Installation Instructions
Wire Connections
If the terminal designations on your old thermostat do not match those
on the new thermostat,
refer to the chart below or the wiring
diagrams that follow.
G,F
Fan
Fan
G
Y,Y1
1st stage
1st stage cooling
Y1
heating/cooling
Y2
2nd stage
2nd stage cooling
Y2
heating/cooling
W,W1
1st stage heating
O
W2
2nd stage heating
W
W (on CLM products)
3rd stage heating
W
emergency heat
O
reversing valve
O
humidifier
humidifier
D/H (note 1)
H (on CLM products)
ClimaDry
D/H (note 2)
dehumidifier
dehumidifier
D/H (note 2)
AL1, AL2
fault
condensate
sensor (note 3)
R,Rh,M,Vr,A
power
power
R
C
common common C
Wire from the old
thermostat terminal
possibly marked
Function
(Heatpump)
Function
(Gas/Electric)
Install on
the new
thermostat
connector
marked
Note 1 :
set the D/H USE to humidifier. Also, set the HUM WITH HEAT ONLY as required
Note 2 :
set the D/H USE to dehumidifier. Also, set the DEHUM WITH COOL ONLY as required
Note 3 :
for equipment lockout caused by internal issue or condensate overflow, bring signals AL1 and AL2 to
the two SENSOR terminals on the backplate and remove jumper JW1
Содержание AVB32V03R
Страница 21: ...13 Main Menu Buttons Schedule Schedule View My Schedule Edit My Schedule...
Страница 56: ...48 Main Menu Buttons Settings The user may limit the maximum Cooling Setpoint...
Страница 57: ...49 Main Menu Buttons Settings The user may limit the minimum Heating Setpoint...
Страница 58: ...50 Main Menu Buttons Settings 2 The user may adjust the ADR Cooling static Setpoint...
Страница 59: ...51 2 Main Menu Buttons Settings The user may adjust the ADR Heating static Setpoint...
Страница 88: ...P N 88 1358 Rev 1 03 27 20 Patents Issued Pending...