background image

INSTRUCTIONS MANUAL

Step and contact voltage meter

GETEST

(M98224701-03-20A)

Содержание GETEST MPC-5

Страница 1: ...INSTRUCTIONS MANUAL Step and contact voltage meter GETEST M98224701 03 20A...

Страница 2: ...2 GETEST Instructions Manual...

Страница 3: ...ly prior to connecting the unit Follow all installation and maintenance in structions throughout the unit s working life Pay special attention to the installation standards of the National Electrical...

Страница 4: ...LATION 9 3 1 PRELIMINARY RECOMMENDATIONS 9 3 2 INSTALLATION 10 4 OPERATION 11 4 1 DESCRIPTION OF THE DEVICE 11 4 2 DESCRIPTION OF THE Getest APP 12 4 3 START UP 12 4 4 TEST TYPES 16 4 4 1 CONNECTION O...

Страница 5: ...BOLS Table 2 Symbols Symbol Description In accordance with the relevant European directive In accordance with the direct CMiM In accordance with the direct UKCA UK Conformity Assessed Device compliant...

Страница 6: ...ruction manual If you notice any reception issue immediately contact the carrier and or CIRCUTOR after sales service 1 2 TRANSPORTATION AND HANDLING Transportation loading and unloading and handling o...

Страница 7: ...h to support at least parts of that depth The forklift blades must be flat and rest firmly on the base The device must be raised supporting the blades below the profile that supports the device Figure...

Страница 8: ...iding up to 50 A for a maximum earth resistance of 10 The device roughly calculates the resistance of the ground to be tested The device features 1 smartphone to configure and perform all the measurem...

Страница 9: ...ance companies This device can generate voltage levels that are harmful to the human body and may even be deadly It has built in protection elements that reduce the risk of electric shock to a minimum...

Страница 10: ...ors it is recommended that the section of the power cables be as large as possible and of the shortest possible length to reduce voltage losses which will affect the maximum capacity of the device By...

Страница 11: ...evice Read all warnings carefully before handling and using the electrodes For use by authorised or specialised personnel only Inspect the electrodes before each measurement and do not use them if the...

Страница 12: ...tance switch Figure 3 Device description Table 4 GETEST LEDs LED Description POWER Indicates that the device is powered LINK Indicates that the device has been wirelessly connected to the Getest appli...

Страница 13: ...nect the measurement cables and the current injection cables according to the test to be performed See 4 4 TEST TYPES 2 Connect the power supply cable The device is designed to work at 230 V 50 60 Hz...

Страница 14: ...to be injected 8 Select the type of test in the Mode tab The device features 3 types of tests Step Voltage Contact Voltage and Ground Resistance 9 For standard testing on Step Voltage and Contact Volt...

Страница 15: ...rratics 10 00 00 0 2 1800 2 2 2 00 00 1800 00 00 00 00 2 1800 2 2 2 00 voltage at 180 C 00 1800 00 00 00 00 2 1800 2 2 2 00 erratic voltage Note Erratic voltages are automatically measured alerting th...

Страница 16: ...n the unlikely failure of software hardware these two devices allow to avoid the current injection 11 Once the test is completed on the Results screen of the application all the results can be consult...

Страница 17: ...ware ground connection details A good auxiliary ground must be sought out or built since it will be the one that will determine if the device can inject the test current Taking into account that the o...

Страница 18: ...aces where dangerous voltages may appear in the event of a ground fault in the installation To carry out the measurements it is necessary to follow the following steps 1 Connect the current injection...

Страница 19: ...this manual are minimum distances which will have to be increased depending on the sizing of the transformation centre or substation 4 Ensure the electrodes are stable Despite featuring a non slip de...

Страница 20: ...is necessary to follow the following steps 1 Connect the current injection cables as shown in section 4 4 1 CONNECTION OF THE HARDWARE GROUND AND AUXILIARY GROUND 2 The measurement electrodes GTEST P...

Страница 21: ...e they are stable before using them 5 Stand on the electrodes stepping inside the marked surface Figure 15 Figure 15 Stand on the electrodes Always wear non conducting safety footwear when using the e...

Страница 22: ...steps 1 Connect the current injection cables as shown in section 4 4 1 CONNECTION OF THE HARDWARE GROUND AND AUXILIARY GROUND 2 At an intermediate distance between the auxiliary ground connection and...

Страница 23: ...the values to the desired current applying the highest current it is capable of being reached Connect the device to a mains sock et connected to an installation with less impedance or to a generator w...

Страница 24: ...T application will extrapolate the values by applying a current less than the desired one Connect the GETEST to a mains socket con nected to an installation with less imped ance or to a generator with...

Страница 25: ...Scales 08 30 70 105 280 V 0 1 V Scale 700 V 0 5 V Current measurement Type True effective value Maximum current 100 A Scales 10 100 A Self adjusting Input impedance 0 1 Resolution Scale 10 A 0 01 A S...

Страница 26: ...get maximum performance since peaks of up to 130 A for 20 ms can appear when maximum power is requested Wiring with a section of 2 5mm2 or greater is recommended to maintain low resistance in the wiri...

Страница 27: ...res Connection Banana type 4 mm Dimensions Figure 18 Packaging 690 x 210 x 85 mm Weight 2 2 kg Couple Enclosure Stainless steel and EPDM Standard Safety requirements for electrical equipment for measu...

Страница 28: ...erived from a possible failure improper installation or improper usage of the unit Consequently this guarantee does not apply to failures occurring in the following cases Overvoltages and or electrica...

Страница 29: ...29 Instructions Manual GETEST 8 CE CERTIFICATE...

Страница 30: ...30 GETEST Instructions Manual...

Страница 31: ...31 Instructions Manual GETEST...

Страница 32: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Phone 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor es...

Отзывы: