6�- TECHNICAL FEATURES
Power Supply
Voltage
120 ... 230V ~
Frequency
50 Hz - 60 Hz
Maximun consumption
6 VA ( 230V ~)
Voltage pulse
4KV
Installation category
CAT III 300V
Current measurement circuit
Sensor input
Transformer type TP-WG, WG o WGC to 500/1
Frequency
50Hz -60Hz
Accuracy in measurement
Accuracy current measurement
< 10%
Characteristics of trip relay TRIP
Maximum voltage open contacts
1000V ~
Isolation voltage
2500V ~
Thermal current, Ith
10A
Maximum switching power
2500 ~
Electrical life (3A)
30*10
3
Characteristics of auxiliar relay AUX
Maximum voltage open contacts
1000V ~
Isolation voltage
2000V ~
Thermal current, Ith
5A
Maximum switching power
1250 VA, 150W
Electrical life (3A)
10
5
Environmental characteristics
Work temperature
-10ºC ... +50ºC
Storage temperature
-25ºC ... 70ºC
Humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Pollution resistance
Category 2
Protection degree
IP40
Mechanical caracteristics
Dimensions
35x112x84 mm (
Figure 21
)
Weight
150gr
Housing
Polycarbonate V0
Standards
Low-voltage switchgear and controlgear � Part 2: Circuit-breakers
IEC 60947-2 Anexo M: 2011
Electrical accessories - Residual current monitors for household
and similar uses (RCMs)
IEC 62020: 1998
24
RGU-2 Earth Leakage Relay
Instruction Manual
Содержание RGU-2
Страница 1: ...INSTRUCTION MANUAL M98251301 03 16A Earth leakage relay RGU 2...
Страница 2: ...2 RGU 2 Earth Leakage Relay Instruction Manual...
Страница 25: ...Figure 21 Dimensions of the RGU 2 25 Instruction Manual RGU 2 Earth Leakage Relay...
Страница 27: ...9 CE CERTIFICATE 27 Instruction Manual RGU 2 Earth Leakage Relay...
Страница 29: ...29 Instruction Manual RGU 2 Earth Leakage Relay...