ClimateMaster iGate AWC99U01 Скачать руководство пользователя страница 12

iGate

®

 Connect Programmable Thermostat

R e v i s e d :   D e c e m b e r   2 0 ,   2 0 2 1

C l i m a t e M a s t e r   Wa t e r-S o u rc e   H e a t   P u m p s

12

C L I M AT E M A S T E R  WAT E R - S O U R C E   H E AT   P U M P S

Unit Manual Operation

Manual Operation mode allows the service technician to 

manually command operation for operating mode, any of 

the thermostat outputs, blower speed, as well as pump 

speed or valve position to aid in troubleshooting. Available 

data will depend on the unit/model installed.

Manual Setting

Description

Options

Field Test Mode

Enabled, Disabled

Operating Mode Selects the manual mode of 

operation.

Standby, Const Fan, 

Cooling, Heating, Aux 

Heat, EM Heat, Hot 

Water, Cooling/HW

Thermostat 

Outputs

Selects the manual output of 

the thermostat. (Applies to 

Tranquility.)

Y1, Y2, W, O, G, H, DH

ECM Target 

Airflow

Configures the target airflow 

during manual operation.

Range will depend on 

unit model

ECM Blower 

Speed

Displays current ECM motor 

rpm.

--

Loop Pump 

Speed

Sets loop pump speed.

0% to 100%. 

Default - 41%

DHW Pump 

Speed

Sets DHW pump speed.

0% to 100%. 

Default - 0%

Compressor 

Actual Speed

Current compressor speed in 

rps (revolutions per second).

--

The ECM Airflow adjustment will not be present if the 

connected communicating control is not configured for 

Blower type = ECM.

The Pump Speed adjustment will not be present if the 

connected communicating control is not configured for 

Loop Configuration = Pump.

The Valve Position adjustment will not be present if the 

connected communicating control is not configured for 

Loop Configuration = Valve.

Clear Fault History

Clear Fault history will clear all fault codes stored in the 

thermostat as well as the fault history in any connected 

communicating controls.

Operating Information

The Diagnostics data set allows the service technician to 

view the real time status of all physical inputs, switches, 

temperature sensor readings, as well as the operational 

status of the heat pump from the myUplink mobile app 

and web portal. Available data will depend on the unit/

model installed.

Compressor Diagnostics

Data

Unit

Description

Compressor 

Current

A

Current compressor amperage.

Compressor 

DC Voltage

V

Current DC bus voltage from the inverter.

Compressor 

Heat Sink

F

Current temperature of the inverter heat sink.

Compressor 

Input Power

W

Current power consumption of the compressor.

Compressor 

Inverter Current

A

Current amperage draw of the inverter.

Compressor 

Speed

rps

Current compressor speed.

Unit Capacity

%

Current operating capacity as a percentage of 

the max capacity.

Blower Diagnostics

Data

Unit

Description

ECM Blower 

Power

W

Instantaneous power consumption of the 

blower.

ECM Blower 

Speed

rpm

Current blower speed.

ECM Target 

Airflow

cfm

Current blower target airflow.

Entering Air 

Temperature

F

Current temperature of the air entering the unit.

Leaving Air 

Temperature

F

Current temperature of the air leaving the unit.

Loop Diagnostics

Data

Unit

Description

A1 Analog 

Output

V

Current voltage output at the configurable 

analog output. (Applies to Tranquility.)

A2 Analog 

Output

V

Current voltage output at the configurable 

analog output. (Applies to Tranquility.)

Entering Water 

Temperature

F

Current temperature of the water entering the 

source heat exchanger.

Leaving Water 

Temperature

F

Current temperature of the water leaving the 

source heat exchanger.

Loop Pump 

Feedback

%

Current feedback signal of the loop pump.

Loop Pump 

Flow Rate

gpm

Current source flow rate.

Loop Pump 

Power

W

Instantaneous power consumption of the loop 

pump.

Loop Pump 

Speed

%

Current speed of the loop pump.

Water Pressure

psi

Current pressure of the water as it leaves the 

source heat exchanger.

Содержание iGate AWC99U01

Страница 1: ...ystem Configuration 4 Thermostat Settings 5 User Settings 5 Alert Configuration 6 System Settings 7 Equipment Settings 8 Configuration 8 Clear Fault History 11 Unit Manual Operation 12 Operating Infor...

Страница 2: ...ASTER WATER SOURCE HEAT PUMPS These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause th...

Страница 3: ...lose to or in a frequently used room preferably on an inside partitioning wall On a section of wall without pipes or duct work Thermostat should NOT be mounted Close to a window on an outside wall or...

Страница 4: ...re so that the insulation extends to the terminal block When the wire is installed properly to the terminal block there should be no copper exposed 22 AWG shielded wire is required when installing a r...

Страница 5: ...ng the user to enter a 4 digit security PIN Disabled Enabled Disabled Security PIN requires Security to be enabled 4 digit security PIN for restricting access 0000 9999 Active Backlight Adjusts the ba...

Страница 6: ...sensor can detect presence but also increases the possibility of a false presence High Medium Low Medium Wireless Configures Wi Fi functionality of the thermostat Enabled Disabled Enabled If disabled...

Страница 7: ...lected amount 5 F to 5 F in 1 F increments 2 5 C to 2 5 C in 0 5 C increments 0 F 0 C Humidity Offset Allows for calibration of the humidity sensor by the selected amount 9 to 9 in 1 increments 0 Remo...

Страница 8: ...onnecting the Wi Fi requires setting up the thermostat using the myUplink mobile application in order to re establish Wi Fi connectivity Disabling this function after the thermostat has been set up an...

Страница 9: ...the cooling mode will be sent to the source ground loop 70 to 100 100 Heating Hot Water Cut Out Potable water heating normally takes priority over space heating This setting determines the point at wh...

Страница 10: ...Airflow Configures the unit airflow during the emergency heat mode if applicable Cool Stage 1 Airflow applies to Tranquility units Configures the unit airflow while operating at minimum capacity in th...

Страница 11: ...te for the water heating mode The variable speed potable water pump will adjust the potable water flow to maintain the selected temperature difference between the entering and leaving potable water du...

Страница 12: ...s data set allows the service technician to view the real time status of all physical inputs switches temperature sensor readings as well as the operational status of the heat pump from the myUplink m...

Страница 13: ...ve Water Coil EEV1 Position Current position of the heating electronic expansion valve in steps 0 fully closed 1040 fully open Air Coil EEV2 Status QE models only Status of the cooling electronic expa...

Страница 14: ...rature reading 40 F Hum Sensor Failure Humidity sensor timed out Humidity reading is 99 Humidity reading is 0 Humidity Range High Humidity reading 90 Humidity Range Low Humidity reading 10 Outdoor Sen...

Страница 15: ...climatemaster com 15 iGate Connect Programmable Thermostat Revised Dec em b er 20 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY Notes...

Страница 16: ...ct ClimateMaster s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herein are not express war...

Отзывы: