EN
EN - 39
No.
Word sequence
Values
Comments
Factory setting
154
Max water setpoint end
heating variation
20°C to 40°C in increments of 0.5
68°F to 104°F in increments of 1
Setting the
maximum setpoint
for water return to
the heat pump...
for underfloor heating system
35°C
95°F
20°C to 55°C in increments of 0.5
68°F to 131°F in increments of 1
for terminal units (fan coil units or radiators)
45°C
113°F
55°C
131°F
20°C to 70°C in increments of 0.5
68°F to 170°F in increments of 1
for terminal units (fan coil units or radiators)
in back up operation
155
Outdoor air T° start
heating variation
-10°C to 30°C in increments of 1
14°F to 86°F in increments of 1
Outdoor air
temperature above
which the water
setpoint (P152 or
P153) is maintained.
for terminal units (fan coil units or radiators)
20°C
68°F
17°C to 25°C in increments of 1
63°F to 77°F in increments of 1
for underfloor heating system
156
Outdoor air T° end
heating variation
-15°C to (P155-5°C) in increments of 1
5°F to (P155-9°F) in increments of 1
Outdoor air
temperature
below which the
maximum water
setpoint (P154) is
maintained.
for terminal units (fan coil units or radiators)
-7°C
19°F
-15°C to 8°C in increments of 1
5°F to 46°F in increments of 1
for underfloor heating system
160
Hot air
comfort setpoint
15 to 30°C in increments of 0.5°C
Setting the ambient air setpoint in zone 2 in comfort mode
21°C
59 to 86°F in increments of 1
70°F
161
Hot air
eco setpoint
15 to P160°C in increments of 0.5
Setting the ambient air setpoint in zone 2 in economy mode
19°C
59 to P160°F in increments of 1
59°F
162
Hot water
comfort setpoint
25 to P164°C in increments of 0.5
Setting the water supply setpoint in zone 2 in comfort mode
25°C
77 to P164°F in increments of 1
77°F
164
Max water setpoint end
heating variation
25 to 45°C in increments of 0.5°C
Setting the max. water supply setpoint in zone 2
40°C
77 to 113°F in increments of 1
104°F
165
Outdoor air T° start
heating variation
17 to 25°C in increments of 1
Outdoor air temperature above which the water setpoint is
maintained in zone 2
20°C
63 to 77°F in increments of 1
68°F
166
Outdoor air T° end
heating variation
-15 to 8°C in increments of 1
Outdoor air temperature below which the max. water setpoint is
maintained in zone 2
-7°C
5 to 46°F in increments of 1
19°F
170
Air
setpoint
8 to 15°C in increments of 0.5
47°F to 59°F in increments of 1
Setting the frost-free air setpoint
10°C
50°F
171
Air absence setpoint
8 to P170 in increments of 0.5
Setting the frost-free air setpoint in zone 2
10°C
47 to P170 in increments of 1
50°F
172
DHW Setpoint
48 to 70°C in increments of 1
118°F to 152°F in increments of 1
Setting the DHW tank setpoint
65°C
149°F
173
DHW thermo
heating period
00:00 to 02:00 in increments of
30 mins
Setting the max. DHW tank thermodynamic heating period
01:00
174
Pool water setpoint
20°C to 35°C in increments of 0.5
68°F to 95°F in increments of 1
Setting the pool setpoint
28°C
82°F
175
DHW heating elements
heating period
00:00 to 04:00 in increments of
30 mins
Setting the max. DHW tank electric heating element thermodynamic heating
period
04:00
176
crank_heater_power
0 to 100W in increments of 10W
Enter the power of the crankcase heater if option to install one
0 W
177 el_heating_element _power
0 to 5kW in increments of 1kW
Enter the power of the electric heating element if an electric heating element
kit is installed
0 kW
178
presence of tank sensor
NO
If there is no sensor in the DHW TANK, the DHW setpoint is controlled via the
heat pump water return
YES
YES
If there is a sensor in the DHW TANK, the DHW setpoint is controlled via the
tank's internal temperature
180
Heat pump stage diff
0.5°C to 5°C in increments of 0.5
1°F to 9°F in increments of 1
Setting the compressor operation differential
4°C
7°F
181
Heating element stage diff
0.5°C to 10°C in increments of 0.5
1°F to 18°F in increments of 1
Setting the heating element operation differential
2°C
3°F
183
Boiler operation diff
0.5°C to 3°C in increments of 1
1°F to 5°F in increments of 1
Setting the operation differential of the boiler controlled by the heat pump
control
1°C
2°F
190
Outdoor air T° limit
heating element authorisation
-20°C to 24°C in increments of 1
-4°F to 75°F in increments of 1
Outdoor air temperature setting below which the heat pump is not authorised
to operate
-20°C
-4°F
191
Outdoor air T° limit
heating element operation
P190 to 24°C in increments of 1
P190 to 75°F in increments of 1
Outdoor air temperature setting below which the heating elements are
authorised to operate
5°C
41°F
193
Outdoor air T° cooling
accelerator pump stop
20 to 30°C in increments of 1
Outdoor air temperature setting below which the indoor accelerator pump is
not authorised to operate
25°C
68 to 86°F in increments of 1
77°F
194
Outdoor air T° heating
accelerator pump stop
15°C to 30°C in increments of 1
50°F to 86°F in increments of 1
Outdoor air temperature setting above which the indoor accelerator pump is
not authorised to operate
20°C
68°F
Note: Cooling mode on a heat pump can only operate if the emitter (P07) is not a radiator.