28
Main Menu Buttons -
Humidity
Humidification Settings
The Humidity feature allows the thermostat to
control a humidifier or use your air conditioner
to dehumidify the space.
Humidity
Dehumidification Settings
Run fan when humidifying - OFF
Humidify setpoint
(0%)
Adjust Humidify setpoint. (0% - 60%)
Humidify with heat - OFF
When this step is ON, Humidify will only run with a demand for heat.
Maximum Overcool
This specifies how many degrees the A/C system will run past the cool
setpoint to satisfy a demand for Dehumidification. (0 - 20 degrees F)
Dehumidify setpoint
(99%)
Adjust Dehumidify setpoint. (25% - 99%)
Run A/C to dehumidify - OFF
When this step is ON, the A/C system will be used for Dehumidification.
When this step is ON, the fan will run with a call for Humidification.
IMPORTANT: D/H Output Usage must be set for Hum or
Dehum for these settings to take effect.
See: D/H Output Settings on page 38.
(0
˚
)
Reheat - OFF
This turns on electric strip heat during an A/C to dehumidify demand to
help maintain desired room temperatures. (Run A/C to dehumidify must
be set to ON and the GAS ELEC Dip Switch must be set to ELEC - to
access this feature).
Dehumidify only when cooling - ON
Run dehumidification only when HVAC calls for A/C.
Содержание AVB32V03R
Страница 21: ...13 Main Menu Buttons Schedule Schedule View My Schedule Edit My Schedule...
Страница 56: ...48 Main Menu Buttons Settings The user may limit the maximum Cooling Setpoint...
Страница 57: ...49 Main Menu Buttons Settings The user may limit the minimum Heating Setpoint...
Страница 58: ...50 Main Menu Buttons Settings 2 The user may adjust the ADR Cooling static Setpoint...
Страница 59: ...51 2 Main Menu Buttons Settings The user may adjust the ADR Heating static Setpoint...
Страница 88: ...P N 88 1358 Rev 1 03 27 20 Patents Issued Pending...