5.
Remove kettle thermistor and allow to
cool. Remove edge connector from
control box. Test resistance across edge
connector's pins #2 and #7. Is it
approximately 100,000 ohms?
6.
Turn the potentiometer on the control box
clockwise to increase the maximum
operating temperature. Does the kettle
now achieve maximum operating
pressure of 30-35 psi in an empty kettle?
No
Replace defective thermistor
Yes
Kettle is operating correctly.
No
Spray contact cleaner on control
terminals and edge connector. Try box
again. If problem still exists, replace
defective control box.
Fault Isolation Procedure
Step
Test
1.
Does the green LED turn off even though
the contactors remain energized?
2.
Unplug the control box and measure the
resistance across the potentiometer, Is the
resistance approximately 0 ohms at maximum
and 50,000 ohms at minimum setting?
3.
Remove kettle thermistor and allow to cool
Remove edge connector from control box.
Test resistance across edge connector’s
pins #2 and #7. Is it approximately 100,000
ohms?
4.
Turn the potentiometer on the control box
counter-clockwise to decrease the
maximum operating temperature. does the
kettle continue to overheat?
Result
Remedy
Yes
Replace defective 12 VDC relay.
No
Go to step #
2
.
Yes
Go to step #
3
.
No
Replace defective thermistor.
Yes
Go to step #
4
.
No
Replace defective thermistor.
Yes
Spray contact cleaner on control box terminal
and edge connector. Try box again. If problem
still exists, replace defective control box.
No
Kettle is operating correctly.
Possible Causes
1.
Defective thermistor
2.
Defective potentiometer.
3.
Defective 12 VDC relay.
4.
Defective control box.
C/ Problem:
Kettle is overheating.
Fault Isolation Procedure
Step
Test
1.
Remove wire from low water level probe
and ground the wire to the body of the
kettle. Does the red LED turn off?
Result
Remedy
Yes
Replace or clean defective low water
level probe.
No
Spray contact cleaner on control box
terminals and edge connector. Try box
again. If problem still exist, replace
defective control box.
Possible Causes
1.
Defective low water level probe
2.
Defective control box.
D/ Problem:
Red LED remains illuminated even though water has been added.