12.2.11.6 - Operating limits
LD 602R to 3500R units
Water type heat exchanger
Minimum
Maximum
Water inlet temperature at start-up
°C
8
40
Water outlet temperature during operation
°C
5
20
Air-cooled exchanger
Minimum
Maximum
Outdoor ambient operating temperature
LD units - Full load
°C
-20
47
LD units - Part load
°C
-20
52
(1)
(1) Part load operation permitted above an outdoor air temperature of 47 °C. Contact the manufacturer to select a unit using the electronic catalogue.
12 - OPTIONS
AQUACIAT
POWER
™ LD/ILD
EN-88