18
Wallbox eNext Series Installation Manual
L
N
P
E
Protections
SINGLE-PHASE Charge Point
•
Connect to the
230VAC
.
THREE-PHASE Charge Point
•
Connect to the
400VAC
.
•
If the Power Supply is Single-
Phase, connect L1 and N.
L1
L2
L3
N
P
E
Protections
Do not forget to connect the ground cable to the ground terminal
Make sure all screws are securely tightened at 4 - 5 Nm
Terminal block maximum cross-section: 10mm
2
S
Type of cable allowed by the terminal block: Copper
Cu
External electric protections should be placed upstreams as shown below: