C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
Unit Manual Operation
Manual Operation mode allows the service technician to
manually command operation for operating mode, any of
the thermostat outputs, blower speed, as well as pump
speed or valve position to aid in troubleshooting. Available
data will depend on the unit/model installed.
Manual Setting
Description
Options
Field Test Mode
Enabled, Disabled
Operating Mode Selects the manual mode of
operation.
Standby, Const Fan,
Cooling, Heating, Aux
Heat, EM Heat, Hot
Water, Cooling/HW
Thermostat
Outputs
Selects the manual output of
the thermostat. (Applies to
Tranquility.)
Y1, Y2, W, O, G, H, DH
ECM Target
Airflow
Configures the target airflow
during manual operation.
Range will depend on
unit model
ECM Blower
Speed
Displays current ECM motor
rpm.
--
Loop Pump
Speed
Sets loop pump speed.
0% to 100%.
Default - 41%
DHW Pump
Speed
Sets DHW pump speed.
0% to 100%.
Default - 0%
Compressor
Actual Speed
Current compressor speed in
rps (revolutions per second).
--
The ECM Airflow adjustment will not be present if the
connected communicating control is not configured for
Blower type = ECM.
The Pump Speed adjustment will not be present if the
connected communicating control is not configured for
Loop Configuration = Pump.
The Valve Position adjustment will not be present if the
connected communicating control is not configured for
Loop Configuration = Valve.
Clear Fault History
Clear Fault history will clear all fault codes stored in the
thermostat as well as the fault history in any connected
communicating controls.
Operating Information
The Diagnostics data set allows the service technician to
view the real time status of all physical inputs, switches,
temperature sensor readings, as well as the operational
status of the heat pump from the myUplink mobile app
and web portal. Available data will depend on the unit/
model installed.
Compressor Diagnostics
Data
Unit
Description
Compressor
Current
A
Current compressor amperage.
Compressor
DC Voltage
V
Current DC bus voltage from the inverter.
Compressor
Heat Sink
F
Current temperature of the inverter heat sink.
Compressor
Input Power
W
Current power consumption of the compressor.
Compressor
Inverter Current
A
Current amperage draw of the inverter.
Compressor
Speed
rps
Current compressor speed.
Unit Capacity
%
Current operating capacity as a percentage of
the max capacity.
Blower Diagnostics
Data
Unit
Description
ECM Blower
Power
W
Instantaneous power consumption of the
blower.
ECM Blower
Speed
rpm
Current blower speed.
ECM Target
Airflow
cfm
Current blower target airflow.
Entering Air
Temperature
F
Current temperature of the air entering the unit.
Leaving Air
Temperature
F
Current temperature of the air leaving the unit.
Loop Diagnostics
Data
Unit
Description
A1 Analog
Output
V
Current voltage output at the configurable
analog output. (Applies to Tranquility.)
A2 Analog
Output
V
Current voltage output at the configurable
analog output. (Applies to Tranquility.)
Entering Water
Temperature
F
Current temperature of the water entering the
source heat exchanger.
Leaving Water
Temperature
F
Current temperature of the water leaving the
source heat exchanger.
Loop Pump
Feedback
%
Current feedback signal of the loop pump.
Loop Pump
Flow Rate
gpm
Current source flow rate.
Loop Pump
Power
W
Instantaneous power consumption of the loop
pump.
Loop Pump
Speed
%
Current speed of the loop pump.
Water Pressure
psi
Current pressure of the water as it leaves the
source heat exchanger.