Hawk 1000
Section 4 — System Configuration
Part No. 750-366
4-17
Communications failure is detected, an alarm message “Remote Communications Failed” is displayed on the
HMI and Setpoint reverts back to the LOCAL setting on the HMI
Dual Set Point
Dual Set Point control - traditionally referred to as night setback - allows the Boiler Controller to easily switch
from the primary set point (Set Point 1) to the setback set point (Set Point 2). Set Point 1 is the primary set
point for the Controller and is the only set point available if the Dual Set Point option is disallowed (see below).
Setback can be initiated manually (through the HMI on the Firing Rate screen) or remotely (by energizing an
isolated contact input signal (120 VAC) on digital input I:5.14. Press the button to the right of “Dual Set Point
Selection By” to toggle between <HMI Input> and <Digital In>.
The Dual Set Point option is not allowed when Remote Modulation, or Remote Set Point options are enabled.
Selecting <Yes> to Dual Setpoint enables dual Set Point control. This option is not allowed for low emission
steam boilers (<60 ppm).
4.4.6 Actuator Selection
FGR Actuator
The FGR actuator should be selected as “Yes” if it is present on this system. This actuator is only available for
parallel positioning control.
Fuel 1 Actuator 2
The Fuel 1 Actuator 2 should be selected as “Yes” if it is present on this system. This actuator is only available
for parallel positioning control.
Fuel 2 Actuator 2
!
Warning
Remote Set Point control should not be used on certain Low
Emission boiler systems. Low Emission boilers can be sensitive to
changing operating set points. Contact your Cleaver-Brooks
representative to determine if Remote Set Point control is allowed on
your boiler. Failure to follow these precautions may result in
damage to equipment, serious personal injury, or death.
!
Warning
Dual Set Point control should not be used on certain Low Emission
boiler systems. Low Emission boilers can be sensitive to changing
operating set points. Contact your Cleaver-Brooks representative to
determine if Dual Set Point control is allowed on your boiler. Failure
to follow these precautions may result in damage to equipment,
serious personal injury, or death.
Содержание Hawk 1000
Страница 1: ...750 366 07 2013 Hawk 1000 Boiler Control Operation Manual...
Страница 4: ......
Страница 6: ......
Страница 30: ...Section 3 Hardware Checkout Hawk 1000 3 12 Part No 750 366...
Страница 54: ...Section 4 System Configuration Hawk 1000 4 24 Part No 750 366...
Страница 78: ...Section 6 Diagnostics and Troubleshooting Hawk 1000 6 6 Part No 750 366...
Страница 82: ...Section 7 Parts Hawk 1000 7 4 Part No 750 366...