Main Menu Buttons -
Settings
The installer or service
technician can use this
feature to test the
functions without any
time delays of the
thermostat.
Test Outputs
With a 1st stage cooling call, Y1 and G are active
Aux In Use
(remote)
The wired sensor may be used as follows:
The integral humidity sensor may be calibrated -20% to +20% RH
Calibrate Sensors
(0
˚
)
The thermostat and wired sensor may be calibrated -7 to +7 degrees F.
Installation Settings
(Continued)
• Use as outdoor sensor
• Use as remote sensor
• Use as supply sensor
• Thermostat
• Wired Sensor
• Humidity
The first four options allow you to connect a 10K thermistor to the
SENSOR terminals to be used to monitor a temperature (outdoor,
supply, return) or control to a temperature (remote). The last two
options allow you to connect a dry contact signal that will simply
short the two SENSOR terminals to detect a Condensate overflow
switch or a fault/alarm signal. Note that on ClimateMaster
equipment, the condensate overflow sensor is connected to the
control board such that an actual condensate overflow event causes
the control board to lock out and generate a fault condition that can
be detected by the thermostat. In this case, set AUX IN use to the
Fault Detect setting.
• Use as return sensor
• Condensate overflow
• Fault Detect
Содержание AVB32V03R
Страница 21: ...13 Main Menu Buttons Schedule Schedule View My Schedule Edit My Schedule...
Страница 56: ...48 Main Menu Buttons Settings The user may limit the maximum Cooling Setpoint...
Страница 57: ...49 Main Menu Buttons Settings The user may limit the minimum Heating Setpoint...
Страница 58: ...50 Main Menu Buttons Settings 2 The user may adjust the ADR Cooling static Setpoint...
Страница 59: ...51 2 Main Menu Buttons Settings The user may adjust the ADR Heating static Setpoint...
Страница 88: ...P N 88 1358 Rev 1 03 27 20 Patents Issued Pending...