![CleaverBrooks Hawk 1000 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/cleaverbrooks/hawk-1000/hawk-1000_operation-manual_2622080057.webp)
Hawk 1000
Section 5 — Commissioning
Part No. 750-366
5-3
Figure 5-3. Actuator rotation
The default direction of rotation is counterclockwise for air and all fuels, and clockwise for FGR.
This screen also indicates the actuator torque rating (read via Modbus by the PLC).
Press <Next> after confirming the actuator direction of rotation. Next store the open and closed positions of
the actuator. Using the <Actuator Close (Open)> buttons, move the actuator to its fully open or closed
position (either position may be stored first). With the actuator fully open (closed), press <Store Open
(Close)>.
Figure 5-4. Actuator stroke
Note:
CCW rotation means the closed position will be greater than the open position.
CW rotation means the open position will be greater than the closed position.
The actuator position is given in units of degrees x 10.
Valid range is 0 - 1100 units (0-110 degrees). Open and closed positions must be greater than 100 units (10
degrees) apart. If these conditions are not met, a “Configuration Invalid” error will result, and reconfiguration
of the actuator will be required.
When valid data have been entered, the <Save Air Actuator Configuration> button will appear. Press to save
data, then press <Next Actuator> and repeat the above steps.
Содержание Hawk 1000
Страница 1: ...750 366 07 2013 Hawk 1000 Boiler Control Operation Manual...
Страница 4: ......
Страница 6: ......
Страница 30: ...Section 3 Hardware Checkout Hawk 1000 3 12 Part No 750 366...
Страница 54: ...Section 4 System Configuration Hawk 1000 4 24 Part No 750 366...
Страница 78: ...Section 6 Diagnostics and Troubleshooting Hawk 1000 6 6 Part No 750 366...
Страница 82: ...Section 7 Parts Hawk 1000 7 4 Part No 750 366...