CircuitWerkes Sicon-8 Скачать руководство пользователя страница 17

Sicon-8 Technical Manual

CircuitWerkes, Inc.

17

72

 

Set Status “polarity”.  - 

Enter 0 for normal (status is considered “ON” when grounded). Enter 1 for inverted (status is

considered “ON” when input is open or ungrounded). Example:  72, Sicon beeps, 0, Sicon beeps twice. Polarity setup

is now ended.  You must enter 72 again if you change you mind.

73 

– Alarm  Setup.

   - 

This function lets you set the number and type of alarms for the currently active channel.  Each

channel can have up to five alarms (upper & lower warning, upper & lower critical & a status alarm).  Alarms may be

set for either over-value or under-value.  An over-value alarm is one that exceeds a pre-programmed value that you

have specified.  Conversely, an under-value alarm is one that drops below a pre-programmed value that you have

specified.  Alarms may be either “warning” or “critical”.  A warning alarm can cause the Sicon-8 to attempt to correct a

situation by operating a relay.  Warning alarms are reported if they still exist when the user dials in, but don’t initiate

outbound calls.  Critical alarms make outbound telephone calls, but do not operate relays.  The Sicon-8 attempts to

rectify warning alarms up to three times, then stops.  It also stops if any new alarm occurs while a warning alarm is still

pending or if a user calls in while the alarm is still pending.  In that case, all current alarms go on the new alarm stack.

Setup:  Enter the alarm type 1-6 as follows:

1 = Metering low warning alarm   (does not call, but can activate a relay)

2 = Metering high warning alarm  (does not call, but can activate a relay)

3 = Metering low critical alarm  

(dials out & stops any automatic action of warning alarms)

4 = Metering high critical alarm  

(dials out & stops any automatic action of warning alarms)

5 = Status warning alarm  

(does not call, but can activate a relay)

6 = Status critical alarm  

(dials out & stops any automatic action of warning alarms)

For metering alarms 1-4 you must now enter the alarm limit value.  Asterisk (*) set a decimal and a Pound (#) must be

used to end the value. The Sicon-8 speaks the value that you entered back to you.  Press 1 to confirm or 0 to re-enter.     

For Status input alarms  (5-6) 0 = alarm is activated when the input is grounded.  1 = alarm is activated when the input is

open.  Note: The channel polarity can be reversed in software which also inverts the alarm.

For all warning alarms you must specify a relay channel, raise (*) function or lower(#) function, and the desired duration

of the contact closure in seconds.  You may enter fractions of a second by using the asterisk (*).  End the time setup with

the #.  To de-activate relay operation enter a zero (0) instead of a relay channel number.  Warning alarms are fixed in

order of occurrence.

For all critical alarms, you specify the two digit telephone dialer memory location that contains the telephone number you

wish to dial.  You may specify up to five dialing sequences.  Enter a # when finished.

Example #1 –

 To set up a high metering warning alarm on the current channel, the sequence might go like this:

You enter DTMF 73.  Sicon beeps.  You enter 2.  Sicon beeps. You enter a number like 10*50# which corresponds to

10.5kW.  The Sicon-8 speaks the value that you entered back.  Press 1 to confirm or 0 to re-enter.  The Sicon-8 beeps.

Enter  01 (the channel you will activate, in this case channel 1).  Enter # (the lower relay command).  Enter 3*5 (for 3.5

seconds).  The Sicon-8 confirms the time value by speaking “3-point-5” back to you.  Confirm by entering a 1 or re-enter

the value by pushing a 0.  If the meter detects a high warning alarm condition, the Sicon will now close channel one’s

relay for 3.5 seconds.  It will take a reading to see if the condition still exists.  If it does still exist, the Sicon will then try

twice more to correct the problem.  The full programming sequence for this example is: 73,2,10*50#,1,01,3*5#,1.

Example #2 –

 Set the current channel’s status input as a critical alarm:

Enter DTMF 73.  Sicon beeps.  You enter 6.  Sicon beeps.  Enter 0 (this alarm will activate if its input is grounded).

Sicon beeps.  Enter 01 (this assumes you want to use the telephone number that you have stored in memory 01.  You

can use 01 thru 20).  Sicon beeps twice indicating that you have successfully programmed the alarm.  The complete

programming sequence for this example is: 73,6,0, 01#.  To add additional dialer numbers the sequence might be:

73,6,0, 01,02,03#.   The alarm could also be activated when ungrounded by entering a 1 after the 6 instead of a 0.

Содержание Sicon-8

Страница 1: ...KE E ES S S M M Ma a ak k ke e er r rs s s o o of f f I I In n nn n no o ov v va a at t ti i iv v ve e e E E El l le e ec c ct t tr r ro o on n ni i ic c cs s s Sicon 8 Transmitter Site Controller Ha...

Страница 2: ......

Страница 3: ...ged in around your site and equipment plugged into them can then be turned on or off by the Sicon 8 with no external wiring to the remote locations With the Sicon 8 you re not limited to the dial up t...

Страница 4: ...de directly to the carrier Do not delay Call the carrier as soon as damage is discovered You should have received the following items with each Sicon 8 that you have purchased 4 depluggable screw term...

Страница 5: ...X10 RJ 11 Connects to a Powerhouse model PL513 or equiv X10 transmitter for more control Note Not for Telephone Use SX 8 RJ 45 Connects to 8 channel expander chassis for extra channels THIS PORT IS NO...

