have full access to the thermostat functionality. The 
thermostat will lock after no buttons have been 
pressed for two minutes.

If the option value is set to “cd”, the mode, up and 
down buttons will work as follows:
1.  Pressing the mode button once will display the 

flashing Option number (21).

2.  Pressing the mode button again and the option 

value will flash OF, 1 or cd.

3.  Pressing the mode button a third time will display 

the keypad lock icon and the code entry values 
(see Fig. 4). The up and down buttons will allow 
the selection of a code value between 00 to 199.

4.  Pressing the mode key again will return the focus 

to the Option number (21) .

Default: OF (off)

 

OPTION 26 — MINIMUM COOLING SET POINT

 

— This parameter establishes the minimum cooling 
set point that the user is allowed to set. Otherwise, 
the equipment type allows both heating and cooling 
operation, so the minimum is 60 F plus Option 11 
(deadband) and the maximum is 90 F.

Selection: minimum = 60 F + deadband, maximum 
= 90 F 
Default: 60 F (based on the adjustable deadband 
default = 5)

OPTION 27 — MAXIMUM HEATING SET POINT

 — 

This parameter establishes the maximum heating set 
point that the user is allowed to set. The equipment 

type allows both heating and cooling operations, so the 
minimum is 50 F plus Option 11 (deadband) and the 
maximum is 90 F.

Selection: minimum = 50 F, maximum = 90 F – 
deadband
Default: 85 F (based on adjustable deadband default = 5)

OPTION 39 — TEMPERATURE DISPLAY

 — This 

configuration allows the installer to select either the 
set point temperature or the space temperature to be 
displayed on the large temperature display digits.

When the option St is chosen, the space temperature, as 
defined by Option 05, is displayed using the traditional 
space temperature digits on the LCD display. The current 
set temperature is displayed using the normal set-point 
display digits.

When SP is chosen, the current set point temperature is 
displayed using the traditional space temperature digits 
on the LCD display. The normal set point display digits 
remain blank. Space temperature is not be displayed, but 
if a problem occurs with the actual space temperature 
sensor, the characters “- -” will be displayed instead of 
the set temperature to indicate that the temperature 
sensor has an error.

NOTE: The “Actual Temp” icon is not to be 

displayed when the sensor type is set to Set Point 

display (SP).

Selection: St, SP
Default: St (Space Temperature)

OPTION 40 — FAN SPEEDS

 — This configuration 

allows the installer to select the number of fan speeds 
the system with operate with. When set to 1, the single 
speed fan only will be available (LO). When set to 2, both 
fan speeds will be available (LO & HI).

Selection: 1, 2
Default: 2
Check unit submittal for fan speeds available. Set 
accordingly.

OPTION 99 — RESET TO FACTORY DEFAULTS

 — This 

configuration allows the installer to return the thermostat 
to its “out of the box” settings. Not recommended  
to use.

IMPORTANT:

 All configuration settings, mode, fan and 

set point settings which have been manually entered will 
be lost and will require resetting.

When this setting is first selected, 99 will be displayed in 
the space temperature location and an initial value of 10 

Configuration

Figure 4: Selection of Code Value

Содержание ATA11U03

Страница 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Страница 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Страница 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Страница 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Страница 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Страница 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Страница 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Страница 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Страница 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Страница 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Страница 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Страница 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Отзывы: