Configuration

Configuration

Configuration options enable the installer to configure 
the thermostat for a particular installation. These 
configuration options are stored to the internal 
memory so they are retained through a power outage. 
The availability of some configuration options will be 
dependent upon other conditions in the thermostat. 

Table 1: Configuration Options Summary

Entering and Exiting Configuration Mode

 - Press and 

hold the fan button for about 10 seconds. After the 10 
second period the Option number “02” will appear 
flashing in the space temperature location. The value of 
the configuration setting will be displayed in the set point 
location.

The parameter that is changeable will be determined by 
the flashing area. The up or down buttons can be used 

to select a new value. The mode button can be used to 
toggle/move the selection between the configuration 
option number and the configuration value. To exit the 
installer configuration screen, press the fan button. If 
no button is pressed for three minutes, the installer 
configuration screen will time out and the thermostat will 
return to normal operation.

All changes to the installer configuration are saved as 
they are made. There is no provision to exit the installer 
configuration and cancel the change. The installer will 
have to manually change a configuration back to its 
original value to “undo” a change.

Configuration Options

OPTION 02 — REMOTE SENSOR SELECTION

 — A 

remote sensor 17B0008N05 (for inside duet), or ASW06 
(for wall) can be connected to the S1 and S2 screw 
terminals to sense either remote space, return air, 
outdoor air, or supply air temperature.

Selection: rA, Od, SA, rS
rA* — Sense return air temperature
 

* Display only, not used for temperature control.

Od*— Sense outdoor air temperature 
SA*— Sense supply air temperature 
rS — Sense remote space temperature
Default: rS

Note: Option 02 cannot be changed from the rS setting 

if Option 05 is set to either r or Lr.

OPTION 03 — ENGLISH/METRIC

 — This configuration 

selects be-tween Fahrenheit (F) and Celsius (C) operation.

Selection: F, C
Default: F

OPTION 05 — SPACE TEMPERATURE SENSING 

— 

This selection determines which sensor the control 
will use for measuring space temperature. Space 
temperature can be sensed in one of three ways: the 
local sensor (L) located on the thermostat, the remote 
sensor (r), or the average of local and remote sensors (Lr).

Selection: L, r, Lr (Do not use)
L — Local sensor: The onboard thermistor is the 
control point for the temperature control algorithm.
r — Remote space sensor: The remote space 
temperature is the control point for the temperature 
control algorithm.

NOTE: This selection is only available if Option 02 

indicates that the S1, S2 terminals are sensing a 

remote space temperature.

 

Default: r 

� 

WARNING!

 �

WARNING!

 User should not reconfigure installer set up. 

Equipment damage could occur.

� 

NOTICE

 �

Wall thermostat requires configurating for on board sensing.  

Installer must configure 05 to L unless remote sensor  

is used.

Option 

Number

Configuration

Default

02

Remote Sensor Selection

rS

03

English/Metric

F

05

Space Temperature Sensing

r

07

Equipment DDC Controller

OF

11

Deadband between Heating and Cooling Set Points

5

13

Space Temperature Display Adjustment (Offset)

0

15

Auto Mode Availability

ON

16 

Maximum Cycles Per Hour

4

18

Backlight Configuration

OF

20

Outdoor Air Temperature Adjustment (Offset)

0

21

Keypad Lockout

OF

26

Minimum Cooling Set Point

60

27 

Maximum Heating Set Point

85

39

Temperature Display

St

40

Fan Speeds Selection

2

Содержание ATA11U03

Страница 1: ...de 5 Configuration Options 5 Exiting Configuration Mode 8 System Start Up and Checkout 8 Installer Test Mode 8 Terminating Installer Test 8 Checklist 8 Operation 9 Mode Selection 9 Fan Selection 9 Fan...

Страница 2: ...2 WATER SOURCE HEAT PUMPS ATA11U03 R ev 09 16 13 This Page Intentionally Left Blank...

Страница 3: ...Non Programmable Heat Pump Thermostat This Installation Instruction covers installation configuration and start up of the non programmable heat pump thermostat This manual is intended for installer a...

Страница 4: ...ovided 6 Secure backplate to box or wall with two screws provided Make sure all wires extend through hole in backplate 7 Adjust length and routing of each wire to reach proper connector block and term...

Страница 5: ...air or supply air temperature Selection rA Od SA rS rA Sense return air temperature Display only not used for temperature control Od Sense outdoor air temperature SA Sense supply air temperature rS S...

Страница 6: ...n an output is energized it will not be energized again for 8 minutes Default 4 OPTION 18 BACKLIGHT CONFIGURATION When set to OF off the backlight will be lit for 10 seconds after a button is pressed...

Страница 7: ...staller to select either the set point temperature or the space temperature to be displayed on the large temperature display digits When the option St is chosen the space temperature as defined by Opt...

Страница 8: ...d cooling equipment Auto mode is not available during installer test When the mode is set to heat H is displayed heating is energized for 180 seconds During the installer test operation the on icon is...

Страница 9: ...account that Option 11 deadband is preserved along with ensuring that Option 26 minimum cooling set point and Option 27 maximum heating set point are taken into account to enforce set point limits If...

Страница 10: ...time must elapse from the start of one cycle before another cycle can start imposing the cycles per hour limits It can be defeated for one cycle by simultaneously pressing the fan and up keys TROUBLES...

Страница 11: ...on 05 _____ Space Temperature Sensing Option 07 _____ Equipment DDC Controller _____ Deadband between Heating and Cooling Set Option 11 Points _____ Space Temperature Display Adjustment Option 13 Offs...

Страница 12: ...as described herein Please contact our Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and other information contained herei...

Отзывы: