CircuitWerkes Sicon-8 Скачать руководство пользователя страница 11

Sicon-8 Technical Manual

CircuitWerkes, Inc.

11

Metering & Status Connections

Eight metering channels are brought into the Sicon-8 on a depluggable euro-connector located at the center of the

back panel (see Figure 2 above).  These analog inputs can handle either positive or negative voltages of up to 12 Volts,

however  all inputs must  be  ground  referenced  by  connecting  your  metering  ground  to  the  Sicon-8's  ground.    To  make

setup and operation simpler, each input is auto-ranging.  You do not have to adjust any potentiometers to set the proper

input range. Inputs are self-calibrating and are based on an internal, precision, low-drift, voltage reference, so the meters

will not drift over time or with temperature.  Metering setup is as simple as connecting the sample voltage and then telling

the  Sicon-8  what  the  input  voltage  represents.    DO  NOT  CONNECT  SAMPLE  VOLTAGES  IN  EXCESS  OF  12V  OR

DAMAGE MAY OCCUR TO YOUR SICON-8.

Floating Grounds

Except for status input #8, 

none

 of the Sicon-8’s metering or status inputs will accept a floating ground.

Damage to the Sicon-8 or your equipment may result from connecting a floating ground output to the Sicon-8.

If you must use a metering or status inputs with equipment that has a floating ground, an isolation amplifier

must be used.

The Sicon-8's optically-isolated status inputs can be used to determine the status (on/off) of your

equipment.  The status input connector is located immediately to the right of the metering connector and the

first seven status channels accept only contact closures as inputs.  If the voltage at the input is at or very near

ground, then the status channel is considered active, and if it is ungrounded, the channel is considered

inactive.  The logic can be reversed on each channel, in firmware, so that the status is considered active when

ungrounded.   You can also choose to disconnect the Sicon-8's internal 5V supply and source your own

Voltage (up to 24V) to inputs 1-8.  To Source Voltage, you must first move the “PWR SEL” jumper (JP517)

from “Int” to “Ext”. Be sure to never jumper both simultaneously.  Then you connect your Voltage source to the

Ext input and ground of the “Stat Pwr” (JP-525) connector located just to the right of JP517.  Internal 5V is also

brought out to the “Stat Pwr” connector should you want to use it for powering temperature probes, etc.  Never

connect up an external Voltage source to the status inputs without moving Jumper JP517 to “Ext”.

Regardless of whether you use the internal Voltage source or your own, your equipment's ground must be tied

to the Sicon-8's ground.
In addition to the ability to source an external Voltage to the status inputs, the eighth status channel provides

some additional flexibility.  Based on the “Ch8 SEL” (JP-517) jumper setting, you may configure channel 8 so

that your equipment sources current to or sinks current from the Sicon-8.  In either case, if current is flowing,

then the input is considered active, but again, this may be inverted according to your preferences.  If both

jumpers are removed from JP-517, you can supply your own, floating Voltage to channel 8’s + and – inputs.  If

you don't want to source your own current to status channel 8, one line is provided with +5 V.  This line is

diode-protected and current-limited.  It is not required that a +5V line be used to source current to channel 8. It

will tolerate up to 24 VDC as input, but at least 3 VDC is needed to turn the optoisolator on.  The status inputs

will not accept AC Voltages.  If an AC input is required, a bridge rectifier with a small capacitor at its output

should be used to convert the sample to DC before connecting it to the Sicon-8's status input.  As noted above

under metering, except for status input #8, connecting a floating ground to your unit may result in damage to

the Sicon-8 or the device that is connected to the Sicon-8.  It will may also result in erroneous readings or

status indications.

     

Fig. 2 - Sicon-8 Back Panel

Diagram

Содержание Sicon-8

Страница 1: ...KE E ES S S M M Ma a ak k ke e er r rs s s o o of f f I I In n nn n no o ov v va a at t ti i iv v ve e e E E El l le e ec c ct t tr r ro o on n ni i ic c cs s s Sicon 8 Transmitter Site Controller Ha...

Страница 2: ......

Страница 3: ...ged in around your site and equipment plugged into them can then be turned on or off by the Sicon 8 with no external wiring to the remote locations With the Sicon 8 you re not limited to the dial up t...

Страница 4: ...de directly to the carrier Do not delay Call the carrier as soon as damage is discovered You should have received the following items with each Sicon 8 that you have purchased 4 depluggable screw term...

Страница 5: ...X10 RJ 11 Connects to a Powerhouse model PL513 or equiv X10 transmitter for more control Note Not for Telephone Use SX 8 RJ 45 Connects to 8 channel expander chassis for extra channels THIS PORT IS NO...

Страница 6: ...LED Indicator Indicates that the 5V relay supply is working Local Telephone Input output This RJ 11 jack provides a means to program operate the Sicon 8 from the front panel This jack is always active...

Страница 7: ...tware support for virtual serial ports for them to be used with the Sicon 8 The Sicontroller interface lets you hide any or all of the meter and control panels letting you display only the ones that y...

Страница 8: ...er a relay changes state Output Gain Control Sets the level of audio that is at the Audio Output jack at the rear of the Sicon 8 The audio at this jack will be the voice responses of the Sicon 8 and a...

Страница 9: ...with a ground a 5V output and the external power input for driving status inputs The 5V output and ground can be used to drive external devices like temperature probes The ext input and ground let yo...

Страница 10: ...raise relays and equipment turned off or parameters lowered with the lower relays The first six channels consist of heavy duty SPDT relays rated at 3 A 30 VDC or 3 A 250 VAC which operate in momentar...

Страница 11: ...Sicon 8 s internal 5V supply and source your own Voltage up to 24V to inputs 1 8 To Source Voltage you must first move the PWR SEL jumper JP517 from Int to Ext Be sure to never jumper both simultaneo...

Страница 12: ...ill be required to enter a valid password before the unit will accept commands The only user password that is factory set is 6736 for the Super Administrator The Sicon 8 is pre programmed with a basic...

Страница 13: ...ord silence into this location so a malicious caller will not recognize the need to enter a password The factory programmed defaults for the Sicon 8 are as follows Passwords DTMF Super Admin PW 6736 S...

Страница 14: ...voice connection requires only a telephone line routed from your wall jack to the TELCO jack on the Sicon 8 It is highly recommended to route the telephone line through a TELCO surge suppressor befor...

Страница 15: ...nable AutoScan for each channel 01 16 Channel menu When you enter a channel the Sicon 8 immediately reports all parameters for that channel You may enter a DTMF command at any time during the channel...

Страница 16: ...tup is identical to Linear with Scaling above The Sicon 8 beeps once Enter actual value of the physical meter the appropriate meter on the transmitter that is associated with this channel The Asterisk...

Страница 17: ...tus input alarms 5 6 0 alarm is activated when the input is grounded 1 alarm is activated when the input is open Note The channel polarity can be reversed in software which also inverts the alarm For...

Страница 18: ...y or latching mode Momentary mode works just like all other relays on the Sicon 8 except that the relays on these channels are the DPDT type with two sets of normally open and normally closed contacts...

Страница 19: ...setting the Sicon 8 to Local mode the remote local switch on any transmitter or high Voltage equipment also be set to the local mode Relay Operation The Sicon 8 employs six channels 1 thru 6 of SPST...

Страница 20: ...ay is latching then closes the raise relay for the tone duration 1latches the lower relay and 0 unlatches the lower relay When relays 7 and or 8 are in latching mode and the raise lower relays are loc...

Страница 21: ...ted This password is used to remotely toggle off on the Sicon 8 s local mode Its use can be dangerous only senior management should have access to the password 71 Passwords setup There are five passwo...

Страница 22: ...rings that has been set in 79 below Default 20 If the remote toggling is enabled See 94 of the system setup menu you can use your remote toggle password default 1379 to change from local mode to remot...

Страница 23: ...ut to speak it will first close the Raise relay of Channel 8 and wait for one second then it will speak Note however that the push to talk relay will not be closed prior to speaking if the Sicon 8 is...

Страница 24: ...e triggered by events We call these functions actions There are four main event modes that can be used 1 One Shot An event that takes place only once and is never repeated 2 Repeating An event that oc...

Страница 25: ...wice You can now go to the Setting the action section below Step 7 If an event will re occur periodically you must tell the Sicon 8 how often the event will happen This consists of two parts Entering...

Страница 26: ...not reported Timed events create new reference readings For details see the sub section titled About readings alarms Alarm Dialing on P27 89 record a phrase The Sicon 8 allows most words phrases to be...

Страница 27: ...also enter any system command or a channel number to jump to a command metering channel About readings alarms Alarm Dialing Like most remote controls the Sicon 8 takes reference readings particularly...

Страница 28: ...control is disabled audio input is normally muted then this will unmute the audio input for 15 seconds or until a DTMF tone is entered by the user If audio control is enabled this simply toggles the a...

Страница 29: ...cal Setup Port Powered RJ 11 jack Connects to standard telephone NOT phone line PC Communication 38400 bps RS 232 8 bits 1 stop bit no parity bit no flow control on female DB 9 Ethernet Etherstuf ET 1...

Страница 30: ...iginal serial number if applicable has been modified or removed NO OTHER WARRANTY EXPRESS OR IMPLIED INCLUDING WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR USE APPLIES TO THE EQUIPMENT no...

Страница 31: ...3sec 82 Meter 4 3sec 83 Meter 5 3sec 84 Meter 6 3sec 85 Meter 7 3sec 86 Meter 8 3sec 87 Meter 9 3sec 88 Meter 10 3sec 89 Meter 11 3sec 90 Meter 12 3sec 91 Meter 13 3sec 92 Meter 14 3sec 93 Meter 15 3s...

Страница 32: ...e Expansion Port Telemetry Port Status Port Buttons and LEDs Control Port Gain Select Voice Record Playback Telephone Interface Audio Interface Host Modem RS 232 X 10 RS 232 DB 9 DB 9 Depluggable Term...

Отзывы: