2.2.- WHAT SHOULD IT BE USED FOR?   

The Getest unit is designed to measure step  and contact voltages that may  arise in a transformer 
substation,  substation,  etc.  It  also  gives  you  the  option  of  calculating  the  approximate  earthing 
resistance to be tested. . 

2.3.- WHERE SHOULD IT BE USED? 

The unit is intended to operate in transformer substations, substations and high-voltage lines.  

2.4.- UNIT SAFETY  

 

This device can generate voltages that are harmful or even fatal to the human body. 
It has built-in protections that reduce the risk of electric shock to a minimum, but 
even so, you should take the necessary safety measures. 

 

  

 

This instrument can generate deadly voltages. It is essential that the operator takes 
safety measures. In the event of risk or device failure, do not hesitate to cancel the 
firing sequence. 

 

  

 

Ensure that there are no people in the current injection area of influence. 
Also ensure that nobody is handling the cables before starting the firing sequence. 

 

  

 

The device weighs 45 kg. This weight may be harmful to the user if it is handled by 
unqualified  people  or  if  it  is  lifted  incorrectly.  The  instrument  has  two  ergonomic 
handles  and  we  recommend  it  be  carried  by  two  people.  The  device  also  includes 
two  electrodes.  These  weigh  25  kg  each.  This  weight  may  be  harmful  if  it  is  not 
lifted 

 
 

If the firing sequence is accidentally started (by pushing the "START" button on the PDA), it may 
be cancelled at any time by: 
 

- Pushing the "STOP" button 
- Switching the safety switch to the "disabled" position 
- Cutting off the Bluetooth link (for example, by removing the PDA's battery or leaving  
 the coverage area) 
- Flipping the circuit breaker switch 

 
The circuit breaker switch and the safety switch are independent devices and they act directly on 
the network power supply (switch) or on the output current (security switch). In this way, even in 
an unlikely software or hardware failure, these two devices prevent current injection. 
If the sequence is not cancelled, the MPC device fires a first shot of 25 V. If the resistance found 
is higher than 110 

, a message warns the user, asking if he would like to continue or not. Bearing 

in mind that the resistance of the human body in normal conditions is 1 k

, this warning is a basic 

protection measure. 
If the sequence continues, the new MPC will only inject current for 20 ms. According to the IEC 
60479-1  standard,  the  maximum  applied  voltage  should  not  cause  ventricular  fibrillation,  even 

Содержание Getest

Страница 1: ...INSTRUCTION MANUAL M98224701 03 13A...

Страница 2: ...has the skills and knowledge related to the construction and operation of the electrical equipment and installations and who has received safety training on the hazards involved WARNING Consult the i...

Страница 3: ...as a cabo exclusivamente por pessoal qualificado O C digo El ctrico Nacional define uma pessoa qualificada como uma pessoa que se encontre familiarizada com a constru o e opera o do equipamento assim...

Страница 4: ...______________________________________________ 9 5 1 PERFORMANCE FEATURES ________________________________________________________9 5 2 ELECTRICAL FEATURES ____________________________________________...

Страница 5: ...the unit throughout its working life In particular follow the installation standards indicated in the Low Voltage Directive and additional technical instructions The installation operation and mainte...

Страница 6: ...he instrument has two ergonomic handles and we recommend it be carried by two people The device also includes two electrodes These weigh 25 kg each This weight may be harmful if it is not lifted If th...

Страница 7: ...libration certificate Samsung Galaxy Young telephone with all its components charger box etc Cocodrile clamp Cable to connect the weights Measuring pick 2 switches Instruction Manual If any problem is...

Страница 8: ...The centre of gravity of some units may be found at a considerable height Therefore when handling with a forklift it is recommended that the unit be securely fastened and that no abrupt operations are...

Страница 9: ...ications to the device or the unit specifications set out in this instruction manual without prior notice CIRCUTOR SA advises the user to obtain the device s latest version of the specifications and a...

Страница 10: ...nt 15 Aac You need a low impedance power supply line to get maximum performance given that peaks of up to 130 A for 20 ms may appear when applying maximum power We recommend using cable with a cross s...

Страница 11: ...Compliance The device complies with EU directives LVD 2006 95 EC and EMC 89 336 EEC Due to the nature of the device an injection of several amps will cause some disturbances in the power supply lines...

Страница 12: ...nical service representative 6 1 INSTALLATION The Getest may be powered directly from the mains 230 Vac and 50 60 Hz or from a single phase generator set The required power of the generator set will d...

Страница 13: ...to perform the test as well as the current and voltage coils supplied with the unit 6 2 UNIT PARTS GETEST Wiring Max R 5A Max R 10A Max R 25A Max R 50A Power on indicator Safety switch 20 A D curve c...

Страница 14: ...GETEST Page 14 of 24 PDA Android PDA Windows Mobile...

Страница 15: ...the device to a line or generator capable of supplying the required power Required power 600 V x current to be injected 3 Flip the switch 6 The red LED will light up 4 Before connecting the telephone...

Страница 16: ...switch 5 to the Enabled position 9 Select the testing mode resistance step or contact If you select resistance you must indicate the test current In step and contact mode you must indicate the maximu...

Страница 17: ...nal b Current output contactor connection c Erratic voltage measurement d Test at 25 Vac e Injection of as a minimum the required current f Increased voltage if the desired current is not reached g In...

Страница 18: ...t must not exceed 10 Hardware earthing detail You must find or build a good auxiliary earthing as it will determine whether the unit can inject the test current Bearing in mind that the ohmic value of...

Страница 19: ...yellow green to the Getest s voltage terminals yellow green Run the other end to the weights one cable for each weight Arrange the weights one metre apart from each other simulating the passage of a p...

Страница 20: ...or substation Once the connections are made select step voltage mode in the PDA and enter the maximum fault current value provided by the supply company 7 2 CONTACT VOLTAGE To perform the contact test...

Страница 21: ...contact or resistance the auxiliary earth must be good enough to allow a correct measurement Bear in mind that a poor auxiliary earth adds a series resistance to the circuit which reduces the MPC dev...

Страница 22: ...oid version 1 Connect your telephone to the computer with a USB cable 2 Enable the phone s connection to the computer 2 Enter in My PC and select the Removable device icon 3 Open the desired file 9 WA...

Страница 23: ...ontinue There is a risk of electric shock The loop resistance is too high for the requested current MPC will apply the maximum power but will not be able to reach the required value Error impossible t...

Страница 24: ...to LV Regulations or that surpasses the limits indicated in the technical and environmental features of this manual In particular capacitor units are very sensitive to adverse environmental condition...

Отзывы: