3.2.4 Machine configuration
- Set the machine parameters according to the type of system (see Machine parameters table in paragraph 5.3).
Lock parameter P99 on YES. Parameter P99 is accessible in the Machine parameters sub-menu of the Unit configuration menu.
The on/off icon is displayed in the main menu.
3.2.5 Starting the heat pump
Position the on/off icon in the main menu selection box then confirm by pressing the button. The unit starts up in comfort heating
mode by default. The accelerator pump starts up, then once the short cycle protection is completed the compressor starts up.
Specific to single-phase models:
In order to meet the requirements of French standard NF-C 15 100 on start-up current limits, your unit features a smart system
that monitors this current. In order to enable the electronics to self-configure and thus adapt to your system, it may not take place
instantaneously when started for the first time (or after a power cut). The unit may attempt to start, acquire some values and then
restart under the best possible conditions.
Specific to the three-phase model
:
The GeoCIAT
TM
Modular
45HT model does not have a phase controller as standard. Electrical connection of the control board may
cause the compressor to rotate in reverse. This is not harmful to the compressor if it is stopped quickly. 2 outcomes are possible:
- The compressor noise will alert you to reverse rotation => Stop the heat pump using the ON/OFF button on the HMI then
reverse the 2 phases on the electronic board (power off first)
- The monitoring software detects a "COMPRESSOR ROTATION" fault => reverse the 2 phases using the above procedure.
Select "Replace" using the
button then
CLIC
Heat pump pairing
S
TimuLaTe
THe
macHine
(
See
manuaL
)
S
eTTing
: canceL
Heat pump pairing
d
eLeTe
B
ack
c
Heck
replace
Replacing a HomeConnect board following an electronic fault:
When an electronic board is replaced, the control terminal retains a certain number of components. The following procedure
should be performed:
In the "UNIT CONFIGURATION" tab, "Pairing", "Heat pump pairing" then select "Heat pump". The screens below will appear:
The heat pump stimulation request screen then appears.
When the message opposite appears, follow the heat pump stimulation
procedure, observing the correct powering up and powering off times
Warning
: when the "Replacement" function is used, all the components must be re-paired in accordance with the rules for
replacing components such as the outdoor sensor, indoor sensor, etc.