6�2�- MODBUS PROTOCOL
In the Modbus protocol, the
DHC-96
device uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:
Function 0x01
:
Reading a relay.
Function 0x02
:
Reading input status.
Function 0x03 and 0x04
:
Reading integer registers.
Function 0x05
: Writing a relay.
Function 0x0F
:
Writing multiples relays
Function 0x10
: Writing multiples registers.
6�2�1� READING EXAMPLE : FUNCTION 0x01�
Question:
Status of output relays
Address
Function
Initial
Register
No� of
Registers
CRC
01
01
0000
0002
BDCB
Address: 01
, Peripheral number: 1 in decimal.
Function: 01
, Read function.
Initial Register: 0000
, on which the reading will start.
No� of Registers: 0002
, number of registers read.
CRC: BDCB
, CRC Character.
Response:
Address
Function
No� of Bytes Register No� 1
CRC
01
01
01
03
1189
Address: 01
, Responding peripheral number: 1 in decimal.
Function: 01
, Read function.
No� of bytes: 01
, No. of bytes received.
Registre: 03
, in binary it is: 0000 0011, output relays 1 and 2 closed.
CRC:1189
, CRC Character.
6�2�2� EXAMPLE OF OPERATION OF THE REMOTE CONTROL: FUNCTION 0X05�
Question:
Activate the output of relay 1, programmed to work in remote control mode.
Address
Function
Initial
Register
Relay action
CRC
01
05
0000
FF00
8C3A
Address: 01
,
Peripheral number: 1 in decimal.
Function: 05
,
Writing a relay
Initial Register: 0000
, relay 1 address.
Relay action: FF00
, We indicate that we want to close the relay.
CRC: 8C3A
, CRC Character.
35
Instruction Manual
DHC-96 mAdc, DHC-96 Adc
Содержание DHC-96 Adc
Страница 1: ...INSTRUCTION MANUAL M227B01 03 22A DC Ammeter DHC 96 mAdc DHC 96 Adc...
Страница 2: ...2 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Страница 44: ...10 CE CERTIFICATE 44 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Страница 45: ...45 Instruction Manual DHC 96 mAdc DHC 96 Adc...
Страница 46: ...46 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Страница 49: ...49 Instruction Manual DHC 96 mAdc DHC 96 Adc...