Chapter 2
Profire V Burner
2-42
750-177
L. Air and Fuel Controls
OPEN
OPEN
FRONT
AIR SHUTTER
REAR
AIR SHUTTER
Figure 2-27: Air Shutters
The V series burners have a two-blade air shutter
design. Both blades are coupled together and are
attached to the modulation motor. Changing the
positions of the linkage rods on the linkage control
arms will change the way the damper blades open
and close.
Fuel and air flow rates can be individually adjusted at
low-fire and high-fire to achieve rated heat input,
firing rate turndown, optimum efficiency, safe
operation, and the ability to cope with environmental
changes (air temperature, humidity, barometric
pressure), and fuel property changes. Adjustments
may be required to meet certain environmental
emissions criteria, such as NOx or CO. Combustion
a d ju s t me n t s a l so v a r y wit h s p ec i f i c s ys te m
applications.
Turndown capability for oil is less than that of natural
gas. On combination fueled burners, gas turndown
performance may be restricted by the excess air and
fuel turndown levels set for oil combustion.
Excess air (O2) and unburned fuel (CO) levels in
b o i l e r f l u e g a s e s a r e u s e d t o d e t e r m i n e
combustionefficiency and fuel and air input
adjustments. The system should be adjusted to a
minimum excess airquantity that provides low levels
of unburned fuel with sufficient remaining O2 to cope
with normal atmospheric and fuel related changes.
Unburned fuel is measured as CO when burning
natural gas, and smoke spots when burning oil.
The burner should be set up and maintained to yield
smoke spot levels less than No. 1 spot (ASTM
D2156 Shell Bacharach Scale) to minimize soot and
buildup in the boiler.
!
DANGER
WARNING
Keep fingers away from the air inlet area of the
damper. The damper is actuated with sufficient force
to cause severe injury.
Содержание FLX 1000
Страница 12: ...Chapter 1 General Description 1 6 750 177...
Страница 68: ...Chapter 2 Profire V Burner 2 56 750 177...
Страница 90: ...Chapter 4 Sequence of Operation 4 10 750 177...
Страница 104: ...Chapter 5 Adjustment Procedures 5 14 750 177...
Страница 110: ...Chapter 6 Troubleshooting 6 6 750 177...
Страница 122: ...8 2 750 177 Figure 8 1 Typical Hot Water Flextube Casing...
Страница 124: ...8 4 750 177 Figure 8 2 Typical Low Pressure Steam Flextube Casing...
Страница 126: ...8 6 750 177 Figure 8 3 Typical High Pressure Steam Flextube Casing...
Страница 128: ...Parts Chapter 8 8 8 750 177 Steam Pressure Controls...
Страница 129: ...Chapter 8 Parts 750 177 8 9 Water Level Controls...
Страница 130: ...Parts Chapter 8 8 10 750 177 Water Level Controls continued...
Страница 131: ...Chapter 8 Parts 750 177 8 11 Water Column Main and Aux 15 Steam...
Страница 132: ...Parts Chapter 8 8 12 750 177 Water Column Main and Aux 150 Steam...
Страница 133: ...Chapter 8 Parts 750 177 8 13 Safety Valves...
Страница 134: ...Parts Chapter 8 8 14 750 177...
Страница 135: ......
Страница 136: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...