No.
Description
Possible choices
Temperature
setpoint
in
Unit
°C
5 to 15°C
Min
5
16
p
p
frost protection
mode
5 to 15 C
In SUMMER mode, frost protection mode is turned off
and converted to ECO mode.
Min.
5
Max.
15
Default
8
Increment
0.5
Temperature sensor
calibration
:
Unit
°C
Mi
5
17
To correct sensor
measurements
-
Min.
-5
Max.
5
Default
0
Increment
0.2
Min. WINTER voltage,
terminal
11
(0-10V):
Unit
V
18
terminal
11
(0 10V):
Minimum coil water
supply setting
Terminal
11
is used to control a (0-10V) valve
Min.
0
Max.
Setting 19
Default
0
Increment
0.2
Max. WINTER voltage,
terminal
11
(0-10V):
Unit
V
(
)
actuator (supplied in optional valve kit).
WINTER Min. setting: in WINTER mode in
full fresh
air
use, it is recommended to always supply the heat
exchanger with water so as to prevent it from freezing
(min. setting > 0V)
M
tti
h
i h
t
l
t d b
d
19
terminal
11
(0-10V):
Maximum coil water
supply setting
Min.
Setting 18
Max.
10
Default
10
Increment
0.2
Min. SUMMER voltage,
t
i
l
11
(0 10V)
Unit
V
Max. setting: when air heaters are selected based on
the minimum air mixing rate, the total heat output
delivered is often greater than the building's heat
requirements. This excess output can be reduced by
limiting the maximum voltage delivered by these
terminals (max. setting <10 V)
20
terminal
11
(0-10V):
Minimum coil water
supply setting
Min.
0
Max.
Setting 21
Default
0
Increment
0.2
Max. SUMMER voltage,
Unit
V
21
terminal
11
(0-10V):
Maximum coil water
supply setting
Min.
Setting 20
Max.
10
Default
10
Increment
0.2
12