To change from "USER" mode (restricted access) to "INSTALLER" mode (all
settings), press both arrows on menu scroll button for 5 seconds.
VIII / INSTALLER SETTINGS:
No.
Description
Possible choices
Temperature
:
Used to display the
temperature measured by the
Unit
°C
Min.
0
Reverts to "USER" mode if no buttons are pressed for a period of 30 seconds.
10
p
y
sensor
Read-only
Max.
51
Default
-
Increment
-
Level
:
Used to display the supply air
d
l
t d
Unit
-
Min.
SPeedL
11
speed selected
Read-only
Max.
SPeedH
Default
-
Increment
-
Time
:
Used to set the time
Unit
hh.mm
Min.
00.00
12
Used to set the time
Necessary for correct system operation when
parameter 01 is set to tIME.
Max.
23.59
Default
-
Increment
1 min
WINTER gradient
(on water):
Used to set the gradient to
h th WINTER
d
Unit
°C
Min.
1
13
reach the WINTER mode
setpoint
The longer the gradient (near to 15°C), the more
gradually the heat exchange coils are supplied with
water. Drawback: reaching the temperature setpoint will
be very slow.
The shorter the gradient (near to 1°C), the more rapidly
Max.
15
Default
5
Increment
0.2
SUMMER gradient
(on
water):
Unit
°C
Min
1
the heat exchange coils are supplied with water.
Drawback: the system is similar to On/Off control.
14
Used to set the gradient to
reach the SUMMER mode
setpoint
Min.
1
Max.
15
Default
8
Increment
0.2
ECO differences
:
Unit
°C
Downward shift in WINTER mode:
15
Adjust the difference to the
setpoint using the comfort
mode
Downward shift in WINTER mode:
e.g.
: comfort setpoint 20°C, difference set at 3°C
Î
ECO setpoint = 17°C
Upward shift in SUMMER mode:
e.g.
: comfort setpoint 24°C, difference set at 3°C
Î
ECO setpoint = 27°C
Min.
1
Max.
5
Default
3
Increment
0.5