Configuration
values
Previous
Next
Confirm
and save
Delete
parameter
Back
Main
menu
Delete
character
Figure 300: Setup menu: transistor digital outputs (impulse mode)�
Use the keys
and
to select the different options.
To confirm the selection, press the key
.
● For programming the
variable code
which controls the transistor digital output use the
.
To cancel the operation of a digital output, the
00
code must be programmed.
● When programming the
energy meter factor
:
The factor of the energy meter is the amount of energy per hour needed for generating a pulse,
in Wh.
● When programming the
low period:
The low period is the time that the pulse is at its minimum value.
The programmed value is a multiple of 10 ms, i.e. when programming 1 the impulse will be at
its minimum value of 10 ms.
Maximum value
:
65536.
Minimum value:
1.
● When programming the
high period
:
The high period is the time that the pulse is at its maximum value.
The programmed value is a multiple of 10 ms, i.e., when programming 1 the impulse will be at
its maximum value of 10 ms.
Maximum value
:
65536.
Minimum value:
1.
210
CVM-A1000 - CVM-A1500
Instruction Manual
Содержание CVM-A1000
Страница 1: ...INSTRUCTION MANUAL M136B01 03 20A Power analyzer CVM A1000 CVM A1500 MEASURING EQUIPMENT E237816...
Страница 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Страница 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Страница 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Страница 366: ...366 CVM A1000 CVM A1500 Instruction Manual...
Страница 377: ...377 Instruction Manual CVM A1000 CVM A1500...