No.
Word sequence
Values
Comments
Factory setting
06
Glycol presence outdoor
circuit
NO
MPEG20%
MPEG40%
Pure water on the primary circuit
Glycol/water mix on the primary circuit, max. glycol content MPEG20%
Glycol/water mix on the primary circuit, max. glycol content MPEG40%
NO
07
Heating type
UHCS
FAN
RADIATOR
FAN+UHCS*
RUHCS*
2UHCS*
Underfloor heating system
Fan coil units
Radiators
Fan coil units + Underfloor heating system
Rad Underfloor heating system
2 Underfloor heating systems
UHCS
08
DHW heating
NO
HEAT PUMP
SOLAR
No domestic hot water production
Thermodynamic domestic hot water production
Solar domestic hot water production
NO
09
Pool heating
NO
YES
No pool heating
Pool heating with heat pump
NO
10
Humidity sensor check
NO
YES
No humidity check on the underfloor heating and cooling system
Humidity sensor connection
NO
11
Heating element type
NO
ELECTRIC
BOILER
No heating elements on the system
Management of electric heating element integrated in the heat pump
Installation of heat pump for boiler backup operation:
ELECTRIC
12
Boiler operation
SIMULTANEOUS
ALTERNATE
Boiler controlled by heat pump control
Boiler controlled by its own control
SIMULTANEOUS
13
Bypass control
Heat pump
HEATING ELEMENT
HP + HEATING ELEMENT
Possibility of heat pump load bypass
Possibility of auxiliary bypass
Possibility of heat pump and heating element bypass
Heat pump
14
Customer pump
management
NO
CONTINUOUS
SIMULTANEOUS
REGULATED
No HomeConnect control management
Continuous operation in heating, cooling or absence mode
Controlled by operation of GeoCIATTM Modular accelerator pump
Regulated by the room sensor based on the indoor environment control
differential setpoints
NO
15
Customer control
NOT USED
COOLING/HEATING
ABSENCE
DHW
On/Off input J11 (terminals 2 and 3) not used
Input used to force the heat pump to stop or into heating mode
Input used to force the heat pump into absence mode
Input used to control domestic hot water production
NOT USED
16
Econo mode signal
management
NO
YES
No connection to comfort units (V2000, V30 type, etc.)
Management of econo mode signal on comfort units
NO
17
Boiler operation direction
of action
NO
NC
Boiler operating authorisation via opening of heating element contact
Boiler operating authorisation via closing of heating element contact
NC
18
Main zone selection
UHCS
RADIATOR
FAN
If P07 activated in dual zone mode (FAN + UHCS or RUHCS)
UHCS
19
DHW 3-way valve direction
of action
NO
NC
Supply direction for 3-way valve when DHW mode is active.
Power supply logic. When the 3-way valve is supplied, the 3-way valve switches
to DHW mode
NO
99
Parameter locking
NO
YES
Unlocking of the setting range of the machine parameters
Locking of the machine parameter values and heat pump operating
authorisation
NO
5.3 Configuration
You will have to adjust a number of parameters to suit your particular system and requirements. These parameters (identified by
the letter 'P' followed by a digit) will help you to keep your unit operating at its peak performance.
To access the parameters, enter the Unit configuration menu
on the control terminal.
The parameters are grouped into 3 families:
-
Machine parameters
-
Adjustment parameters
-
Reading parameters
Machine parameters
The Machine parameters are used to quickly configure the heat pump in accordance with the system.
IMPORTANT:
Only qualified personnel may access the machine parameters.
Setting P99
For security reasons relating to the operation of the heat pump, parameter P99 is used
to lock the machine parameter values .
Once configuration is complete, make sure that machine parameter P99 is locked by selecting
the value YES in the setting field.
A key symbol appears in front of the machine parameters number to indicate that the
parameters are no longer modifiable.
If machine parameter P99 is not locked (P99=NO), it is not possible to start up the heat pump: The On/Off button is
not visible in the main menu.
MACH. PARAMETERS
09 cHauffage piScine
no
UNIT CONFIGURATION
c
ommiSSioning
m
acH
.
parameTerS
a
djuST
.
parameTerS
r
eading
parameTerS