OPERATION

Mode Selection

 — The mode button allows the user to 

display the off, heat, cool, auto icons. Pressing the mode 
button cycles through the available modes based on the 
equipment selection from Option 15. Available choices 
are listed in Table 2.

Table 2: Mode Selection

Fan Selection 

— The thermostat offers two continuous 

(ON) or two cycling (AUTO) and two fan speeds high (HI) 
or low (LO). Pressing the fan button cycles through the 
following displays fan on LO, fan on HI, auto fan LO, auto 
fan HI.

Fan Display

 — If Option 39 is set to display set point 

(SP), then the two-speed fan setting remains on the 
display. If the current fan speed is not shown on the 
display, the first press of the fan button will display the 
current selection. The fan selection can only be changed 
by a fan button press when the current selection is shown 
on the display. See Fig. 6.

If Option 39 is set to display the space temperature (St), 
then the two-speed fan setting (LO or HI) remains on the 
display for three seconds after the last press of the fan 
button.

Figure 6: Current Fan Selection Display

Set Temperature Selection

 — If auto mode is not 

active and off mode is not active, pressing the up or 
down button causes the set point corresponding to the 
current system mode to be updated. If the up or down 
button is held, the set point value will be scrolled. The 
set point change also takes into account that Option 11 
(deadband) is preserved along with ensuring that Option 
26 (minimum cooling set point) and Option 27 (maximum 
heating set point) are taken into account to enforce set 
point limits.

If auto mode is active, pressing the up or down button 
causes the set point corresponding to the current 
operating mode to be updated. To move between the 
heat and cool set points, press the mode button to 
toggle between set points. Once the desired set point 
has been adjusted, press the mode button to return to 
auto mode.

If off mode is active, the up and down buttons are 
ignored for changing set point(s).

When changing the set points, the following restrictions 
are in place. The cool set point cannot be increased 
above 90 degrees F (32 C) or decreased below Option 
26, the minimum cooling set point. The heat set point 
cannot be decreased below 50 F (10 C) or increased 
above Option 27, the maximum heating set point.

When Option 39 is set to SP (set point), the set point 
adjustment is displayed in the large space temperature 
digits.

Display Lighting

 — The display has two levels of 

lighting, high level and low level. High level lighting 
comes on for 10 seconds when buttons are being 
pressed. The low level can be selected (see Option 18) 
for continuous backlight.

Remote Sensor Temperature Display 

— Pressing 

the up and down buttons simultaneously displays the 
temperature of the sensor connected to the S1 and S2 
terminals for five seconds, then the thermostat returns to 
normal operation.

If the sensor is invalid, then the display shows “--” in the 
large temperature display digits.

 

 

OPTION 15

AVAILABLE MODES

On

Off, Heat Cool, Auto

Off

Off, Heat, Cool

Содержание ATA11U03

Страница 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Страница 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Страница 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Страница 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Страница 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Страница 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Страница 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Страница 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Страница 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Страница 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Страница 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Страница 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Отзывы: