Functional Troubleshooting

Only Compressor Runs

X

X

Thermostat wiring

Check G wiring at heat pump.  Jumper G and R for fan
operation.

X

X

Fan motor relay

Jumper G and R for fan operation.  Check for Line voltage
across BR contacts.

Check fan power enable relay operation (if present)

X

X

Fan motor

Check for line voltage at motor.  Check capacitor

X

X

Thermostat wiring

Check thermostat wiring at heat pump.  Jumper Y and R for
compressor operation in test mode.

Unit Doesn't Operate in
Cooling

X

Reversing Valve

Set for cooling demand and check 24VAC on RV coil and at
CXM/DXM board.
If RV is stuck, run high pressure up by reducing water flow
and while operating engage and disengage RV coil voltage
to push valve.

X

Thermostat setup

Check for 'O' RV setup not 'B'

X

Thermostat wiring

Check O wiring at heat pump.  Jumper O and R for RV coil
'Click'.

X

Thermostat wiring

Put thermostat in cooling mode. Check for 24VAC on O
(check between C and O); check for 24VAC on W (check
between W and C). There should be voltage on O, but not
on W. If voltage is present on W, thermostat may be bad
or wired incorrectly.

Performance Troubleshooting

Performance
Troubleshooting

Htg Clg Possible Cause

Solution

Insufficient capacity/

X

X

Dirty Filter

Replace or clean

Not cooling or heating

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

properly

in heating

Check fan motor operation and airflow restrictions
Too high of external static.  Check static vs blower table

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions
Too high of external static.  Check static vs blower table

X

X

Leaky duct work

Check supply and return air temperatures at the unit and at
distant duct registers if significantly different, duct leaks
are present

X

X

Low refrigerant charge

Check superheat and subcooling per chart

X

X

Restricted metering device

Check superheat and subcooling per chart.  Replace.

X

Defective Reversing Valve

Perform RV touch test

X

X

Thermostat improperly located

Check location and for air drafts behind stat

X

X

Unit undersized

Recheck loads & sizing check sensible clg load and heat
pump capacity

X

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

X

X

Inlet Water too Hot or Cold

Check load, loop sizing, loop backfill, ground moisture.

High Head Pressure

X

Reduced or no Air flow

Check for dirty air filter and clean or replace

in heating

Check fan motor operation and airflow restrictions

Too high of external static.  Check static vs blower table

X

Reduced or no water flow

Check pump operation or valve operation/setting

in cooling

Check water flow adjust to proper flow rate

X

Inlet Water too Hot

Check load, loop sizing, loop backfill, ground moisture.

X

Air Temperature out of range in
heating

Bring return air temp within design parameters

X

Scaling in water heat exchanger

Perform Scaling check and clean if necessary

X

X

Unit Overcharged

Check superheat and subcooling.  Reweigh in charge

X

X

Non-condensables insystem

Vacuum system and reweigh in charge

X

X

Restricted metering device

Check superheat and subcooling per chart.  Replace.

Low Suction Pressure

X

Reduced water flow

Check pump operation or water valve operation/setting

in heating

Plugged strainer or filter.  Clean or replace.
Check water flow adjust to proper flow rate

X

Water Temperature out of range

Bring water temp within design parameters

X

Reduced Air flow

Check for dirty air filter and clean or replace

in cooling

Check fan motor operation and airflow restrictions
Too high of external static.  Check static vs blower table

X

Air Temperature out of range

Too much cold vent air? Bring entering air temp within
design parameters

X

X

Insufficient charge

Check for refrigerant leaks

Low discharge air
temperature in heating

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Poor Performance

See 'Insufficient Capacity'

High humidity

X

Too high of air flow

Check fan motor speed selection and airflow chart

X

Unit oversized

Recheck loads & sizing check sensible clg load and heat
pump capacity

Содержание CCE07 Series

Страница 1: ...op Heat Pump Applications 17 Ground Water Heat Pump Applications 18 Water Quality Standards 20 Electrical Wiring Line Voltage 21 23 Electrical Wiring Low Voltage 24 Thermostat Wiring 25 Electrical Wir...

Страница 2: ......

Страница 3: ...orized Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valve Afr 3 0 E L T Secondary Circulation Pump U V W Water Circuit...

