GETEST
Page 9 of 24
The forks must be flat and supported firmly by the base. The cabinet must be raised by placing the
forks underneath the profile that supports the unit.
Unloading with a forklift
3.3.- STORAGE
The unit should be stored according to the following recommendations:
-
Avoid placing it on uneven surfaces.
-
Do not store it in outdoor areas, humid areas or areas exposed to splashing water.
-
Avoid hot spots (maximum temperature: 45 ºC)
-
Avoid saline and corrosive environments.
-
Avoid storing the unit in areas where a lot of dust is generated or where the risk of
chemical or other types of contamination is present.
-
Do not place any weight on top of the unit cabinets.
-
4.-
DISCLAIMER
CIRCUTOR, SA reserves the right to make modifications to the device or the unit specifications
set out in this instruction manual without prior notice. CIRCUTOR, SA advises the user to obtain
the device's latest version of the specifications and applications at
http://www.circutor.es
CIRCUTOR, SA recommends the use of the original cables and accessories
supplied with the unit.
5.-
UNIT FEATURES
5.1.- PERFORMANCE FEATURES
- Step and contact analyzer based on current injection during one network cycle
- Provides up to 50 A to a load of 10 ohms (test earthing plus auxiliary earthing). At 5 A the
maximum loop resistance may be 110 ohms (test earthing plus auxiliary earthing).
- Maximum voltage of 600 Vac.
- Maximum power equivalent to 30 kV·A, with a weight of only 45 kg
- Remote control via Bluetooth connection. The software is easily updated and customized. It can
be controlled with any Microsoft Windows or Android device. We recommend the use of PDAs
- Data storage, easy transfer to a PC
Содержание Getest
Страница 1: ...INSTRUCTION MANUAL M98224701 03 13A...
Страница 14: ...GETEST Page 14 of 24 PDA Android PDA Windows Mobile...