iGate
®
Connect Programmable Thermostat
R e v i s e d : D e c e m b e r 2 0 , 2 0 2 1
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Option Configuration
System Setting
Description
Range/Options
Default
Compressor ASCD
(Anti-Short Cycle Delay)
Configures the minimum amount of time the compressor will remain off
between cycles.
5 to 8 minutes
5 minutes
Motorized Valve
(applies to Tranquility)
Configures the control to delay the compressor start until the valve is fully open.
Off, On
Off
Over/Under Voltage
Detection
(applies to Tranquility)
Configure the over/under voltage detection.
Enabled, Disabled
Enabled
Source Antifreeze
(if applicable)
Configures the low temperature protection setting for the source water heat
exchanger.
No - 30°F, Yes - 10°F
No - 30°F
Over/Under Voltage condition exists when the control voltage is outside the range of 18VAC to 31.5VAC.
DHW Pump Configuration
System Setting
Description
Range/Options
Default
Water Heating Delta T
(applies to SmartTank
Water Heater)
Sets the potable water flow rate for the water heating mode. The variable
speed potable water pump will adjust the potable water flow to maintain the
selected temperature difference between the entering and leaving potable
water during the water heating mode.
8.0°F to 12.0°F
8.0°F
Smart Tank Configuration (applies to Trilogy)
Configure the hot water mode settings.
System Setting
Description
Range/Options
Default
Hot Water Efficiency
When Hot Water Efficiency is enabled (ON) the AWS backup electric elements
will operate when the connected heat pump is locked out or when the heat
pump cannot keep up with the household hot water demand. When Hot Water
Efficiency is disabled (OFF) the iGate Smart Tank electric elements will engage
sooner when the connected heat pump is locked out or when the heat pump
cannot keep up with the household hot water demand.
Efficiency, Comfort
Efficiency
Hot Water Mode
Determines the heat source for your hot water.
Off, Heat Pump,
Emergency Heat
(electric tank elements)
Off
Hot Water Setpoint
Establishes the set point for your hot water.
50.0°F to 135.0°F
120.0°F
HW Heat Dead Band
Configures the amount of droop allowed from the potable hot water setpoint
before activating water heating.
10.0°F to 25.0°F
15.0°F