Страница 4: ...emote Mounted w DXM MPC G 208 230 60 1 B 20Amp Plug Cord D Disconnect Switch 15Amp Fuse F Disconnect Switch Non Fused H 20Amp Plug Cord Receptacle Disconnect Switch 15Amp Fuse K 20Amp Plug Cord Recept...

Страница 5: ...on dirt and debris which may cause system damage WARNING WARNING WARNING CAUTION Safety Warnings cautions and notices appear throughout this manual Read these items carefully before attempting any ins...

Страница 6: ...for installation above false ceiling or in a ceiling plenum Other unit configurations are typically installed in a mechanical room The installation site chosen should include adequate service clearanc...

Страница 7: ...ngs in 1 2 1 2 1 2 1 2 1 2 Optional EPT Fittings in 1 2 1 2 1 2 1 2 1 2 Condensate Connection Size I D Vinyl Hose In mm 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 5 8 15 9 Air Coil Size Dimensions h x w in m...

Страница 8: ...ir Coil Size Dimensions h x w in mm 8 x 26 203 x 660 10 x 26 254 x 660 10 x 32 254 x 812 Filter Size Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 36 x 1 254 x 914 x 25 Front Return In mm 1...

Страница 9: ...ction Size I D Vinyl Hose In mm 5 8 15 9 Air Coil Size Dimensions h x w in mm 8 x 26 203 x 660 10 x 26 254 x 660 10 x 32 254 x 813 Filter Size Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 3...

Страница 10: ...ssemblies are available for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted with swivel joi...

Страница 11: ...Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause blockage If blo...

Страница 12: ...figuration Power Supply Water In Water Out Blower Deck Blower Access Panel 3 50 89 1 93 49 4 49 114 0 75 19 3 88 99 11 54 293 3 22 82 1 94 49 16 66 423 7 06 179 30 0 87 22 3 01 76 5 36 136 Condensate...

Страница 13: ...w Regulator Optional Motorized Water Valve 1 75 44 Out In Water Connections 5 8 15 9 OD Copper 1 2 IPT or 1 2 EPT 8 00 Min 203 11 25 286 1 62 41 2 00 51 2 25 57 Left Hand Configuration Water In Water...

Страница 14: ...t Compressor Access Panel Control Box 1 84 77 Condensate Condensate 5 8 15 9 ID Vinyl Hose ptional orized Valve onal flow alve Connections 5 9AA pper T or T O R Optional Motorized Water Valve 1 75 44...

Страница 15: ...fittings is 30 ft lbs 41 N m If a torque wrench is not available tighten finger tight plus one quarter turn Tighten steel fittings as necessary Optional pressure rated hose assemblies designed specifi...

Страница 16: ...id valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to operation se...

Страница 17: ...fore backfilling Test vertical U bends and pond loop assemblies prior to installation Pressures of at least 100 psi 689 kPa should be used when testing Do not exceed the pipe pressure rating Test enti...

Страница 18: ...t use A monitoring plan should be implemented in these probable scaling situations Other water quality issues such as iron fouling corrosion prevention and erosion and clogging should be referenced in...

Страница 19: ...e of any field provided shut off valves and connected to the heat pump controls in series with the built in refrigerant circuit high pressure switch to disable compressor operation if water pressure e...

Страница 20: ...Y IYHZZ JHZ JVTWVULU Z HYL 62 V WWT TTVUPH PVU HZ O KYV_PKL JOSVYPKL UP YH L HUK Z SMH L JVTWV UKZ SS WWT 4H_PT T 4H_PT T SSV HISL H TH_PT T H LY LTWLYH YL OSVYPKL 3L LSZ 100 F 38 C VWWLY WWT 59 NR WY...

Страница 21: ...s or the National Electric Code whichever is applicable Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the L side of the contactor Consult Tables 4 t...

Страница 22: ...08 230 60 1 197 254 1 5 2 24 0 0 6 5 8 7 1 15 E 265 60 1 239 292 1 4 2 25 0 0 4 4 6 5 7 15 TRC15 G 208 230 60 1 197 254 1 6 1 30 0 0 8 6 9 8 4 15 E 265 60 1 239 292 1 4 7 28 5 0 6 5 3 6 5 15 TRC18 G 2...

Страница 23: ...nly required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the power supply disconnec...

Страница 24: ...heating or cooling and press the arrow up or arrow down key to change the set point The differential between heating and cooling set points is factory set at 3 F 1 5 C Unit mounted controls are shippe...

Страница 25: ...ct number of heating and cooling stages WIRE SIZE MAX WIRE LENGTH 18 Gauge 75 feet 22m 16 Gauge 125 feet 38m 14 Gauge 200 feet 60m Length Physical distance from thermostat to unit Table 6 Recommended...

Страница 26: ...0N04 LON ETL R410A 96B0100N05 MPC ETL R410A 96B0099N60 220 240 50 1 CXM ACO MCO CE R410A 96B0099N61 REM CE R410A 96B0099N62 LON CE R410A 96B0099N63 MPC CE R410A 96B0100N60 DXM MCO ACO CE R410A 96B0100...

Страница 27: ...SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 5 Nov 2 0 0 9 B climatemaster com Typical Wiring Diagram Unit Mounted Manual Auto Change Over CCE Units Rev B TRC Units with CXM Controller 2...

Страница 28: ...ER SOURCE HEAT PUMPS Co n sole s R ev 5 Nov 2009B 28 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Remote Mounted Thermosat CCE TRC Units with CXM Controller 1 Speed wi...

Страница 29: ...SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 5 Nov 2 0 0 9 B climatemaster com Typical Wiring Diagram Unit Mounted Manual Auto Change Over CCE Units Rev B TRC Units with DXM Controller 2...

Страница 30: ...WATER SOURCE HEAT PUMPS Co n sole s R ev 5 Nov 2009B 30 ClimateMaster Water Source Heating and Cooling Systems Typical Wiring Diagram Unit Mounted Manual Auto Change Over TRC Units 50Hz with CXM Cont...

Страница 31: ...E SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 5 Nov 2 0 0 9 B climatemaster com Typical Wiring Diagram Remote Mounted Thermostat TRC Units 50Hz with DXM Controller 1 Speed with Selector S...

Страница 32: ...witches Note In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field s...

Страница 33: ...d selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact no connection Not Clipped AL2 connected to R Clipped AL2 dry contact no connection Low pressure normally open...

Страница 34: ...boilerless mode the compressor is only used for heating when FP1 is above the temperature specified by the setting of DIP 1 8 Below DIP 1 8 setting the compressor is not used and the control goes into...

Страница 35: ...uick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the low pre...

Страница 36: ...e unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM Controls Diagnostic Features The LED on the CXM board advises the technician of th...

Страница 37: ...0 4 5 49 60 90 16 43 EXTENDED RANGE UNIT ENTERING WATER MIN MAX 30 110 1 43 20 90 6 7 32 30 120 1 49 20 90 6 7 32 Requires optional insulation package when operating below the dew point Requires antif...

Страница 38: ...750 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period...

Страница 39: ...em water temperature Check water temperature for proper range and also verify heating and cooling set points for proper operation System pH Check and adjust water pH if necessary to maintain a level b...

Страница 40: ...position A hissing noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to the...

Страница 41: ...12 6 6 9 8 9 17 23 17 23 17 23 TRC12 Full Load Cooling without HWG Active Full Load Heating without HWG Active Entering Water Temp F Water Flow GPM Ton Suction Pressure PSIG Discharge Pressure PSIG Su...

Страница 42: ...30 36 90 2 1 3 15 4 2 138 148 138 148 138 148 366 386 353 373 340 360 9 14 9 14 9 14 11 16 9 14 6 11 15 8 17 8 14 9 16 9 14 16 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 1...

Страница 43: ...onditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan mot...

Страница 44: ...erature limit in cooling Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Air Temperature out of range Too much cold vent air Bring enterin...

Страница 45: ...evice Check superheat and subcooling per chart Replace X Defective Reversing Valve Perform RV touch test X X Thermostat improperly located Check location and for air drafts behind stat X X Unit unders...

Страница 46: ...IL F F PSI SAT PSI SAT F F F F WATER IN WATER OUT PSI PSI F F WATER IN WATER OUT PSI PSI Look up pressure drop in I O M or spec catalog to determine flow rate Look up pressure drop in I O M or spec ca...

Страница 47: ...t or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or repl...

Страница 48: ...performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or unrealized savin...

Страница 49: ...49 THE SMAR T SOLUTION FOR ENERGY EFF IC IE NC Y C ons oles Rev 5 Nov 2 0 0 9 B climatemaster com Notes...

Страница 50: ...solenoid valves 01 01 07 Applications Added Notice on ground water applications 01 01 06 First Published Revision History 97B0035N01 ClimateMaster works continually to improve its products As a resul...

Отзывы: