Low-pressure single pump motors for ILD units (Fixed-speed single pump, hydraulic module option)
No.
(2)
Description
(3)
0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R
1
Nominal efficiency at full load and nominal voltage
%
86,4
86,4
86,4
86,4
86,4 87,5 89,6 89,6 89,6 89,6 89,7 89,7
1
Nominal efficiency at 75% of full load and
nominal voltage
%
86,9
86,9
86,9
86,9
86,9 88,2 90,4 90,4 90,4 90,4
90
90
1
Nominal efficiency at 50% of full load and
nominal voltage
%
85,7
85,7
85,7
85,7
85,7 87,5 89,9 89,9 89,9 89,9
89
89
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial
registration number and head office of manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1 Nominal shaft power output at full load and
nominal voltage (400 V)
kW
2,2
2,2
2,2
2,2
2,2
3
4
4
4
4
5,5
5,5
7-2 Maximum input power (400 V)
(4)
kW
2,53
2,53
2,53
2,53
2,53 3,44 4,49 4,49 4,49 4,49 6,17 6,17
8
Rated input frequency
Hz
50
9-1 Nominal voltage
V
3 x 400
9-2 Maximum current drawn (400 V)
(5)
A
4,56
4,56
4,56
4,56
4,56 6,33 7,75 7,75 7,75 7,75 10,40 10,40
10
Nominal speed
r/s - rpm
48 - 2900
11
Product disassembly, recycling or disposal at
end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate company
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific conditions
given in the selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
Low-pressure dual pump motors for ILD units (Fixed-speed dual pump, hydraulic module option)
No.
(2)
Description
(3)
0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R
1
Nominal efficiency at full load and nominal voltage
%
85,9
86,4
87,5
87,5
87,5 87,5 89,6 89,6 89,6 89,6 89,7 89,7
1
Nominal efficiency at 75% of full load and
nominal voltage
%
86,4
86,9
88,2
88,2
88,2 88,2 90,4 90,4 90,4 90,4
90
90
1
Nominal efficiency at 50% of full load and
nominal voltage
%
84,9
85,7
87,5
87,5
87,5 87,5 89,9 89,9 89,9 89,9
89
89
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor name plates,
4
Manufacturer's name and trademark, commercial
registration number and head office of
manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1 Nominal shaft power output at full load and
nominal voltage (400 V)
kW
1,5
2,2
3
3
3
3
4
4
4
4
5,5
5,5
7-2 Maximum input power (400 V)
(4)
kW
1,76
2,53
3,44
3,44
3,44 3,44 4,49 4,49 4,49 4,49 6,17 6,17
8
Rated input frequency
Hz
50
9-1 Nominal voltage
V
3 x 400
9-2 Maximum current drawn (400 V)
(5)
A
3,17
4,56
6,33
6,33
6,33 6,33 7,75 7,75 7,75 7,75 10,40 10,40
10
Nominal speed
r/s - rpm
48 - 2900
11
Product disassembly, recycling or disposal
at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate company
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the specific conditions
given in the selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 2019/1781 concerning the application of directive 2009/125/EC on the ecodesign requirements for electric motors.
(2) Item number imposed by regulation No. 2019/1781, annex I2b.
(3) Description given by regulation No. 2019/1781, annex I2b.
(4) To obtain the maximum input power for a unit with a hydraulic module, add the "maximum operating input power" for the unit (see Electrical data table) to the pump
power.
(5) To obtain the maximum operating intensity for a unit with a hydraulic module, add the "maximum operating intensity" for the unit (see Electrical data table) to the pump
intensity.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
AQUACIAT
POWER
™ LD/ILD
EN-20