7. Once the unit is linked, return to the Circutor Getest program. Select the linked unit by opening
the following window and then clicking on the "Connect" icon.
8.- Turn the safety switch (5) to the "Enabled" position.
9.- Select the testing mode (resistance, step or contact). If you select "resistance" you must
indicate the test current. In "step" and "contact" mode, you must indicate the maximum fault
current (value provided by the supply company) and the test current.
The step and contact voltage currents are calculated using the following formulas according to the
erratic voltage values: