background image

iGate

®

 Connect Programmable Thermostat

R e v i s e d :   D e c e m b e r   2 0 ,   2 0 2 1

C l i m a t e M a s t e r   Wa t e r-S o u rc e   H e a t   P u m p s

4

C L I M AT E M A S T E R  WAT E R - S O U R C E   H E AT   P U M P S

TIP: 

Wrap the wires around a pen or 

pencil to keep them from falling inside  

the wall.

4.  Remove the current backplate. 

5.  Mount the new base.

a.  Gently separate the display from the base of the 

new thermostat by pulling thermostat straight 

away from the base. 

b.  Position the base against the wall and determine 

if wall anchors from current thermostat align with 

screw locations of new base. 

c.  If base does not align with existing anchor holes, 

mark new screw locations with a pencil. 

•  Drywall: Drill 3/16” hole for the anchor. 

•  Plaster: Drill 7/32” hole for the anchor. 

d.  Pull wires through opening in base and secure to 

the wall using provided screws. 

TIP: 

Use a level to ensure thermostat 

is properly aligned.

 

6.  Connect wires. 

a.  Match your wire configuration to the terminals on 

the base. Reference Diagram 1.

b.  Connect each wire individually by pushing down 

on the quick connect tab, inserting the wire into 

the connector opening, and then releasing the tab. 

c.  If remote indoor and/or outdoor sensors are used, 

they may be connected at this time. 

TIP: 

Use pliers to straighten wire before 

inserting into new base. Be sure to cut any 

excess wire so that the insulation extends 

to the terminal block. When the wire is 

installed properly to the terminal block, 

there should be no copper exposed.

22 AWG shielded wire is required when installing a 

remote sensor further than 100 ft (30.5 meters). 

7.  Attach the thermostat face. 

a.  Align the thermostat face using hinge guide on top.

b.  Rotate the thermostat down until tab aligns with 

hole in base. 

c.  Install security screw if necessary.

8.  Return power to system.

Wiring Diagram

All excess wire should be pushed back into the wall as far 

as possible.

A+

B-

C

R

S1

S2

Thermostat

Remote

Sensor

R

B-
C

A+

Unit Control

Diagram 1: Thermostat Connections

Thermostat Connections

A+  Communications (Positive)

B–  Communications (Negative)

C  24V Common for Control Circuit

R  24V Supply for Control Circuit

S

1

  Remote Sensor

S

2

  Remote Sensor 

SYSTEM CONFIGURATION

From the thermostat display:

1.  To configure the System Settings using the myUplink 

PRO mobile app, set the thermostat System Mode 

 

to “OFF”.

2.  Swipe left or right on the thermostat screen until you 

reach the Fan screen. 

3.  Press the Fan button for 5 seconds to enable the 

“System Settings” screen. 

4.  Scroll down to select the “AP Access” option. 

5.  Select “YES” to enable.

 

From the myUplink PRO app:

6.  With your mobile device within 15 ft of the 

thermostat, open and login to your myUplink 

 

PRO app. 

7.  From the Systems screen, select the green “add” 

button at the top right.

8.  Select the “Connect Locally”. The app will find any 

devices in Access Point mode. 

Содержание iGate AWC99U01

Страница 1: ...ystem Configuration 4 Thermostat Settings 5 User Settings 5 Alert Configuration 6 System Settings 7 Equipment Settings 8 Configuration 8 Clear Fault History 11 Unit Manual Operation 12 Operating Infor...

Страница 2: ...ASTER WATER SOURCE HEAT PUMPS These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause th...

Страница 3: ...lose to or in a frequently used room preferably on an inside partitioning wall On a section of wall without pipes or duct work Thermostat should NOT be mounted Close to a window on an outside wall or...

Страница 4: ...re so that the insulation extends to the terminal block When the wire is installed properly to the terminal block there should be no copper exposed 22 AWG shielded wire is required when installing a r...

Страница 5: ...ng the user to enter a 4 digit security PIN Disabled Enabled Disabled Security PIN requires Security to be enabled 4 digit security PIN for restricting access 0000 9999 Active Backlight Adjusts the ba...

Страница 6: ...sensor can detect presence but also increases the possibility of a false presence High Medium Low Medium Wireless Configures Wi Fi functionality of the thermostat Enabled Disabled Enabled If disabled...

Страница 7: ...lected amount 5 F to 5 F in 1 F increments 2 5 C to 2 5 C in 0 5 C increments 0 F 0 C Humidity Offset Allows for calibration of the humidity sensor by the selected amount 9 to 9 in 1 increments 0 Remo...

Страница 8: ...onnecting the Wi Fi requires setting up the thermostat using the myUplink mobile application in order to re establish Wi Fi connectivity Disabling this function after the thermostat has been set up an...

Страница 9: ...the cooling mode will be sent to the source ground loop 70 to 100 100 Heating Hot Water Cut Out Potable water heating normally takes priority over space heating This setting determines the point at wh...

Страница 10: ...Airflow Configures the unit airflow during the emergency heat mode if applicable Cool Stage 1 Airflow applies to Tranquility units Configures the unit airflow while operating at minimum capacity in th...

Страница 11: ...te for the water heating mode The variable speed potable water pump will adjust the potable water flow to maintain the selected temperature difference between the entering and leaving potable water du...

Страница 12: ...s data set allows the service technician to view the real time status of all physical inputs switches temperature sensor readings as well as the operational status of the heat pump from the myUplink m...

Страница 13: ...ve Water Coil EEV1 Position Current position of the heating electronic expansion valve in steps 0 fully closed 1040 fully open Air Coil EEV2 Status QE models only Status of the cooling electronic expa...

Страница 14: ...rature reading 40 F Hum Sensor Failure Humidity sensor timed out Humidity reading is 99 Humidity reading is 0 Humidity Range High Humidity reading 90 Humidity Range Low Humidity reading 10 Outdoor Sen...

Страница 15: ...climatemaster com 15 iGate Connect Programmable Thermostat Revised Dec em b er 20 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Notes...

Страница 16: ...ct ClimateMaster s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express war...