Страница 6: ...LED Indicator Indicates that the 5V relay supply is working Local Telephone Input output This RJ 11 jack provides a means to program operate the Sicon 8 from the front panel This jack is always active...

Страница 7: ...tware support for virtual serial ports for them to be used with the Sicon 8 The Sicontroller interface lets you hide any or all of the meter and control panels letting you display only the ones that y...

Страница 8: ...er a relay changes state Output Gain Control Sets the level of audio that is at the Audio Output jack at the rear of the Sicon 8 The audio at this jack will be the voice responses of the Sicon 8 and a...

Страница 9: ...with a ground a 5V output and the external power input for driving status inputs The 5V output and ground can be used to drive external devices like temperature probes The ext input and ground let yo...

Страница 10: ...raise relays and equipment turned off or parameters lowered with the lower relays The first six channels consist of heavy duty SPDT relays rated at 3 A 30 VDC or 3 A 250 VAC which operate in momentar...

Страница 11: ...Sicon 8 s internal 5V supply and source your own Voltage up to 24V to inputs 1 8 To Source Voltage you must first move the PWR SEL jumper JP517 from Int to Ext Be sure to never jumper both simultaneo...

Страница 12: ...ill be required to enter a valid password before the unit will accept commands The only user password that is factory set is 6736 for the Super Administrator The Sicon 8 is pre programmed with a basic...

Страница 13: ...ord silence into this location so a malicious caller will not recognize the need to enter a password The factory programmed defaults for the Sicon 8 are as follows Passwords DTMF Super Admin PW 6736 S...

Страница 14: ...voice connection requires only a telephone line routed from your wall jack to the TELCO jack on the Sicon 8 It is highly recommended to route the telephone line through a TELCO surge suppressor befor...

Страница 15: ...nable AutoScan for each channel 01 16 Channel menu When you enter a channel the Sicon 8 immediately reports all parameters for that channel You may enter a DTMF command at any time during the channel...

Страница 16: ...tup is identical to Linear with Scaling above The Sicon 8 beeps once Enter actual value of the physical meter the appropriate meter on the transmitter that is associated with this channel The Asterisk...

Страница 17: ...tus input alarms 5 6 0 alarm is activated when the input is grounded 1 alarm is activated when the input is open Note The channel polarity can be reversed in software which also inverts the alarm For...

Страница 18: ...y or latching mode Momentary mode works just like all other relays on the Sicon 8 except that the relays on these channels are the DPDT type with two sets of normally open and normally closed contacts...

Страница 19: ...setting the Sicon 8 to Local mode the remote local switch on any transmitter or high Voltage equipment also be set to the local mode Relay Operation The Sicon 8 employs six channels 1 thru 6 of SPST...

Страница 20: ...ay is latching then closes the raise relay for the tone duration 1latches the lower relay and 0 unlatches the lower relay When relays 7 and or 8 are in latching mode and the raise lower relays are loc...

Страница 21: ...ted This password is used to remotely toggle off on the Sicon 8 s local mode Its use can be dangerous only senior management should have access to the password 71 Passwords setup There are five passwo...

Страница 22: ...rings that has been set in 79 below Default 20 If the remote toggling is enabled See 94 of the system setup menu you can use your remote toggle password default 1379 to change from local mode to remot...

Страница 23: ...ut to speak it will first close the Raise relay of Channel 8 and wait for one second then it will speak Note however that the push to talk relay will not be closed prior to speaking if the Sicon 8 is...

Страница 24: ...e triggered by events We call these functions actions There are four main event modes that can be used 1 One Shot An event that takes place only once and is never repeated 2 Repeating An event that oc...

Страница 25: ...wice You can now go to the Setting the action section below Step 7 If an event will re occur periodically you must tell the Sicon 8 how often the event will happen This consists of two parts Entering...

Страница 26: ...not reported Timed events create new reference readings For details see the sub section titled About readings alarms Alarm Dialing on P27 89 record a phrase The Sicon 8 allows most words phrases to be...

Страница 27: ...also enter any system command or a channel number to jump to a command metering channel About readings alarms Alarm Dialing Like most remote controls the Sicon 8 takes reference readings particularly...

Страница 28: ...control is disabled audio input is normally muted then this will unmute the audio input for 15 seconds or until a DTMF tone is entered by the user If audio control is enabled this simply toggles the a...

Страница 29: ...cal Setup Port Powered RJ 11 jack Connects to standard telephone NOT phone line PC Communication 38400 bps RS 232 8 bits 1 stop bit no parity bit no flow control on female DB 9 Ethernet Etherstuf ET 1...

Страница 30: ...iginal serial number if applicable has been modified or removed NO OTHER WARRANTY EXPRESS OR IMPLIED INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR USE APPLIES TO THE EQUIPMENT no...

Страница 31: ...3sec 82 Meter 4 3sec 83 Meter 5 3sec 84 Meter 6 3sec 85 Meter 7 3sec 86 Meter 8 3sec 87 Meter 9 3sec 88 Meter 10 3sec 89 Meter 11 3sec 90 Meter 12 3sec 91 Meter 13 3sec 92 Meter 14 3sec 93 Meter 15 3s...

Страница 32: ...e Expansion Port Telemetry Port Status Port Buttons and LEDs Control Port Gain Select Voice Record Playback Telephone Interface Audio Interface Host Modem RS 232 X 10 RS 232 DB 9 DB 9 Depluggable Term...

Отзывы: