9
Product Documentation and Compliance for the Cisco IE 5000 Switches—
Documentation produit et conformité pour les commutateurs Cisco IE 5000
78-100604-01
Step 4
Slide the ground screw from Step 1 through the terminal lug. Insert the ground screws into the opening
on the cable side.
Figure 1-3
Attaching the Terminal Lug
Step 5
Use a ratcheting torque screwdriver to tighten the ground screws to 30 in-lb (± 2 in-lb) or 3.39 Nm (± 0.23 Nm).
Step 6
Attach the other end of the ground wire to a grounded bare metal surface, such as a ground bus or a
grounded bare rack.
1
Dual-hole terminal lug
Cisco IE 3010
20
833
5