Section 5 — Commissioning
Part No. 750-366
5-7
Figure 5-11. Store Lightoff
5.2.3 Curve Setup
A help screen is available to guide the user through the steps of setting the combustion curve:
Figure 5-12. Combustion setup help
To set the combustion curve, the burner must be on. If all conditions to start the boiler have been met, the
<Burner Start> pushbutton will appear on the Combustion Setup screen. Press <Burner Start>; the purge
sequence will run and the actuators will return to the lightoff position. Press <Lightoff>. The Flame Safeguard
will sequence through pilot trial and main flame and the burner will ignite. The actuators can now be
positioned for the first point.
•
8 points
minimum must be stored for a valid curve (16 maximum allowed)
• Points can not be skipped
• Values for Air and Fuel Actuator 1 must be greater than previous values for a valid point to be stored.
• Pressing <New Profile> at any time will erase the current curve.
• When the combustion curve is complete (8 valid points are stored) the <Firing Rate> button will appear,
replacing the <Main> button.
• Pressing <Pt Adv Enable> will allow stepping through the combustion curve using <Next> and <Prev>.
With Points Advance disabled, the actuators will not move when <Next> or <Prev> is pushed.
Содержание Hawk 1000
Страница 1: ...750 366 07 2013 Hawk 1000 Boiler Control Operation Manual...
Страница 4: ......
Страница 6: ......
Страница 30: ...Section 3 Hardware Checkout Hawk 1000 3 12 Part No 750 366...
Страница 54: ...Section 4 System Configuration Hawk 1000 4 24 Part No 750 366...
Страница 78: ...Section 6 Diagnostics and Troubleshooting Hawk 1000 6 6 Part No 750 366...
Страница 82: ...Section 7 Parts Hawk 1000 7 4 Part No 750 366...