Electrical - Line Voltage
Electrical - Line Voltage
- All fi eld installed wiring,
including electrical ground, must comply with the National
Electrical Code as well as all applicable local codes. Refer
to the unit electrical data for fuse sizes. Consult wiring
diagram for fi eld connections that must be made by
the installing (or electrical) contractor. All fi nal electrical
connections must be made with a length of fl exible conduit
to minimize vibration and sound transmission to the
building.
General Line Voltage Wiring
- Be sure the available
power is the same voltage and phase shown on the unit
serial plate. Line and low voltage wiring must be done in
accordance with local codes or the National Electric Code,
whichever is applicable.
WARNING!
To avoid possible injury or death due to electrical
shock, open the power supply disconnect switch and secure
it in an open position during installation.
CAUTION!
Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
WARNING!
CAUTION!
Transformer
- All 208/230 voltage units are factory wired
for 208 volt. If supply voltage is 230 volt, installer must
rewire transformer. See wire diagram for connections.
Standard Unit
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan Motor
FLA
Total Unit
FLA
Min Circ
Amp
Max Fuse/
HACR
RLA
LRA
Qty
024
G
208/230/60/1
197/252
11.7
58.3
1
3.9
15.6
18.5
30
E 265/60/1
239/292
9.1
54.0
1
3.2
12.3
14.6
20
H
208/230/60/3
197/252
6.5
55.4
1
3.9
10.4
12.0
15
F*
460/60/3*
414/506
3.5
28.0
1
3.2
6.7
7.6
15
030
G
208/230/60/1
197/252
13.1
73.0
1
3.9
17.0
20.3
30
E 265/60/1
239/292
10.2
60.0
1
3.2
13.4
16.0
25
H
208/230/60/3
197/252
8.7
58.0
1
3.9
12.6
14.8
20
F*
460/60/3*
414/506
4.3
28.0
1
3.2
7.5
8.6
15
036
G
208/230/60/1
197/252
15.3
83.0
1
3.9
19.2
23.0
35
E 265/60/1
239/292
13.0
72.0
1
3.2
16.2
19.5
30
H
208/230/60/3
197/252
11.6
73.0
1
3.9
15.5
18.4
30
F*
460/60/3*
414/506
5.7
38.0
1
3.2
8.9
10.3
15
042
G
208/230/60/1
197/252
17.9
96.0
1
5.2
23.1
27.6
45
H
208/230/60/3
197/252
14.2
88.0
1
5.2
19.4
23.0
35
F*
460/60/3*
414/506
6.2
44.0
1
4.7
10.9
12.5
15
048
G
208/230/60/1
197/252
21.2
104.0
1
5.2
26.4
31.7
50
E 265/60/1
239/292
16.0
109.7
1
4.7
20.7
24.7
40
H
208/230/60/3
197/252
14.0
83.1
1
5.2
19.2
22.7
35
F*
460/60/3*
414/506
6.4
41.0
1
4.7
11.1
12.7
15
060
G
208/230/60/1
197/252
27.1
152.9
1
6.9
34.0
40.8
60
E 265/60/1
239/292
22.4
130.0
1
6.0
28.4
34.0
50
H
208/230/60/3
197/252
16.5
110.0
1
6.9
23.4
27.5
40
F*
460/60/3*
414/506
7.2
52.0
1
6.0
13.2
15.0
20
HACR circuit breaker in USA only
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units require a four wire power supply with neutral. ECM motor is rated
265 vac and is wired between one hot leg and neutral.