T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
ATA11U03
R e v. : 0 9 / 1 6 / 1 3
Configuration
Configuration
Configuration options enable the installer to configure
the thermostat for a particular installation. These
configuration options are stored to the internal
memory so they are retained through a power outage.
The availability of some configuration options will be
dependent upon other conditions in the thermostat.
Table 1: Configuration Options Summary
Entering and Exiting Configuration Mode
- Press and
hold the fan button for about 10 seconds. After the 10
second period the Option number “02” will appear
flashing in the space temperature location. The value of
the configuration setting will be displayed in the set point
location.
The parameter that is changeable will be determined by
the flashing area. The up or down buttons can be used
to select a new value. The mode button can be used to
toggle/move the selection between the configuration
option number and the configuration value. To exit the
installer configuration screen, press the fan button. If
no button is pressed for three minutes, the installer
configuration screen will time out and the thermostat will
return to normal operation.
All changes to the installer configuration are saved as
they are made. There is no provision to exit the installer
configuration and cancel the change. The installer will
have to manually change a configuration back to its
original value to “undo” a change.
Configuration Options
OPTION 02 — REMOTE SENSOR SELECTION
— A
remote sensor 17B0008N05 (for inside duet), or ASW06
(for wall) can be connected to the S1 and S2 screw
terminals to sense either remote space, return air,
outdoor air, or supply air temperature.
Selection: rA, Od, SA, rS
rA* — Sense return air temperature
* Display only, not used for temperature control.
Od*— Sense outdoor air temperature
SA*— Sense supply air temperature
rS — Sense remote space temperature
Default: rS
Note: Option 02 cannot be changed from the rS setting
if Option 05 is set to either r or Lr.
OPTION 03 — ENGLISH/METRIC
— This configuration
selects be-tween Fahrenheit (F) and Celsius (C) operation.
Selection: F, C
Default: F
OPTION 05 — SPACE TEMPERATURE SENSING
—
This selection determines which sensor the control
will use for measuring space temperature. Space
temperature can be sensed in one of three ways: the
local sensor (L) located on the thermostat, the remote
sensor (r), or the average of local and remote sensors (Lr).
Selection: L, r, Lr (Do not use)
L — Local sensor: The onboard thermistor is the
control point for the temperature control algorithm.
r — Remote space sensor: The remote space
temperature is the control point for the temperature
control algorithm.
NOTE: This selection is only available if Option 02
indicates that the S1, S2 terminals are sensing a
remote space temperature.
Default: r
�
WARNING!
�
WARNING!
User should not reconfigure installer set up.
Equipment damage could occur.
�
NOTICE
�
Wall thermostat requires configurating for on board sensing.
Installer must configure 05 to L unless remote sensor
is used.
Option
Number
Configuration
Default
02
Remote Sensor Selection
rS
03
English/Metric
F
05
Space Temperature Sensing
r
07
Equipment DDC Controller
OF
11
Deadband between Heating and Cooling Set Points
5
13
Space Temperature Display Adjustment (Offset)
0
15
Auto Mode Availability
ON
16
Maximum Cycles Per Hour
4
18
Backlight Configuration
OF
20
Outdoor Air Temperature Adjustment (Offset)
0
21
Keypad Lockout
OF
26
Minimum Cooling Set Point
60
27
Maximum Heating Set Point
85
39
Temperature Display
St
40
Fan Speeds Selection
2