76
Installation Instructions -
Sample Wiring Diagrams
2 Stage Heat, 2 Stage Cool
(with condensate overflow)
D/H
W
O
SENSOR
W1
W2
Y1
Y2
G
R
C
Dip Switch
Settings
Condensate Switch
(optional)
open = normal
closed = condensate
pan full
HVAC
Equipment
1
GAS
O
GAS/EL
ELEC
B
HP
ON
23
2) Connect the normally open Condensate Overflow switch between the two
SENSOR terminals. To enable the function, set MENU > Settings > Installation
Settings > Sensor Settings > AUX IN use to Condensate Overflow. When
triggered, cooling is turned off. If the switch opens, cooling will resume, and
a condensate pan overflow alert will be triggered to notify the user that
servicing of the condensate drain is required.
Notes:
1) Make sure to select 2 heat and 2 cool stages via Menu >
Settings > Installation Settings > Heat & Cool Stages