Table 32 (Continuation): Code of variables for programming the digital outputs and transistor�
Variable
Module 1
(23)
Module 2
(23)
Module 3
(23)
Module 4
(23)
Analogue input I1
934
942
950
958
Analogue input I2
935
943
951
959
Analogue input I3
936
944
952
960
Analogue input I4
937
945
953
961
(21)
In the
CVM-A1x00-FLEX
version, the neutral current is a calculated parameter, except in Single-Phase connec-
tion mode, where it is not supported.
(22)
The integrated variables are those that the device has as standard.
(23)
If in the device there is more than one module connected with the same type of inputs, the module with the
lowest number is the one with the lowest serial number.
(24)
When programming as an alarm a digital input programmed as logic state if:
- You program the maximum value = minimum value = 0 the output will show an alarm when the input has
a value of 1.
- You program the maximum value = minimum value = 1 the output will show an alarm when the input has
a value of 0.
Any other combination of values will cause erroneous behaviour of the alarm.
The pre-alarm value is not considered.
(25)
Codes valid only for programming the digital outputs of the transistor in impulse mode.
(26)
Codes not valid for programming analogue outputs.
Table 33: Code of the quality variables used for programming the digital and transistor outputs�
Quality variables
(27)
Variable
Phase Code Phase Code Phase Code
Phase Code
PST Flicker (Pst)
L1
97
L2
98
L3
99
-
-
K-factor
L1
100
L2
101
L3
102
-
-
Voltage peak factor
L1
103
L2
104
L3
105
-
-
Current peak factor
L1
106
L2
107
L3
108
-
-
Quality event
L1
109
L2
110
L2
111
III
112
Transient
L1
113
L2
114
L3
115
III
116
Variable
Code
% V Unbalance (Kd)
64
-
-
-
% I Unbalance (Kd)
66
-
-
-
% V Asymmetry(Ka)
65
-
-
-
% I Asymmetry(ka)
67
-
-
-
(
27)
The quality variables cannot be configured in the expansion modules.
● When programming the
pre-alarm value
:
If the device exceeds the programmed pre-alarm value, the icon
is activated on the
display, and the icon that indicates the alarm status changes colour:
.
The value is programmed in %.
● When programming the
minimum value
below which the relay is activated:
The units and maximum and minimum values of the variables to program are shown in
● When programming the
maximum value
above which the relay is activated:
The units and maximum and minimum values of the variables to program are shown in
203
Instruction Manual
CVM-A1000 - CVM-A1500
Содержание CVM-A1000
Страница 1: ...INSTRUCTION MANUAL M136B01 03 20A Power analyzer CVM A1000 CVM A1500 MEASURING EQUIPMENT E237816...
Страница 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Страница 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Страница 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Страница 366: ...366 CVM A1000 CVM A1500 Instruction Manual...
Страница 377: ...377 Instruction Manual CVM A1000 CVM A1500...