Note:
The maximum value must be greater than the minimum value programmed.
Table 34: Units and maximum and minimum values of the programming variables of the digital outputs�
Variable
Units
Maximum
Minimum
Phase-Neutral Voltage
V
1000.00 * voltage ratio
(28)
0
Phase-Phase Voltage
V
Neutral Voltage
V
Current
A
10.000 *current ratio
(29)
0
Neutral Current
A
Frequency
Hz
70.000
40.000
Active Power
(30)
kW
180000
-180000
Apparent Power
(30)
kVA
0
Total Reactive Power
(30)
kvar
-180000
Inductive Reactive Power
(30)
kvar
0
Capacitive Reactive Power
(30)
kvar
0
Power factor
-
1.00
-1.00
Cos φ
º
1.00
-1.00
Voltage THD %
%
100.0
0
Current THD %
%
100.0
0
Maximum Demand of
Current
A
10.000 *current ratio
(29)
0
Maximum Demand of
Active power
kW
180000
0
Maximum Demand of
Apparent Power
kVA
PST Flicker (Pst)
Pst
20.00
0.00
K-factor
-
99.99
Voltage peak factor
-
20.00
Current peak factor
-
% V Unbalance (Kd)
-
100.000
0.000
% I Unbalance (Kd)
-
% V Asymmetry(Ka)
-
% I Asymmetry(ka)
-
(28)
The voltage ratio is the ratio between the primary and secondary voltage.
(29)
The current ratio is the ratio between the primary and secondary current.
(30)
The three-phase powers accept up to 540000kW.
● When programming the
connection delay (ON)
of the relay digital output:
Maximum value:
999 s.
Minimum value:
0 s.
● When programming the
disconnection delay (OFF)
of the relay digital output:
Maximum value:
999 s.
Minimum value:
0 s.
● When programming the
output status
of the relay:
204
CVM-A1000 - CVM-A1500
Instruction Manual
Содержание CVM-A1000
Страница 1: ...INSTRUCTION MANUAL M136B01 03 20A Power analyzer CVM A1000 CVM A1500 MEASURING EQUIPMENT E237816...
Страница 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Страница 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Страница 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Страница 366: ...366 CVM A1000 CVM A1500 Instruction Manual...
Страница 377: ...377 Instruction Manual CVM A1000 CVM A1500...