WINTER LS/HS threshold
:
Defines the limits based on
Unit
V
The higher the threshold (near to 100%), the longer ventilation
22
Defines the limits, based on
parameter 13, for switching
between low and high speed
during WINTER mode
g
(
),
g
will be maintained at low speed (LS).
Advantage: system very quiet, less electricity consumed, less
boiler kWs consumed.
Drawback: achieving the temperature setpoint will be very slow.
In SUMMER mode, the threshold is set by default to 100% in
order to use only LS and thereby ensure that the flow of air
blown across the heat exchange coil does not cause condensate
droplets to form
Min.
0
Max.
100
Default
50
Increment
1
droplets to form.
The lower the threshold (near to 0%), the longer ventilation will
be maintained at high speed (HS).
Advantage: swift building warm-up times.
Drawback: the system is similar to an On/Off control, "energy-
wasting" system.
23
SUMMER LS/HS threshold
:
Defines the limits, based on
parameter 14, for switching
between low and high speed
during SUMMER mode
Unit
V
Min.
0
Max.
100
Default
100
Increment
1
Increment
1
24
Cut-off on setpoint
:
Used to shut off the fans or
keep them on when the
setpoint is reached.
Unit
-
There are two operating modes:
-
YES
: the ventilation is turned off when the setpoint is reached.
-
NO
: the ventilation will remain on (limits stratification in
WINTER mode, circulates air in SUMMER mode).
Min.
-
Max.
-
Default
Yes
Increment
Increment
-
26
Return air/Fresh air or mix
:
Used to run the system with
fresh air or return air
Unit
-
Allows two operating modes when parameter 01 is not set to
tiME (in which case the operating mode will be depend on the
time schedule):
- Air.in: 100% return air.
- Air.out: fresh air or mix (depends on mechanical setting of
damper actuator supplied with the optional fresh air kit).
Min.
-
Max.
-
p
pp
p
)
When fresh air or mixed air is used, the optional fresh air kit
must be installed to protect the coil from frost.
Default
Air In
Increment
-
27
Supply air speed override
time
:
Used to set the fan delay
time
Unit
mn
Parameter 04 is used to manually override the supply air speed
(LS or HS).
Parameter 27 is used to set the duration of the speed override.
When this time elapses the a tomatic speed control (based on
Min.
0
Max.
180
When this time elapses, the automatic speed control (based on
the ambient temperature/temperature setpoint and the clock)
turns back on without any manual intervention by the user.
Default
30
Increment
5
29
Number of power units
controlled:
Used to define the number
of slaves controlled by a
Unit
-
This parameter defines the number of slave units controlled by a
3-PH Eco+ BOX controller.
Min.
1
Max
3
29
master controller
The number entered must correspond to the position of the
switches (see page 7).
Max.
3
Default
1
Increment
-
13
Содержание BOX TRI Eco+
Страница 18: ...XII CERTIFICAT CEM 18 ...
Страница 35: ...XII EMC CERTIFICATE 18 ...
Страница 52: ...XII EMV BESCHEINIGUNG 18 ...
Страница 69: ...XII CERTIFICADO CEM 18 ...
Страница 86: ...XII CERTIFICAZIONE CEM 18 ...
Страница 103: ...XII EMC CERTIFICAAT 18 ...