Table 109: Modbus memory map: Transistor digital outputs, expansion modules (Table 5)�
Transistor Digital Outputs configuration: Slot 4
Configuration variable
Address
Alarm
Impulse
output
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Maximum value
Energy
meter factor
CF08
CF1C
CF30
CF44
CF58
CF6C
CF80
CF94
Minimum value
-
CF0A
CF1E
CF32
CF46
CF5A
CF6E
CF82
CF96
Delay in the
Connection (ON) High period
CF0C
CF20
CF34
CF48
CF5C
CF70
CF84
CF98
Delay in the
Disconnection
(OFF)
Low period
CF0D
CF21
CF35
CF49
CF5D
CF71
CF85
CF99
Value of
Pre-alarm
-
CF0E
CF22
CF36
CF4A
CF5E
CF72
CF86
CF9A
Status of
The output
-
CF0F
CF23
CF37
CF4B
CF5F
CF73
CF87
CF9B
Latch
-
CF10
CF24
CF38
CF4C
CF60
CF74
CF88
CF9C
Not used
CF11
CF25
CF39
CF4D
CF61
CF75
CF89
CF9D
Variable code
CF12
CF26
CF3A
CF4E
CF62
CF76
CF8A
CF9E
Module no
.
CF13
CF27
CF3B
CF4F
CF63
CF77
CF8B
CF9F
Note:
The 12 registers must be written and read at once (as a group), otherwise it will respond
with an error.
7�3�4�2�- Manual programming of transistor digital outputs
The following functions are implemented for these variables:
Function 0x04:
reading registers.
Function 0x10:
Writing multiple registers.
Table 110: Modbus memory map: Manual programming of outputs, expansion modules (Table 1)�
Manual programming of transistor digital outputs
Configuration variable
Valid data window
Default value
Programming status
(82)
0
: Automatic
1
:Manual
0
Value
0
: Open
1
:Closed
0
(82)
When programming the
Programming status
manually set the output for the transistors manually, using the
Value
parameter. The configuration of the transistor digital outputs programmed in the device no longer works.
The transistors work in automatic mode according to the configuration programmed in the device.
Table 111: Modbus memory map: Manual programming of outputs, expansion modules (Table 2)�
Manual programming of transistor digital outputs: Slot 1
Configuration variable
Address
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Programming status
C428
C43C
C450
C464
C478
C48C
C4A0
C4B4
Value
C429
C43D
C451
C465
C479
C48D
C4A1
C4B5
Note:
The 2 registers must be written at once (as a group), otherwise it will respond with an
error.
285
Instruction Manual
CVM-A1000 - CVM-A1500
Содержание CVM-A1000
Страница 1: ...INSTRUCTION MANUAL M136B01 03 20A Power analyzer CVM A1000 CVM A1500 MEASURING EQUIPMENT E237816...
Страница 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Страница 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Страница 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Страница 366: ...366 CVM A1000 CVM A1500 Instruction Manual...
Страница 377: ...377 Instruction Manual CVM A1000 CVM A1500...