background image

                                                                                   

GETEST 

 

 

Page 10 of 24 

- The use of a Windows-based device to control the MPC lets you take advantage of the  
 power of Windows software, and avoid having to carry other tools, like notepads,  
  calculators, etc. 
- Operates on 50 and 60 Hz networks 
- Detects non-resistive earthing connections and self-adjusts in order to measure correctly 
- Measures step and contact voltage and earth resistance 
- True-RMS voltmeter accurate to 10 mV. Auto ranging up to 700 Vac. 
- True-RMS ammeter accurate to 10 mA. Auto ranging up to 100 Vac. 
- It has built-in safety protection that make it almost impossible to cause harm to people 
- Output protected against short-circuit (25 Vac output limited to 35 A). 
 

5.2.- ELECTRICAL FEATURES  

 

Power circuit 

F-N Voltage (L1-N) 

230 Vac 

±

20%

 

Frequency 

50…60 Hz 

Current 

15 Aac 

 

 

You need a low-impedance power supply line to get maximum performance, given 
that peaks of up to 130 A for 20 ms may appear when applying maximum power. 
We recommend using cable with a cross-section of 2.5 mm

2

 or greater to get low 

resistance in the cabling. 

 

 

We recommend protecting the line with: 50 A B-curve Circuit Breaker (ICP), or 30 
A  C-curve  Circuit  Breaker,  or  16  A  D-curve  Circuit  Breaker,  per  EN60898.  This 
avoids potential firing of the protections when taking measurements with the unit. 

 

 

Measurement circuit 

Maximum output voltage 

600 Vac 

Maximum current 

50 A at 10 

 

5 A at 110 

 

Maximum power 

30 KVA 

 

Voltmeter  
Type 

True-RMS 

Input impedance  

1 K

 

 
 
 
Resolution  

700 Vac range – 0.5 Vac resolution 
280 Vac range – 0.1 Vac resolution 
105 Vac range – 0.1 Vac resolution 

70 Vac range – 0.1 Vac resolution 
30 Vac range – 0.1 Vac resolution 

0.8 Vac range – 0.1 Vac resolution 

 

Maximum voltage 

700 Vac 

Ranges 

Auto (0.8, 30, 70, 105, 280 and 700) 

Accuracy 

1% r 2 digits 

 

Содержание Getest

Страница 1: ...INSTRUCTION MANUAL M98224701 03 13A...

Страница 2: ...has the skills and knowledge related to the construction and operation of the electrical equipment and installations and who has received safety training on the hazards involved WARNING Consult the i...

Страница 3: ...as a cabo exclusivamente por pessoal qualificado O C digo El ctrico Nacional define uma pessoa qualificada como uma pessoa que se encontre familiarizada com a constru o e opera o do equipamento assim...

Страница 4: ...______________________________________________ 9 5 1 PERFORMANCE FEATURES ________________________________________________________9 5 2 ELECTRICAL FEATURES ____________________________________________...

Страница 5: ...the unit throughout its working life In particular follow the installation standards indicated in the Low Voltage Directive and additional technical instructions The installation operation and mainte...

Страница 6: ...he instrument has two ergonomic handles and we recommend it be carried by two people The device also includes two electrodes These weigh 25 kg each This weight may be harmful if it is not lifted If th...

Страница 7: ...libration certificate Samsung Galaxy Young telephone with all its components charger box etc Cocodrile clamp Cable to connect the weights Measuring pick 2 switches Instruction Manual If any problem is...

Страница 8: ...The centre of gravity of some units may be found at a considerable height Therefore when handling with a forklift it is recommended that the unit be securely fastened and that no abrupt operations are...

Страница 9: ...ications to the device or the unit specifications set out in this instruction manual without prior notice CIRCUTOR SA advises the user to obtain the device s latest version of the specifications and a...

Страница 10: ...nt 15 Aac You need a low impedance power supply line to get maximum performance given that peaks of up to 130 A for 20 ms may appear when applying maximum power We recommend using cable with a cross s...

Страница 11: ...Compliance The device complies with EU directives LVD 2006 95 EC and EMC 89 336 EEC Due to the nature of the device an injection of several amps will cause some disturbances in the power supply lines...

Страница 12: ...nical service representative 6 1 INSTALLATION The Getest may be powered directly from the mains 230 Vac and 50 60 Hz or from a single phase generator set The required power of the generator set will d...

Страница 13: ...to perform the test as well as the current and voltage coils supplied with the unit 6 2 UNIT PARTS GETEST Wiring Max R 5A Max R 10A Max R 25A Max R 50A Power on indicator Safety switch 20 A D curve c...

Страница 14: ...GETEST Page 14 of 24 PDA Android PDA Windows Mobile...

Страница 15: ...the device to a line or generator capable of supplying the required power Required power 600 V x current to be injected 3 Flip the switch 6 The red LED will light up 4 Before connecting the telephone...

Страница 16: ...switch 5 to the Enabled position 9 Select the testing mode resistance step or contact If you select resistance you must indicate the test current In step and contact mode you must indicate the maximu...

Страница 17: ...nal b Current output contactor connection c Erratic voltage measurement d Test at 25 Vac e Injection of as a minimum the required current f Increased voltage if the desired current is not reached g In...

Страница 18: ...t must not exceed 10 Hardware earthing detail You must find or build a good auxiliary earthing as it will determine whether the unit can inject the test current Bearing in mind that the ohmic value of...

Страница 19: ...yellow green to the Getest s voltage terminals yellow green Run the other end to the weights one cable for each weight Arrange the weights one metre apart from each other simulating the passage of a p...

Страница 20: ...or substation Once the connections are made select step voltage mode in the PDA and enter the maximum fault current value provided by the supply company 7 2 CONTACT VOLTAGE To perform the contact test...

Страница 21: ...contact or resistance the auxiliary earth must be good enough to allow a correct measurement Bear in mind that a poor auxiliary earth adds a series resistance to the circuit which reduces the MPC dev...

Страница 22: ...oid version 1 Connect your telephone to the computer with a USB cable 2 Enable the phone s connection to the computer 2 Enter in My PC and select the Removable device icon 3 Open the desired file 9 WA...

Страница 23: ...ontinue There is a risk of electric shock The loop resistance is too high for the requested current MPC will apply the maximum power but will not be able to reach the required value Error impossible t...

Страница 24: ...to LV Regulations or that surpasses the limits indicated in the technical and environmental features of this manual In particular capacitor units are very sensitive to adverse environmental condition...

Отзывы: