Страница 1: ...technical and technological changes revisions or updates Cleveland Range LLC assumes no liability or responsibility regarding errata changes revisions or updates Qualified Cleveland Range LLC Authoriz...

Страница 2: ...Cleveland Range LLC 1333 East 179th St Cleveland Ohio U S A 44110 Ph 1 216 481 4900 Fx 1 216 481 3782 Visit our Web Site at www clevelandrange com...

Страница 3: ...ounded for 20 seconds 115 VAC is removed from HTR and sent back to IND energizing the low water light 3 When the momentary amber switch is depressed 115 VAC is sent to the R1 relay closing it The norm...

Страница 4: ...mer begins to count down 115 VAC is sent to the condensate solenoid and cold water is sent to the condensate spray nozzle pulling the steam down the drain When the steam pressure drops below the opera...

Страница 5: ...ized and the heat process begins again 11 The unit is turned off by depressing the red rocker switch 115 VAC is removed from the timing and heat circuits 115 VAC is removed from the normally open blow...

Страница 6: ......

Страница 7: ......

Страница 8: ...closed R1 contacts to energize the amber light If the low water cut off probe is not grounded for 20 seconds 115 VAC is removed from HTR and sent back to IND energizing the low water light 3 When the...

Страница 9: ...cted around the product and pulled down the drain by the condensate spray When the cooking compartment reaches 193 degrees internally the thermal switch closes and the timer begins to count down 115 V...

Страница 10: ...ing the steam down the drain 11 The unit is turned off by depressing the red rocker switch 115 VAC is removed from the timing and heat circuits 115 VAC is removed from the normally open blowdown valve...

Страница 11: ......

Страница 12: ......

Страница 13: ...es the Amber light go off With the High Limit pressure switch temporarily bypassed does the Amber light go off when the reset switch is depressed No Yes No Replace the high limit pressure switch Repla...

Страница 14: ...solenoid Replace the fill solenoid Yes Is water leaving the fill solenoid Replace wiring to drain solenoid Does the steamer have the optional intermittent blowdown timer Replace the wiring to the int...

Страница 15: ...terminal is there 1 0 micro amp DC to the ignition module No Is there flame at the pilot assy Yes Yes No Replace pilot assy and ignition wire Yes Yes Replace the pilot assy and ignition wire No Boile...

Страница 16: ...t See Boiler won t ignite Yes Is the low water indicator on 120 VAC bewtween the IND and L2 terminals on the waterboard Clean or replace the low water probe Is high pressure switch opening prematurely...

Страница 17: ...eam leaks around the door Steam Leaks Around Door Is COLD water supplied to the steamer Supply cold water 35 60 PSI to the steamer No Is the door gasket physically damaged Yes Turn over the gasket or...

Страница 18: ...1333 East 179th Street Cleveland Ohio 44110 Phone 216 481 4900 Fax 216 481 3782...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Отзывы: