W A T E R - S O U R C E   H E A T   P U M P S

ATA11U03

R e v. :   0 9 / 1 6 / 1 3

Timers

 — There are several timers which influence the 

thermostat’s operation that are listed below. If any of the 
timers is preventing the equipment from turning on, the 
“on” icon will flash.

Five-Minute Compressor Timeguard

 — This timer 

prevents the Y1 output from turning on unless it has been 
off for 5 minutes. (Option 07 set to OF)

After a power cycle, a randomized delay will be added 
to end of the timeguard timer to prevent multiple units 
from hitting the power grid all at the same time. The 
randomization timer will be between zero and five 
minutes. If a demand exists, compressor outputs will 
energize between 5 and 10 minutes after the power 
cycle. It can be defeated by simultaneously pressing the 
fan and up keys.

Minimum On Timer 

— Once the equipment has been 

turned on, it must remain on for 3 minutes. A change in 
mode or set point will cancel this timer.

Cycle Timer

 — The number of equipment cycles per hour 

is determined by configuration Option 16. Based on the 
selection of 4, 6 or 8 cycles per hour, this timer is set to 
15, 10 or 8 minutes. This much time must elapse from the 
start of one cycle before another cycle can start, imposing 
the cycles per hour limits. It can be defeated for one cycle 
by simultaneously pressing the fan and up keys.

TROUBLESHOOTING

There are three system error messages that may appear 
on the thermostat screen indicating a problem with 
the thermostat’s operation. See text below for possible 
system error messages and their meaning.

Space Temperature Sensor Failure

 — If the room 

temperature sensor fails, the temperature display will 
show “--” (two dashes). If the space temperature is 
the average of both the local and remote sensors (as 
configured in Option 5), and one of the sensors fails, the 
thermostat provides control to the valid sensor only. The 
display will alternate every 10 seconds between “--” for 
the invalid sensor and the reading from the valid sensor.

Memory Failure 

— If there is an internal memory failure, 

the temperature display will show “E4,” the thermostat 
needs to be replaced.

WIRING DIAGRAMS

System wiring diagram is shown for typical ClimateMaster 
heat pump unit. See Fig. 7.
   

O is Energized for cooling
G is low speed fan
G2 is hi speed fan

Figure 7: Typical Wiring Diagram - Heat Pump

Rc

Rh

W

C

G

G2

R

W OR W1
C
G
H (DXM ONLY)

O
Y or Y1

NOTE 1

NOTE 2

S2
S1

O

Y1

THERMOSTAT

HEAT PUMP

CXM/DXM

HEAT PUMP

REMOTE 

SENSOR 

(Optional)

Содержание ATA11U03

Страница 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Страница 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Страница 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Страница 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Страница 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Страница 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Страница 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Страница 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Страница 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Страница 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Страница 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Страница 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Отзывы: