EN

EN - 37

No.

Word sequence

Values

Comments

Factory setting

06

Glycol presence outdoor 

circuit

NO
MPEG20%
MPEG40%

Pure water on the primary circuit 

Glycol/water mix on the primary circuit, max. glycol content MPEG20%
Glycol/water mix on the primary circuit, max. glycol content MPEG40%

NO

07

Heating type

UHCS
FAN
RADIATOR
FAN+UHCS*
RUHCS*
2UHCS*

Underfloor heating system
Fan coil units

Radiators

Fan coil units + Underfloor heating system
Rad Underfloor heating system
2 Underfloor heating systems

UHCS

08

DHW heating

NO

HEAT PUMP
SOLAR

No domestic hot water production 
Thermodynamic domestic hot water production

Solar domestic hot water production

NO

09

Pool heating

NO

YES

No pool heating 
Pool heating with heat pump

NO

10

Humidity sensor check

NO

YES

No humidity check on the underfloor heating and cooling system
Humidity sensor connection 

NO

11

Heating element type

NO

ELECTRIC
BOILER

No heating elements on the system
Management of electric heating element integrated in the heat pump
Installation of heat pump for boiler backup operation:

ELECTRIC

12

Boiler operation

SIMULTANEOUS
ALTERNATE

Boiler controlled by heat pump control
Boiler controlled by its own control

SIMULTANEOUS

13

Bypass control

Heat pump
HEATING ELEMENT
HP + HEATING ELEMENT

Possibility of heat pump load bypass 
Possibility of auxiliary bypass 
Possibility of heat pump and heating element bypass

Heat pump

14

Customer pump 

management

NO

CONTINUOUS
SIMULTANEOUS

REGULATED

No HomeConnect control management
Continuous operation in heating, cooling or absence mode

 

Controlled by operation of GeoCIATTM Modular accelerator pump 
Regulated by the room sensor based on the indoor environment control 
differential setpoints

NO

15

Customer control

NOT USED
COOLING/HEATING
ABSENCE
DHW

On/Off input J11 (terminals 2 and 3) not used

Input used to force the heat pump to stop or into heating mode
Input used to force the heat pump into absence mode
Input used to control domestic hot water production 

NOT USED

16

Econo mode signal 

management

NO

YES

No connection to comfort units (V2000, V30 type, etc.)

Management of econo mode signal on comfort units

NO

17

Boiler operation direction 

of action

NO
NC

Boiler operating authorisation via opening of heating element contact
Boiler operating authorisation via closing of heating element contact

NC

18

Main zone selection

UHCS

RADIATOR

FAN

If P07 activated in dual zone mode (FAN + UHCS or RUHCS)

UHCS

19

DHW 3-way valve direction 

of action

NO
NC

Supply direction for 3-way valve when DHW mode is active.
Power supply logic. When the 3-way valve is supplied, the 3-way valve switches 
to DHW mode

NO

99

Parameter locking

NO

YES

Unlocking of the setting range of the machine parameters 

Locking of the machine parameter values and heat pump operating 

authorisation

NO

5.3 Configuration

You will have to adjust a number of parameters to suit your particular system and requirements. These parameters (identified by 

the letter 'P' followed by a digit) will help you to keep your unit operating at its peak performance.

To access the parameters, enter the Unit configuration menu

 

 on the control terminal.

The parameters are grouped into 3 families:

Machine parameters

Adjustment parameters

Reading parameters

Machine parameters

The Machine parameters are used to quickly configure the heat pump in accordance with the system.

IMPORTANT:

 Only qualified personnel may access the machine parameters.

Setting P99

For security reasons relating to the operation of the heat pump, parameter P99 is used 

to lock the machine parameter values  . 

Once configuration is complete, make sure that machine parameter P99 is locked by selecting 
the value YES in the setting field. 

A key symbol appears in front of the machine parameters number to indicate that the 
parameters are no longer modifiable.

If machine parameter P99 is not locked (P99=NO), it is not possible to start up the heat pump: The On/Off button   is 

not visible in the main menu.

MACH. PARAMETERS

 09 cHauffage piScine

no

UNIT CONFIGURATION

c

ommiSSioning

m

acH

parameTerS

a

djuST

parameTerS

r

eading

 

parameTerS

Содержание GeoCIAT

Страница 1: ...Instruction manual GeoCIAT TM Modular 07 2016 NA 13 14 E...

Страница 2: ......

Страница 3: ...ONNECT CONTROL 34 5 1 Terminal unit screen display 34 5 2 Accessing the settings 36 5 3 Configuration 37 5 4 Operating modes 42 5 5 Heating elements 44 5 6 On Off control inputs 46 6 SPECIFICATIONS 47...

Страница 4: ...y WARNING Paragraphs preceded by this symbol contain very important information and provisions in particular concerning safety Failure to follow this information may result in danger to operators loss...

Страница 5: ...the transport brackets have been removed 2 Assemble the roof and the 2 side panels between the female couplers fig 2 and the male ball joints on the frame fig 3 3 Fit the GeoCIATTM Modular front panel...

Страница 6: ...instruction manual and the user manual form an integral part of the unit and must therefore be kept safe and ALWAYS handed over if the unit is transferred to a new owner or another system If a manual...

Страница 7: ...o 45 C Powered by 3 x 1 5V LR06 AA batteries Protection rating IP 30 Class II insulation Supplied with wall bracket foot and batteries Outdoor sensor 868 Mhz wireless link Homecontrol IO radio protoco...

Страница 8: ...DIFICATION 01350 CULOZ FRANCE ECHELLE 0 059 FOLIO 1 1 RE FORMAT A3 VERIFIE PAR DATE DESSINE PAR DATE PAC ENS TUYAUX xx xx 06 70 MATIERE SPEC N E T M 70 70 70 508 760 130 1055 5 APPAREIL OU UNITE DESIG...

Страница 9: ...therefore essential to place the control terminal inside the home within the environment to be monitored and away from heat sources chimney radiator sunlight draughts windows doors and areas of activ...

Страница 10: ...gs FS 4 mm flat head slotted screws 5 mm wall plugs which are not supplied using the mounting holes To close the sensor Place the cover on the body Turn the cover clockwise to lock it 2 1 3 GeoCIATTM...

Страница 11: ...ith two spanners could cause the couplings to rupture and may result in the equipment warranty being voided Fasten the water pipes to the walls with brackets lined with highly flexible rubber to preve...

Страница 12: ...rom fine suspended solids risk of clogging or aggressive water iron manganese or chlorine risk of corrosion or deposits We therefore recommended that you have the physical and chemical properties of y...

Страница 13: ...ances do they constitute actual installation diagrams Hydraulic hoses 20 or 40 MPG monopropylene glycol Buried glycol solution loop Filler material Geothermal sensor Return circuit Supply circuit Shut...

Страница 14: ...nection kit mandatory Flexible connection kit mandatory Shut off valves Thermometer pockets Control valves Radio connection Discharge valve Safety valve Outdoor sensor Radio signal Radio signal Radiat...

Страница 15: ...adio signal Radio signal Wire connection HomeConnect Underfloor heating system Safety valve 3 bar DIVIO ZONE 1 ZONE 2 DIVIO Screen filter valve Screen filter valve Automatic degassing device Dual zone...

Страница 16: ...e heating emitters If using an under floor heating cool ing system the UHCS safety thermostat kit option is recommended BOILER 3 bar safety valve mandatory Thermostatically controlled valve Boiler out...

Страница 17: ...below Always dilute the antifreeze with water before adding it to the system Never add them separately Always mix the correct amounts of water antifreeze and corrosion inhibitor in a container before...

Страница 18: ...insulation 1 mm2 3G4 5G1 5 PVC V2K insulation 2 mm2 3G4 5G1 All or nothing inputs Terminal blocks J11 and J12 Input bypass absence Cooling Heating DHW limiter thermostat mm2 0 2 1 Potential free cont...

Страница 19: ...N EN 17 Electrical connection to the board The customer s main supply cable must be routed from the rear of the unit via to the board Customer s main supply cable routing RIGHT VIEW FRONT VIEW TOP VIE...

Страница 20: ...ree way valve WARNING the power cables MUST follow this route To be added as an option e g 4kW GeoCIATTM Modular heating element kit 33H and 45H models 33H and 45H models with integrated starter Custo...

Страница 21: ...r the unit off before carrying out any work Access the electrical section of the heat pump by following the instructions in paragraph 2 3 accessing the electrical section Make sure that the 6 spacing...

Страница 22: ...accelerator pump 1 Neutral 1 Live 2 Live 2 Neutral 1 2 3 4 1 2 3 Three phase electric heating element supply 3P x 400V 50Hz Phase 3 T Phase 1 R Neutral Phase 2 S Earth J5 J9 J4 J2 J3 J1 Live Neutral...

Страница 23: ...he screen one at a time 1 Select the language 2 Set the date 3 Set the time 4 Set the altitude at which the heat pump is installed 5 Select the temperature unit Turn the button to change the parameter...

Страница 24: ...t the machine stimulation procedure to pair the radio terminal and the heat pump WARNING the time between powering off and powering up must be observed to ensure successful pairing Pairing the termina...

Страница 25: ...ars on the screen for 3 seconds Repeat the heat pump stimulation procedure Press the button Restart the heat pump pairing sequence strictly adhering to the powering up and powering off times Case 3 Th...

Страница 26: ...appear Select Maintenance using the button then CLIC PAIRING SYSTEM pairing Back Heat pump pairing Maintenance Select Element reset using the button then maintenance Range test Back Element reset Sel...

Страница 27: ...seconds c power back up for 10 seconds d power off for 5 seconds e power back up definitively Once the stimulation procedure has been performed select CONFIRM using the button then confirm CLIC Heat...

Страница 28: ...ng procedure 2 Press and hold the PROG button again for 3 seconds until the LED lights up steady green The information on the display C indicates that there is no communication between the terminal an...

Страница 29: ...atible version Activate the stimulation procedure for the new sensor Press the button Restart the sensor pairing sequence Case 4 The sensor has been found but pairing failed Repeat the sensor stimulat...

Страница 30: ...or receive the system key Maintenance This function is used to check the range of the radio signal for each paired component or to erase a component paired with the heat pump Machine unpaired If radi...

Страница 31: ...have a phase controller as standard Electrical connection of the control board may cause the compressor to rotate in reverse This is not harmful to the compressor if it is stopped quickly 2 outcomes a...

Страница 32: ...trongly recommended to install one on the circuit s high point A new function has been integrated on this machine preparation for system start up The GeoCIATTM Modular is equipped with an automatic fu...

Страница 33: ...ay below appears unit parameter Back machine parameters Adjustment parameters COMMISSIONING Select UHCS heating by turning the button then confirm with CLIC commissioning Air bleed Back UHCS heating T...

Страница 34: ...option on the GeoCIATTM Modular The refrigerating block s top cover is easily accessible working on the sensors by removing the 2 roof sections The HP pressure switch is accessed via the front of the...

Страница 35: ...water filters for dirt The filters may need to be checked more frequently Date Time Ambient air temperature P 251 C Ambient air temperature P 250 C Compressor LP pressure P275 bar LP sat temp P268 C...

Страница 36: ...er trend Degrading trend Outdoor temperature in C or F Good weather Variable weather Overcast Rainy Compressor on Electric heating element operation Boiler operating Solar domestic hot water productio...

Страница 37: ...uration Information not visible if the heat pump is not paired see paragraph 3 2 3 Heat pump pairing Unit operating mode setting Operation type setting programmed economy comfort Temperature setpoint...

Страница 38: ...code can be accessed and set Select the YES setting field Set the new code Once the 4th digit has been confirmed the message CODE STORED appears for 5 seconds then the screen reverts to the Level 1 ac...

Страница 39: ...used to control domestic hot water production NOT USED 16 Econo mode signal management NO YES No connection to comfort units V2000 V30 type etc Management of econo mode signal on comfort units NO 17...

Страница 40: ...pump in comfort mode for fan coil unit with or without underfloor heating system 12 C 54 C 20 to 25 C in increments of 1 68 to 77 F in increments of 1 For 1 or 2 underfloor heating systems 23 C 73 C 1...

Страница 41: ...ncrements of 0 5 Setting the frost free air setpoint in zone 2 10 C 47 to P170 in increments of 1 50 F 172 DHW Setpoint 48 to 70 C in increments of 1 118 F to 152 F in increments of 1 Setting the DHW...

Страница 42: ...mperature measured at the compressor discharge 275 LP pressure Relative pressure of the refrigerant fluid measured at the LP pressure sensor 277 HP pressure Relative pressure of the refrigerant fluid...

Страница 43: ...aneous electrical power 401 Inst heat cap Instantaneous heating capacity 402 Inst_tot_abs_power Instantaneous total absorbed power 403 Inst_tot_aux_power Instantaneous total auxiliary power 410 Heatin...

Страница 44: ...trol on the water return depending on the difference between the ambient temperature and the air setpoint Air setpoint P150 hot air setpoint Air setpoint P151 hot air setpoint The maximum water setpoi...

Страница 45: ...ter control with P132 as the water comfort setpoint The air economy setpoint P131 activates the water control with P133 as the water economy setpoint Air setpoint P130 cool air setpoint Air setpoint P...

Страница 46: ...ation authorised Water return temperature P280 Electric heating element only Heat pump electric heating element Heat pump only 55 C Heat pump turned off Heating element authorisation Backup heater onl...

Страница 47: ...ot water contained in the boiler s heating source Operating limit If only the boiler is authorised to operate the control terminal manages the ambient temperature and the controller controls the boile...

Страница 48: ...HEATING To activate heating mode by remote control set parameter P15 to COOLING HEATING Connect a contact to connector J11 terminals 2 and 3 on your unit s HomeConnect control board Contact quality co...

Страница 49: ...r Quantity 1 Type hermetic scroll Oil capacity POE L 0 7 1 24 1 24 1 2 R410A charge kg 1 25 1 35 1 25 1 25 Indoor heat exchanger Type Brazed plate heat exchanger Capacity L 1 06 Indoor hydraulic modul...

Страница 50: ...NN Indoor heat exchanger water return sensor J26 Indoor heat exchanger water outlet sensor J16 Suction temperature sensor J24 Outdoor heat exchanger water return sensor J25 Indoor heat exchanger freon...

Страница 51: ...o the accelerator pumps and the heat pump ensure that the water return on the heat pump remains below 60 C The ambient temperature in the area where the heat pump is installed must be below 40 C to en...

Страница 52: ...strongly advise against powering off your machine The machine must be turned off using the On Off button on the terminal and not electrically Indoor accelerator pump The accelerator pump operates cont...

Страница 53: ...r parameters A limiter thermostat If you connect the machine to an underfloor heating system only see paragraph 2 3 3 1 the thermostat is positioned on the water supply elbow at the outlet of the indo...

Страница 54: ...667 5 42 33 50 3 548 105 0 577 0 32 6 55 2 940 110 0 501 5 25 29 60 2 449 115 0 436 10 19 77 65 2 050 120 0 381 Temperature C Sensor resistance in k Temperature C Sensor resistance in k Temperature C...

Страница 55: ...door exchanger water supply temperature P283 3 C pure water 9 C MPG 40 P96 5 C 45 C 62 C Operating zone heat pump pure water or heat pump glycol water mix Additional operating zone heat pump glycol wa...

Страница 56: ...y reads Outdoor sensor fault A power outage on the heat pump causes an outdoor sensor fault to be displayed The outdoor temperature sensor sends a new signal to the electronic board every 30 minutes T...

Страница 57: ...tions on the HomeConnect board For information on the complete function refer to the relevant section in the operating manual 14 CONTROL BOARD 14 1 Single phase or three phase model electronic board v...

Страница 58: ...at com Compagnie Industrielle d Applications Thermiques Corporation with a capital of 26 728 480 R C S Bourg en Bresse B 545 620 114 This document is not legally binding As part of its continuous driv...

Отзывы: