        4.2.- BASIC SETUP

Once the unit has been connected, it must be programmed in accordance with the installation's 

features.

The following basic parameters can be programmed:

 

 Adjust the trip current.

 

 Adjust the trip delay time.

 

 Select the frequency of the installation to be supervised.

 5�- OPERATION 

The 

RGU-2 

unit helps control the electrical insulation level of an installation by controlling the 

intensity of the leakage current. 

Intelligent block

Actuator block

Sensor block

Inputs

O

utputs

RGU-2

An external sensor detects and measures the earth leakage current. 

Circutor

 offers the follow-

ing unit protection models in its current range of sensors: 

WG/WGS/WGC/TP-WG

.

When the instantaneous leakage current has been measured, the 

RGU-2

 unit will operate in 

accordance with the programmed parameters:

 

- Trip current (

IΔn

)

 

- Trip delay time (

td

)

As a result, the status of the device's output contacts will be changed. The output of this contact 

will be used as follows, depending on the final application type:

 

- Earth leakage protection (IEC61008-1), the circuit breakers are activated.

 

- Earth leakage monitoring (IEC62020), alarm alerts, sound and/or visual devices.

       5.1.- KEYBOARD FUNCTIONS

The unit has 3 keys: 

RESET

TEST

 and 

PROG

.

PROG

 

Key

Pressing this key displays the different screens and opens the programming mode (hold down 

the key for 2 seconds) to adjust the different programming parameters.

This key is sealable; it is supplied with a small hole where the configuration can be physically 

disabled.

12

RGU-2 Earth Leakage Relay

Instruction Manual

Содержание RGU-2

Страница 1: ...INSTRUCTION MANUAL M98251301 03 16A Earth leakage relay RGU 2...

Страница 2: ...2 RGU 2 Earth Leakage Relay Instruction Manual...

Страница 3: ...ad the manual carefully prior to connecting the unit Follow all installation and maintenance instructions throughout the unit s working life Pay special attention to the installation stan dards of the...

Страница 4: ...RY RELAY AUX 16 5 6 PROGRAMMING 17 5 6 1 TRIP CURRENT I n and TRIP DELAY TIME td 17 5 6 2 PROGRAMMING THE AUXILIARY RELAY AUX 18 5 6 3 FREQUENCY AND STATUS OF THE OUTPUT RELAY CONTACTS 18 5 6 4 LOCKIN...

Страница 5: ...log Date Revision Description 10 13 M98251301 03 13A Initial Version 11 13 M98251301 03 13B Modified Figure 1 05 16 M98251301 01 16A Modification section 2 3 3 3 4 5 6 1 5 7 1 5 7 2 6 5 Instruction Ma...

Страница 6: ...detecting element or sensor A relay A circuit breaker The unit is fully programmable It is supplied with the following 3 Keys used to TEST RESET and program the unit 2 operation LEDs that display the...

Страница 7: ...dents personal injury and damage to installations The manufacturer of the unit is not responsible for any damages resulting from failure by the user or installer to heed the warnings and or recommenda...

Страница 8: ...disconnect the unit from the power supply mains Note The connection diagram suggests a cable section of 1 1 5 mm Recommended torque 0 5 0 6 Nm Terminals opening covers or removing elements can expose...

Страница 9: ...system with RESET Figure 2 Connection diagram of the unit as a protection element shunt coil trip B UNDERVOLTAGE COIL TRIP Manual reclosing system with RESET Figure 3 Connection diagram of the unit a...

Страница 10: ...3 4 2 AS A MONITOR RCM Figure 4 Connection diagram of the unit as a monitor 10 RGU 2 Earth Leakage Relay Instruction Manual...

Страница 11: ...is supplied with the following default factory configuration Trip current scale I n 30mA Trip time scale td Instantaneous curve IN Frequency 50 Hz Auxiliary relay function Fault relay Polarity of the...

Страница 12: ...hen the instantaneous leakage current has been measured the RGU 2 unit will operate in accordance with the programmed parameters Trip current I n Trip delay time td As a result the status of the devic...

Страница 13: ...it LCD The background will be green under normal conditions The display will be red in case of events that cause an action protection trigger or circuit breaker being tripped Figure 8 Display The foll...

Страница 14: ...gure 11 Figure 11 Trip current screen Example 45mA trip current Floating screens can also be displayed they will be shown during 5 seconds and then return to the fixed active screen such as AUX relay...

Страница 15: ...ccordance with the selected trip scale Table 3 LED Bar Leakage current level Color LED bar 20 40 60 Green 80 Yellow 100 Red 5 4 INPUTS The unit has two inputs External current sensor input terminals 1...

Страница 16: ...rlocking Its operation can be programmed as a prealarm or fault relay refer to 5 6 2 PROGRAMMING THE AUXILIARY RE LAY AUX Prealarm ALAR activated when the I 0 5 I n in 200 milliseconds The logical sta...

Страница 17: ...ROG key PROG If changes have been applied SAVE will be displayed for 3 seconds and the unit will exit the programming screens If changes have not been applied EXIT will be displayed for 3 sec onds and...

Страница 18: ...the auxiliary relay RESET Prealarm ALAR This is activated when I 0 5 I n in 200 milliseconds Fault relay AUXF Shows fault events in the unit such as undervoltages or faults in the external sensor Ope...

Страница 19: ...the PROG key Status of the AUX relay contact STD by default STD Standard NO status POS NC positive safety status When this option is activated the sign will appear on all screens that refer to the AUX...

Страница 20: ...OY Y appears flashing Locked keyboard Accept with the PROG key If changes have been applied SAVE will be displayed for 3 seconds and the unit will exit the programming screens If changes have not been...

Страница 21: ...5 only changes its status if it has been configured as a pre alarm DISPLAY Fixed red screen that shows the leakage with the earth leakage symbol Figure 16 Figure 16 Leakage screen Prealarm symbol whe...

Страница 22: ...changes its status if it has been configured in the fault mode with positive safety When the power supply voltage is below the minimum operating voltage of the unit the relay output will change its st...

Страница 23: ...breaker MCB MCCB with coil is set to OFF 2 The unit returns to the normal operating conditions after the RESET key has been pressed 3 Finally the ON circuit breaker is activated manually Note In case...

Страница 24: ...auxiliar relay AUX Maximum voltage open contacts 1000V Isolation voltage 2000V Thermal current Ith 5A Maximum switching power 1250 VA 150W Electrical life 3A 105 Environmental characteristics Work tem...

Страница 25: ...Figure 21 Dimensions of the RGU 2 25 Instruction Manual RGU 2 Earth Leakage Relay...

Страница 26: ...rating or storage condition con trary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual CIRCUTOR accepts no liability du...

Страница 27: ...9 CE CERTIFICATE 27 Instruction Manual RGU 2 Earth Leakage Relay...

Страница 28: ...APPENDIX A TRIP CURVES Figure 22 Instantaneous Trip Curve Figure 23 Selective Trip Curve INSTANTANEOUS CURVE INS SELECTIVE CURVE SEL 28 RGU 2 Earth Leakage Relay Instruction Manual...

Страница 29: ...29 Instruction Manual RGU 2 Earth Leakage Relay...

Страница 30: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor es...

Отзывы: