Cooling mode operating range
Desuperheater water outlet temperature (°C)
Inlet air temperature (°C)
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
46
44
50
55
60
40
45
50
55
60
65
70
75
80
85
Part load, all sizes
Partial load ILD only
Heating mode operating range
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
15
20
25
30
35
40
45
50
55
60
Outside air temperature (°C)
Heat pump water outlet temperature (°C)
DSH
OFF
Part load
Desuperheater
=
45
to
60°C
Desuperheater
=
60
to
70°C
Desuperheater
=
70
to
80°C
potential load shedding
during the frosting cycle
Desuperheater
LWT
water
outlet
=
80°C
Notes
1. Desuperheater water type heat exchanger ∆T = 10K.
2. The water exchanger is protected against freezing down to -20 °C (with the Water exchanger frost protection option or Hydraulic module (if present) or loop protected
by an antifreeze solution for outdoor temperatures of less than 0 °C)
However, the customer is responsible for protecting the desuperheater water type heat exchanger water loop at outdoor temperatures below 0 °C
3. Operating ranges are guidelines only. Verify the operating range with the electronic catalogue.
Key
Operating range at full load
Extension of the operating range, LD 602 to 1400 unit: frost protection required (see note 2).
Heating mode: Partial load at inlet air temperature between -10 and -15°C.
Cooling mode: Partial load at inlet air temperature above 46°C.
Limited desuperheater power.
Operating range at partial load for ILD only with limited desuperheater power.
Potential load shedding during the defrosting cycle at low outdoor temperatures (see operating range for ILD 602R - 2000R)
Limited desuperheater power. Please refer to the selection in the electronic catalogue.
Desuperheater not operational
Limited desuperheater water outlet temperature
12 - OPTIONS
EN-67