conditions Operating Limits Environm...

Страница 38: ...0 gallons 8 kg per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the...

Страница 39: ...fittings see table 3 System flushing Verify that all hoses are connected end to end when flushing to ensure that debris bypasses the unit heat exchanger water valves and other components Water used in...

Страница 40: ...ure drop across the heat exchanger to table 10 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperatur...

Страница 41: ...F 27 19 C in cooling Subcooling is based upon head pressure at compressor service port Cooling air and water values can vary greatly with changes in humidity level Model GPM Pressure Drop psi 30 F 50...

Страница 42: ...7 22 88 98 96 106 105 115 353 373 361 381 370 390 6 11 8 13 9 14 12 17 12 17 12 17 13 2 15 2 9 0 11 0 4 8 6 8 24 29 25 30 26 31 70 1 5 2 25 3 128 138 124 134 119 129 328 348 300 320 273 293 8 13 9 14...

Страница 43: ...7 7 12 7 12 8 13 10 15 10 15 10 15 8 4 10 4 6 0 8 0 3 6 5 6 19 24 20 25 20 25 50 1 5 2 25 3 120 130 120 130 118 128 225 245 222 242 220 240 9 14 9 14 9 14 13 18 10 15 9 14 21 8 23 8 14 7 16 7 8 7 10 7...

Страница 44: ...motor and reduce air flow resulting in poor performance It is especially important to provide consistent washing of these filters in the opposite direction of the normal air flow once per month using...

Страница 45: ...s are paired wires connecting each component to the board Therefore continuity on pressure switches for example can be checked at the board connector The thermistor resistance should be measured with...

Страница 46: ...aller menu For more detailed information on the advanced diagnostics of the DXM2 see the DXM2 Application Operation and Maintenance AOM manual part 97B0003N15 DXM2 Troubleshooting Process Flowchart Fu...

Страница 47: ...Start Did Unit Lockout at Start up Unit Short Cycles Only Fan Runs Only Compressor Runs Did unit lockout after a period of operation Does unit operate in cooling Unit is OK See Performance Troubleshoo...

Страница 48: ...rature limit setting 30 F vs 10 F 1 C vs 12 C Normal airside applications will require 30 F 1 C only X X Bad thermistor Check temp and impedance correlation per chart Condensate Fault Code 6 X X Block...

Страница 49: ...ard Reset power and check operation Unit Short Cycles X X Dirty air filter Check and clean air filter Unit in Test Mode Reset power or wait 20 minutes for auto exit Unit selection Unit may be oversize...

Страница 50: ...airflow restrictions Too high of external static check static vs blower table X Reduced or no water flow Check pump operation or valve operation setting in cooling Check water flow adjust to proper fl...

Страница 51: ...pressor and electric heat Unit Doesn t Operate in Cooling X Reversing Valve Set for cooling demand and check 24VAC on RV coil If RV is stuck run high pressure up by reducing water flow and while opera...

Страница 52: ...or CFM Settings ECM Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Tempera...

Страница 53: ...1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 27 5 6 2 75...

Страница 54: ...t of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to...

Страница 55: ...or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or un...

Страница 56: ...T E R T O AIR BRI N E T O A I R 97B0075N15 97B0075N15 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com ClimateMaster Inc 2009 ClimateMaster works conti...

Отзывы: