![ClimateMaster CCE07 Series Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/climatemaster/cce07-series/cce07-series_installation-operation-and-maintenance-instructions-manual_2624715022.webp)
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S
C o n s o l e s
R e v. : 5 N o v. , 2 0 0 9 B
22
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s
Table 5a: TRC Electrical Data (60Hz)
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY
RLA
LRA
TRC09
A
115/60/1
104-126
1
8.1
46.5
0.6
8.6
10.7
15
G
208-230/60/1
197-254
1
4.5
23.0
0.4
4.9
6.0
15
E
265/60/1
239-292
1
3.1
24.0
0.4
3.5
4.3
15
TRC12
A
115/60/1
104-126
1
10.6
55.8
1.0
11.6
14.3
20
G
208-230/60/1
197-254
1
5.2
24.0
0.6
5.8
7.1
15
E
265/60/1
239-292
1
4.2
25.0
0.4
4.6
5.7
15
TRC15
G
208-230/60/1
197-254
1
6.1
30.0
0.8
6.9
8.4
15
E
265/60/1
239-292
1
4.7
28.5
0.6
5.3
6.5
15
TRC18
G
208-230/60/1
197-254
1
6.8
38.0
0.7
7.5
9.2
15
E
265/60/1
239-292
1
6.2
29.0
0.6
6.8
8.4
15
Table 5b: TRC Electrical Data (50Hz)
Model
Voltage
code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
TRC09
V
220-240/50/1
198-264
1
3.2
17
0.4
3.6
4.4
15.0
TRC12
V
220-240/50/1
198-264
1
4.0
19
0.4
4.4
5.4
15.0
TRC15
V
220-240/50/1
198-264
1
4.7
23
0.6
5.3
6.5
15.0
TRC18
V
220-240/50/1
198-264
1
5.6
25
0.6
6.2
7.6
15.0
Electrical - Line Voltage