5.7.- TRIP EVENTS
When a circuit breaker has been activated, the LEDs, output contacts and display will indicate
the cause that generated this situation.
5�7�1� EARTH LEAKAGE CURRENT INTENSITY TRIP
LED
ON
LED, fixed.
LEAKAGE
LED, fixed.
OUTPUT RELAYS
The
TRIP
relay (terminals 13,14,15) changes its status, IΔ >0,85•IΔn, in accordance with the
programmed times
The
AUX
relay (terminals 4,5) only changes its status if it has been configured as a pre-alarm
DISPLAY
Fixed red screen that shows the leakage with the earth leakage symbol (
Figure 16
).
Figure 16:Leakage screen
Prealarm symbol when this function has been activated (
Figure 17
).
Figure 17:Leakage with prealarm screen
Note :
Press the PROG key to modify the current and trip time. (
refer to
“
5�6�1 TRIP CURRENT
I
Δ
n and TRIP DELAY TIME td”
)
If the value is off the scale (> 5•IΔn),
OVR
and the pre-alarm symbol will be displayed (
Figure
18
).
Figure 18: Off the scale screen